Brand:

Parker 7341NAKBHNM0 Lucifer Series Solenoid Valve

Description

Parker 7341NAKBHNM0 overview

The Parker 7341NAKBHNM0 is a Parker Lucifer solenoid valve reference from the 7341NAKB group of NAMUR-mounted spool valves. In the Parker Lucifer catalogue, these are pilot-operated 3/2 or 5/2 valves that mount directly on the NAMUR interface of rotary pneumatic actuators used on quarter-turn process valves. The family has an anodised aluminium body with NBR seals and a 1/4 inch interface, and is designed for dry or lubricated compressed air.

The published Parker tables reviewed list the closely related references 7341NAKBJNM0 (Lucifer 341N31), 7341NAKBJPM0 (341N3108, low-temperature version) and 7341NAKBHN90 (341N3190). The exact meaning of the H character in the Parker 7341NAKBHNM0 was not found in the manufacturer literature, so any option it encodes should be confirmed against the manufacturer datasheet or the valve nameplate. Seven Star LLC supplies the Parker 7341NAKBHNM0 on request for actuator-control applications in Oman and the GCC.

Key features of the Parker 7341NAKBHNM0 valve family

  • Direct NAMUR mounting: The interface follows the NAMUR standard and the VDI/VDE 3845 recommendations, so the valve bolts directly onto the actuator with no tubing between them.
  • 3/2 or 5/2 function: The same valve can be set up for single-acting (spring-return) or double-acting actuators. Check the function on the installed valve.
  • Re-breather function: In 3/2 operation, the air from the actuator spring chamber flows back through the pilot valve. Parker states this prevents corrosion of the actuator springs.
  • Pilot-operated spool: Gives a high flow from a compact body with a low-power coil.
  • Manual override: Fitted as standard across the range, for testing and commissioning.
  • Coil compatibility: The N3x series accepts Parker Lucifer electrical group 2 coils (8/9 W), including ATEX versions, according to the catalogue.

Technical specifications (341N31 family data)

The values below are taken from Parker data for the 341N31 NAMUR spool valve (global reference 7341NAKBJNM0). Confirm each value for the Parker 7341NAKBHNM0 against the manufacturer datasheet before ordering.

Parameter Specification
Reference 7341NAKBHNM0 (H option: confirm against the manufacturer datasheet)
Family Parker Lucifer 341N, NAMUR interface, spool design
Function 3/2 or 5/2, pilot operated
Body / seals Anodised aluminium / NBR
Port size (as listed) 1/4 – 1/8 inch, 1/4 inch NAMUR interface
Nominal orifice 4 mm
Flow, Qn 600 L/min
Pressure range 2–10 bar (AC and DC)
Fluid temperature (air) –25 to +80 °C
Ambient temperature –25 to +50 °C
Media Dry or lubricated air
Coil housing / coil (catalogue) Housing 2995 with coil 481865
Power consumption 9 W DC / 8 W AC
Assembly weight Approx. 510 g
Coil voltage Confirm against the manufacturer datasheet or the coil label

Operating principle

The Parker 7341NAKBHNM0 is a pilot-operated spool valve. When the coil is energised, a small pilot stage lets supply pressure act on the main spool. The spool then shifts and connects the supply to the actuator port. When the coil is de-energised, the spool returns by a combination of spring and air pressure.

  • 3/2 function: Pressurises one chamber of a spring-return actuator, and the spring returns the valve to its safe position when the signal is removed. The re-breather path sends the exhausting air into the spring chamber instead of drawing in ambient air.
  • 5/2 function: Drives both chambers of a double-acting actuator, alternately pressurising and exhausting the two sides.

Because the valve is pilot operated, it needs at least 2 bar of supply pressure to shift reliably.

Typical applications

  • On/off control of ball, butterfly and plug valves fitted with pneumatic rack-and-pinion or scotch-yoke actuators.
  • Water and wastewater plants, desalination and pumping stations.
  • Oil and gas, petrochemical and chemical process skids. Hazardous-area use depends on the coil fitted.
  • Food and beverage, pharmaceutical and powder-handling lines.

Parker 7341NAKBHNM0 selection and reference notes

The Parker global reference is a coded number, but this research found no public decoding of every character. Parker tables reviewed show these related references:

  • 7341NAKBJNM0: 341N31, –25 to +80 °C, coil housing 2995, coil 481865.
  • 7341NAKBJPM0: 341N3108, rated down to –40 °C fluid temperature.
  • 7341NAKBHN90: 341N3190, a variant with a different coil (483580.01) and 400 L/min flow.

Do not substitute one reference for another without checking. When replacing a valve, read the full global reference, the Lucifer reference and the coil label (part number, voltage and frequency) from the installed unit. Then check the function (3/2 or 5/2), the supply pressure and any hazardous-area requirement.

Installation and commissioning

  • Clean the actuator NAMUR face and fit the valve with its gasket and screws. Align the dowel pins so that the valve sits in the intended 3/2 or 5/2 orientation.
  • Supply filtered, dry or lubricated air between 2 and 10 bar. Fit exhaust silencers or protective plugs suitable for the site.
  • Wire the coil to the voltage on its label, using a connector and cable gland suited to the enclosure rating required.
  • Test the actuator stroke with the manual override before energising the coil, then check the stroke from the control system.

Maintenance and troubleshooting

  • If the valve does not shift, measure the coil voltage and resistance, and confirm that the supply pressure is above the 2 bar minimum.
  • Slow or partial strokes often come from dirty air, a blocked exhaust or swollen seals. Use clean, dry air, especially in humid coastal sites.
  • Persistent leakage at the exhaust points to worn spool seals or debris in the valve.
  • In hot outdoor installations, check that the coil and body stay within the 50 °C ambient limit, for example by shading the actuator.
  • Before replacing a Parker 7341NAKBHNM0, record the coil part number, voltage and function so that the new unit can be checked against them.

