Brand: TDK Electronics (EPCOS)
TDK B32305A4252B040 DeltaCap X Black 25 kvar 440 V Capacitor
Description
A black-can PFC capacitor for 440 V low-voltage banks
The TDK B32305A4252B040 is a DeltaCap X Black premium capacitor from the EPCOS power factor correction range, type designation MKD440-D-25.0-X. It is a three-phase unit with an internal delta connection, rated 25 kvar at 50 Hz (30 kvar at 60 Hz) on a 440 V AC rating, built around polypropylene film in a round, black-painted extruded aluminium can with a threaded mounting stud. Discharge resistors are already integrated, so the can is ready to be connected to a contactor-switched step of a capacitor bank.
This ordering code sits at the upper end of the single-can range for the series: 3 x 137 uF in a 136 x 245 mm can weighing about 4.2 kg. A smaller step in the series is B32305A4202B040 (20 kvar, 3 x 110 uF) with the same can size.
Technical specification from the datasheet
| Parameter | Specification |
|---|---|
| Ordering code / type | B32305A4252B040 / MKD440-D-25.0-X |
| Series | PFC DeltaCap X Black premium capacitors (film capacitors for power factor correction) |
| Rated capacitance CR | 3 x 137 uF, tolerance -5 / +5 % |
| Connection | D (internal delta), three-phase |
| Rated voltage VR | 440 V AC |
| Rated frequency / output | 50 Hz: 25.0 kvar, 32.8 A; 60 Hz: 30 kvar, 39.4 A |
| Maximum voltage | VR + 10 % up to 8 h daily; + 15 % up to 30 min daily; + 20 % up to 5 min daily; + 30 % up to 1 min daily |
| Maximum current Imax | Up to 1.5 x IR, including harmonics, overvoltage and capacitance tolerance |
| Inrush current IS | Up to 500 x IR; 1000 switchings per year at 500 x IR, 6200 per year at 400 x IR, 62 000 per year at 300 x IR |
| Power dissipation (without discharge resistors) | 0.2 W/kvar dielectric, 0.5 W/kvar total |
| Test voltages | Terminal to terminal 2.15 x VR for 2 s (tolerance +/-50 V AC); terminals to case 3000 V AC for 10 s |
| Loss factor tan delta | 50 Hz at rated voltage: max 0.5 x 10-3; at 1 kHz: max 7.0 x 10-3 |
| Climatic category | -40/D; Tmin -40 C, Tmax +65 C, hot-spot max +85 C; storage -40 to +85 C |
| Mean life expectancy | Up to 300 000 h at class -40/55; 200 000 h at -40/60; 100 000 h at -40/65 |
| Humidity / altitude | Below 95 % average RH; up to 4000 m |
| Dimensions (d x h) / weight | 136 x 245 mm / approx 4.2 kg |
| Impregnation | Non-PCB soft polyurethane resin filling, biodegradable |
| Terminals | Screw clamp terminals, M6, max torque 3.5 Nm; cross section 35 mm2; max terminal current 100 A |
| Protection degree | IP20 |
| Creepage / clearance (min) | 19.1 mm / 19.1 mm |
| Fixing | M12 bolt at can bottom, max 10 Nm; vertical preferred |
| Safety | Overpressure disconnector; self-healing; discharge resistor to 75 V or less within 60 s |
| Short-circuit rating | AFC 10 kA according to UL 810, UL file E489229 (as printed) |
| Reference standards | IEC 60831-1/2 (2014) and UL 810 5th edition |
| Packing unit | 4 pieces |
Selection and ordering guide
The datasheet is organised by ordering code, so each rating in the series has its own PDF. For this code the rating is fixed: 440 V, 25 kvar at 50 Hz. Reactive output falls with the square of the applied voltage; the can label shown in the photo lists 22.2 kvar at 415 V and 20.6 kvar at 400 V for the 50 Hz rating.
- The 440 V rating suits 400 or 415 V networks where voltage rise or harmonics may lift the capacitor voltage; the datasheet permits VR + 10 % for up to 8 hours a day.
- Size short-circuit protection at 1.6 to 1.8 times the rated capacitor current as per the datasheet: 1.6 x 32.8 A is about 52 A, 1.8 x 32.8 A about 59 A (derived arithmetic, check the fuse series you use).
- Connecting cables and protection must carry 1.5 x IR continuously, which is about 49 A at 50 Hz (derived).
- Packing unit is 4 pieces.
