Dwyer Series 616D DIN Rail Differential Pressure Transmitter

Description

Series 616D DIN rail differential pressure transmitter

The Dwyer Series 616D is a differential pressure transmitter housed in a narrow case that clips onto a 35 mm DIN rail. It senses the pressure difference of air and compatible gases and outputs 4-20 mA in a 2-wire loop or 0-10 V DC in 3-wire operation, with the unusual option of using the current and voltage outputs simultaneously. Accuracy is ±0.25 % of full scale, and zero and span push buttons are provided for calibration checks.

Seven Star LLC supplies the Series 616D in Oman and the GCC as an independent supplier in Muscat. The sections that follow describe the model structure, electrical behaviour and application points.

Series 616D ordering code

The product code is built from the series, a range number and optional suffixes, for example 616D-5-NIST. The range numbers are -2 for 0 to 6 in w.c., -3 for 0 to 10 in w.c., -4 for 0 to 20 in w.c., -5 for 0 to 40 in w.c., -6 for 0 to 100 in w.c., -7 for 0 to 200 in w.c. and -8 for 0 to 10 psid.

Options on the datasheet are -C0C for a certificate of calibration, -FC for factory calibration and -NIST for a NIST traceable calibration certificate.

Technical specifications of the Series 616D

Parameter Specification
Manufacturer / part number Dwyer / Series 616D
Service Air and non-combustible, compatible gases
Accuracy ±0.25 % FS at 77 °F (25 °C)
Thermal effect ±0.036 % FS/°C
Stability ±1 % FS/year
Output 4-20 mA (2-wire); 0-10 V DC (3-wire); simultaneous current and voltage possible
Power 10-35 V DC (2-wire); 17-36 V DC or isolated 21.6-33 V AC (3-wire)
Loop resistance Current: 0 … 1250 Ω max.; voltage: 1 kΩ min.
Current consumption 40 mA max.
Adjustments Zero and span push buttons
Temperature limits 14 … 185 °F (-10 … 85 °C)
Process connections 1/8 in female NPT; two barbed fittings for 1/8 and 3/16 in ID tubing supplied
Electrical connections Screw-type terminal block
Mounting Vertical, 35 mm DIN rail
Weight 4.8 oz (136 g)
Agency approval CE

How the Series 616D is applied

The sensor compares the pressures on its two ports and the electronics provide a conditioned output. The standard two-wire current output is the robust choice for long cable runs and noisy environments, while the 3-wire voltage output suits short runs to building controllers. The simultaneous output feature means that a PLC can read the current while a local meter or a test instrument reads the voltage from the same unit.

The zero and span controls help to check and correct small calibration shifts, but they are not designed for re-ranging, so the correct range number should be ordered. Because the case is made for a DIN rail, several transmitters can be mounted close together in a panel, which reduces cabling and puts all instruments near the I/O cards.

The wide ambient range, -10 to 85 °C, is greater than that of the 616KX and 616W models and suits warm panels.

Series 616D among related models

Choose the 616D when transmitters are to be gathered in a control panel with pneumatic tubing brought to the panel, for example when many duct or filter taps are collected. The Series 607D is the DIN rail model with lower ranges (0 to 0.1 in w.c.), and the Series 616KX is the smaller OEM module.

For outdoor mounting without a panel, the Series 616W is the weatherproof alternative.

Selection and ordering checklist for the Series 616D

  • Range number and the maximum pressure that can occur
  • Output: current, voltage or both
  • Supply type: 2-wire or 3-wire
  • Calibration paperwork required
  • Panel DIN rail space and tubing arrangement
  • Ambient temperature in the panel

Installing the Series 616D

Clip the unit onto the rail in a vertical position, run tubing from the sensing points to the NPT ports (or use the barbed fittings supplied), and wire the terminal block following the current output, voltage output or simultaneous output diagrams in the datasheet.

After power-up, zero the unit with both ports at the same pressure. Check the span at an applied pressure in the middle of the range, and record the readings. The stability of 1 % per year suggests annual verification in critical duties.

Typical applications in Oman and the GCC

Air handlers, duct pressure, variable air volume systems and filter monitoring are named in the datasheet. In Gulf facilities, central plant rooms, data centres and clean areas use differential pressure for filter condition and room pressurization, and the DIN rail case keeps these devices in the panel next to the controllers.

Range options for the Series 616D

From the ordering chart.

Code Range
616D-2 0 … 6 in w.c.
616D-3 0 … 10 in w.c.
616D-4 0 … 20 in w.c.
616D-5 0 … 40 in w.c.
616D-6 0 … 100 in w.c.
616D-7 0 … 200 in w.c.
616D-8 0 … 10 psid

Information to send with an RFQ for the Series 616D

Please send the following.