Quotation enquiries for Oman and the GCC

Seven Star LLC supplies the Parker 7341NAKBHNM0 on request. Availability, condition and lead time are confirmed at quotation. Please send:

  • The full part number and quantity.
  • Photos of the valve nameplate and coil label.
  • The coil voltage.
  • The actuator type.

Technical support with selection and cross-checking of the reference is available.

Datasheets & Documents
  • PDF Instruction Manual Parker Lucifer Solenoid Valves General Catalogue Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Parker Hannifin is an American manufacturer of motion and control technologies, founded in 1917 in Cleveland, Ohio, by Arthur L. Parker as the Parker Appliance Company. Its first product was a pneumatic brake system for trucks and buses. In 1957 the company bought Hannifin, a maker of hydraulic and pneumatic cylinders and valves, and took the Parker Hannifin name. It is headquartered in the Cleveland area and listed on the New York Stock Exchange.

Seven Star LLC supplies the Parker items that maintenance teams request most: Lucifer solenoid valves, including NAMUR types for actuated valves, along with filter elements and hydraulic gear pumps.

Parker company profile

Founded 1917, Cleveland, Ohio, USA, by Arthur L. Parker
Headquarters Cleveland area, Ohio, USA
Ownership Public company, New York Stock Exchange (PH), listed since 1964
First product Pneumatic brake system for trucks and buses
Product families Hydraulic pumps, cylinders and valves, pneumatic valves and FRLs, instrumentation fittings and valves, hoses and couplings, filtration (including Racor and Velcon), seals and O-rings

Milestones

  • 1917: Arthur L. Parker starts the Parker Appliance Company in Cleveland.
  • 1924: Parker restarts the business after a 1919 accident destroyed its inventory.
  • 1957: Parker acquires Hannifin and becomes Parker Hannifin.
  • 1964: The shares are listed on the New York Stock Exchange.

Parker product lines listed here

Most of the listing is Lucifer, the Parker solenoid valve line that many nameplates still show as a brand in its own right. The 341N types (341N01, 341N22, 341N31) are NAMUR-interface valves that bolt straight onto a pneumatic actuator to pilot it. The E131K03 is a direct-acting 3/2 valve, and the 322K4706 and 7341NAKBHNM0 are further Lucifer solenoid valves. Parker sells Lucifer valve bodies and their coils or electrical parts as separate items, so one body can be combined with different voltages and enclosure types.

Other Parker lines appear: a hydraulic gear pump (P51A478BEY25-07-ZY), a coalescing filter element (9000040001) and a Triple-Lok 37-degree flare tube fitting.

Where Parker components are used

Lucifer NAMUR valves sit on quarter-turn actuators for on-off and shutdown valves in oil and gas, power and water plants across the GCC. Line-mounted solenoid valves switch instrument air, water, steam and light oils on skids and machines. Gear pumps drive hydraulic power units and mobile equipment, and coalescing elements protect instrument air and gas sampling systems from oil and water aerosols.

Parker products we list

Family Examples
Solenoid Valves 7341NAKBHNM0 Lucifer Series Solenoid Valve, Lucifer 322K4706 2-Way Solenoid Valve, Lucifer 341N01 NAMUR Solenoid Valve, Lucifer 341N22 SOLENOID VALVE, Lucifer 341N31 NAMUR Solenoid Valve, Lucifer E131K03 Solenoid Valve
Filtration Elements 9000040001 Coalescing Filter Element
Pumps P51A478BEY25-07-ZY Hydraulic Gear Pump
Pipes & Fittings Triple-Lok 37° Flare Tube Fitting

Ordering Parker parts: what we need

Parker part numbers are long and every character counts. Please send:

  • Solenoid valves: valve number from the body, coil or electrical part number, voltage and frequency, and the Ex marking if the coil is certified
  • Gear pumps: the complete code from the nameplate, including the assembly number, which fixes displacement, shaft, ports and rotation
  • Filter elements: element number and the housing model it fits

A photo of the nameplate is welcome. We check the code against Parker documentation and identify the manufacturer's current equivalent if a number has been superseded.

Facts checked against Parker's centennial timeline and the Encyclopedia of Cleveland History, October 2026.

FAQ

Questions about the Parker 7341NAKBHNM0 Lucifer Series Solenoid Valve

Answers from our engineering team on installation, compatibility and integration.

01What is the Parker 7341NAKBHNM0 used for?
It is a Parker Lucifer NAMUR-mount valve from the 341N spool family. It controls single-acting or double-acting pneumatic actuators on quarter-turn process valves.
02Is the Parker 7341NAKBHNM0 a 3/2 or a 5/2 valve?
The 341N NAMUR spool valves are listed for 3/2 or 5/2 operation. Check the function and mounting orientation on the installed valve.
03What pressure does it need?
Parker data for the 341N31 family gives 2 to 10 bar. A minimum of 2 bar is needed for the pilot to shift the spool.
04What coil does it use?
Parker lists coil housing 2995 with coil 481865 (9 W DC / 8 W AC) for the 341N31. Confirm the coil and voltage for this reference against the manufacturer datasheet or the coil label.
05How does 7341NAKBHNM0 differ from 7341NAKBJNM0?
The 7341NAKBJNM0 is catalogued as 341N31. The meaning of the H character was not found in the published tables, so confirm it with the manufacturer datasheet.