Installation and operation notes
Leave at least 12 mm above every can so the overpressure disconnector can extend, use flexible leads, and do not clamp the folding beads. Use the threaded bottom stud for earthing, remove the varnish under the washer and nut if the chassis is used as the earth path, and keep within the 12 Nm limit given in the earthing paragraph (the mounting table gives 10 Nm for the M12 stud).
Before switching in again, discharge to 10 % of rated voltage; the built-in resistors reach 75 V or less within 60 s. HRC fuses are for short-circuit protection only and must not be used to switch capacitors. Use a thermal-magnetic relay for overload protection, read the current twice a year with a true-RMS meter, and consider detuned (reactor) banks when non-linear loads grow. A dent deeper than 1 mm rules the capacitor out of use.
Applications in GCC power systems
Oil and gas facilities, petrochemical plants, desalination and pumping stations and large air-conditioning plants run many induction motors that depress power factor. A 25 kvar DeltaCap X Black can is a common step size for automatic banks in indoor motor control centres and substations. The datasheet limits the series to indoor mounting, naturally air cooled or with forced cooling; at 65 C ambient the class falls to 100 000 h, so in hot switchrooms check the cabinet temperature rise and ventilation. The datasheet warns against chloride or sulphide gas atmospheres and calls for regular terminal cleaning in dust, both relevant to coastal and desert sites.
Related items
A complete step needs a capacitor contactor such as the TDK B44066S2410J230, a power factor controller and, for networks with harmonics, a harmonic filter reactor. See the electrical and power category and confirm the exact code and voltage with us before ordering.
Frequently asked questions
What is B32305A4252B040?
It is the ordering code of the TDK (EPCOS) DeltaCap X Black capacitor type MKD440-D-25.0-X: a three-phase, delta-connected power factor correction capacitor rated 440 V AC, 25 kvar at 50 Hz and 30 kvar at 60 Hz.
What is the rated current?
The datasheet lists 32.8 A at 50 Hz and 39.4 A at 60 Hz. Imax can reach 1.5 x IR including harmonics, overvoltage and capacitance tolerance.
Can it be mounted outdoors?
No. The datasheet lists indoor mounting with natural air cooling or forced air cooling, and protection degree IP20 at the terminals.
Does it include discharge resistors?
Yes, integrated discharge resistors are provided. They bring the voltage down to 75 V or less within 60 s according to the datasheet.
Who supplies this part in Oman?
Seven Star LLC is an independent supplier in Muscat and not the manufacturer. Confirm the code, voltage and quantity with us before ordering.
Datasheets & Documents
- Datasheet TDK DeltaCap X Black B32305A4252B040 datasheet (ordering code B32305A4252B040, MKD440-D-25.0-X, 02-12-2018) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
TDK Electronics, which still markets many components under the EPCOS name, is the electronic components and power quality business of TDK Corporation, the Tokyo-based group established in 1935. Its published data sheets cover power factor correction capacitors, capacitor contactors, EMC filters, line and output reactors and LCL filters for drives.
Power factor correction and harmonic filtering
The TDK PFC range includes DeltaCap X Black film capacitors, capacitor contactors for switching capacitor banks, power factor controllers, thyristor modules, harmonic filter reactors and FilterCap gas-filled capacitors for inverter filters.
EMC filters and drive components
For converters and power electronics TDK lists single-phase, three-line and four-line EMC power line filters, IEC inlet filters, three-phase line reactors, dv/dt output reactors and LCL filters for active infeed converters.
Supply from Muscat
Seven Star LLC supplies selected TDK Electronics (EPCOS) items to industrial customers in Oman and the GCC, with the official data sheet attached to every product page.
Related products
Frequently Asked Questions
It is the ordering code of the TDK (EPCOS) DeltaCap X Black capacitor type MKD440-D-25.0-X: a three-phase, delta-connected power factor correction capacitor rated 440 V AC, 25 kvar at 50 Hz and 30 kvar at 60 Hz.
The datasheet lists 32.8 A at 50 Hz and 39.4 A at 60 Hz. Imax can reach 1.5 x IR including harmonics, overvoltage and capacitance tolerance.
No. The datasheet lists indoor mounting with natural air cooling or forced air cooling, and protection degree IP20 at the terminals.
Yes, integrated discharge resistors are provided. They bring the voltage down to 75 V or less within 60 s according to the datasheet.
Seven Star LLC is an independent supplier in Muscat and not the manufacturer. Confirm the code, voltage and quantity with us before ordering.