  • Range code and units
  • Output type
  • Calibration certificate type
  • Quantity and delivery date

Site conditions in Oman for the Series 616D

Field instruments in Oman are exposed to strong sun, high ambient temperature, wind-blown dust and, on coastal plants, salt in the air. When you specify the Series 616D, check the ambient and process temperature limits, the enclosure rating and the wetted and housing materials against the actual installation point, and consider sunshades for transmitters mounted in direct sunlight. Cable entries should be sealed with suitable glands so that dust and moisture cannot enter the housing.

Calibration and verification planning matters as much as selection. Record the range, configuration and tag data of each Series 616D at commissioning, define a check interval that suits the criticality of the loop, and keep the certificates with the plant documentation so that audits and shutdown work can proceed without delay.

Documents and quotation

The manufacturer datasheet for the Series 616D is attached on this page, so the electrical data, terminal assignment and ambient limits quoted above can be checked against the original document before an order is placed.

Seven Star LLC supplies Dwyer products in Oman and the GCC as an independent supplier in Muscat. Send the quantity, the signal types and the project delivery date, and we will confirm availability and lead time in a written quotation.

Other Models in the Dwyer 616 Range

Seven Star LLC supplies models from the Dwyer 616 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Dwyer Series 616KX Compact DP TransmitterPressure InstrumentationView details
Dwyer Series 616W Weatherproof DP TransmitterPressure InstrumentationView details
Dwyer Series 616D DIN Rail Differential Pressure TransmitterPressure InstrumentationYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Dwyer Series 616D Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Dwyer Instruments is an American maker of pressure, flow, level and temperature instruments, founded in Chicago in 1931 as F.W. Dwyer Manufacturing Company to make liquid-filled manometers. It later moved to Michigan City, Indiana, and became known for the Magnehelic differential pressure gauge. Dwyer bought OMEGA Engineering in 2022, and the combined business trades as DwyerOmega.

Seven Star LLC sources and supplies Dwyer instruments for projects and plant maintenance in Oman and the GCC, and checks each order code against the manufacturer's documentation.

Dwyer Instruments company profile

Founded 1931, Chicago, Illinois
Original name F.W. Dwyer Manufacturing Company
Headquarters Michigan City, Indiana
Group DwyerOmega, since 2022
Product families Magnehelic gauges, Photohelic switch gauges, Series 626/628 pressure transmitters, MSX Magnesense transmitters, Flotect flow switches

Milestones

  • 1931: F.W. Dwyer Manufacturing Company is founded.
  • 2022: Dwyer acquires OMEGA Engineering.

Dwyer product families on this page

Four Dwyer lines are listed. The Magnehelic 2000 is a diaphragm-type differential pressure gauge for air and compatible non-combustible gases. The Photohelic 3000MR and 3000MRS combine the gauge with switching, with relay (MR) or solid-state (MRS) outputs. The Series MSX Magnesense is a differential pressure transmitter for building and HVAC air systems. The Flotect V6 is a flow switch; the listed V6EPS-S-S-4-S version is SPDT, in stainless steel, for 1-1/4 inch lines.

Dwyer Instruments products we list

Family Examples
Pressure Instrumentation Dwyer Magnehelic 2000 Differential Press…, Dwyer Photohelic 3000MR/3000MRS Differen…, Dwyer Series 626/628 Industrial Pressure…, Dwyer Series MSX Magnesense Differential…
Flow Indicators & Switches Dwyer V6EPS-S-S-4-S Flotect Flow Switch

Ordering Dwyer instruments: what we need

Send the full model number from the dial or label, because the range is part of it: a 2000-series Magnehelic number changes with the scale and the units. For Photohelic units add the supply voltage and output type. For Dwyer pressure transmitters state range, output signal and display option. For flow switches give line size, medium, wetted material and enclosure type. Recent paperwork may carry the DwyerOmega name; the model numbers stay the reference.

Facts checked against DwyerOmega's Dwyer brand page and HVAC Today, October 2026.

FAQ

Questions about the Dwyer Series 616D DIN Rail Differential Pressure

Answers from our engineering team on installation, compatibility and integration.

01How is the Series 616D mounted?
Vertically on a 35 mm DIN rail inside a panel.
02What outputs does it provide?
4-20 mA in a 2-wire loop or 0-10 V DC in 3-wire operation, and the datasheet shows a simultaneous current and voltage wiring.
03What is the temperature range?
14 to 185 degrees F (-10 to 85 degrees C).
04What process connections are fitted?
1/8 inch female NPT, with two barbed fittings supplied for tubing.
05What calibration documents can be ordered?
A certificate of calibration, factory calibration or a NIST traceable calibration certificate.