Schneider Electric GV3P18 TeSys GV3 12-18 A Motor Breaker
Description
GV3P18: rotary handle, thermal-magnetic motor circuit breaker
The GV3P18 belongs to the TeSys Deca GV3 range and is built for motor feeders from 12 A upwards, adjustable up to 18 A. Thermal-magnetic protection, a rotary handle and the datasheet-listed 252 A magnetic trip make it a complete starter-protection device.
Reading the reference against the datasheet: the device short name is GV3P, which the datasheet pairs with a rotary handle and thermal-magnetic trip technology; the digits after the family letters follow the current band, here 12–18 A.
The datasheet gives the range as TeSys Deca and the product name as TeSys GV3, with the application stated as motor protection. Rated operational voltage is 690 V AC 50/60 Hz, rated insulation voltage 690 V AC 50/60 Hz and the rated impulse withstand 6 kV.
GV3P18 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / GV3P18 |
| Range / product name | TeSys Deca / TeSys GV3 |
| Device short name | GV3P |
| Product type | Motor circuit breaker |
| Trip unit technology | Thermal-magnetic |
| Poles | 3P |
| Control | Rotary handle |
| Rated current [In] | 18 A |
| Thermal setting range | 12–18 A |
| Magnetic tripping current | 252 A |
| Conventional thermal current [Ith] | 18 A |
| Rated operational voltage [Ue] | 690 V AC 50/60 Hz |
| Utilisation categories | Category A; AC-3 |
| Phase failure sensitivity | Yes |
| Suitability for isolation | Yes |
| Power dissipation per pole | 8 W |
| Mechanical durability | 50000 operating cycles |
| Electrical durability | 50000 cycles for AC-3 at 415 V In |
| Fixing | 35 mm symmetrical DIN rail: clipped | Panel: screwed (with 3 x M4 screws) |
| Mounting position | Horizontal or Vertical |
| Dimensions H × W × D | 132 × 55 × 136 mm |
| Net weight | 0.96 kg |
| Tightening torque | 5 N.m – on screw clamp terminal |
| IP / IK protection | IP20; IK09 enclosure |
| Operating temperature | -20 to 60 °C |
| Storage temperature | -40 to 80 °C |
| Operating altitude | 3000 m |
| Standards | EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, IEC/EN 60335-1:Clause 30.2, IEC/EN 60335-2-40:Annex JJ |
| Certifications | CB Scheme, CE, UKCA, CCC cULus, EAC, ATEX, LROS (Lloyds register of shipping), BV, ABS, DNV-GL |
GV3P18 compared with neighbouring TeSys GV3 ratings
The table lists the closest GV3 references by current. Moving one step up or down changes the thermal range, the magnetic trip and the motor power it is intended for, while the frame stays the same. Neighbouring references are GV3P25, GV3L40, GV3P40 and GV3L50.
| Reference | Type | Setting / rating | Magnetic trip | Motor kW at 400/415 V |
|---|---|---|---|---|
| GV3P18 (this page) | rotary handle, thermal-magnetic | 12–18 A | 252 A | 7.5 kW |
| GV3P25 | rotary handle, thermal-magnetic | 17–25 A | 350 A | 11 kW |
| GV3L40 | rotary handle, magnetic only | 40 A | 560 A | 18.5 kW |
| GV3P40 | rotary handle, thermal-magnetic | 30–40 A | 560 A | 18.5 kW |
| GV3L50 | rotary handle, magnetic only | 50 A | 700 A | 22 kW |
| GV3P50 | rotary handle, thermal-magnetic | 37–50 A | 700 A | 22 kW |
Among the GV3 references covered here, the rotary thermal-magnetic GV3P units run from 12 A to 65 A and the magnetic-only GV3L units from 40 A to 80 A; the L versions need a separate overload relay.
Using the GV3P18 in Oman and the GCC
Motor starters are everywhere in Gulf plants, and this breaker suits chemical dosing and circulation pumps, cooling-tower fans, small compressors and machine-tool drives. The datasheet lists motor powers up to 15 kW across its voltages, which is what the GV3 frame is built for. Typical sites are desalination and water treatment, power auxiliaries, oil and gas utilities, petrochemical units and commercial HVAC.
Heat and dust drive the real life of a breaker. With an operating limit of -20 to 60 °C and protection of IP20, the device belongs inside a ventilated or air-conditioned enclosure rather than on an open wall in summer sun. For a retrofit, send the nameplate and the old breaker marking and we will match it.
Breaking capacity of the GV3P18 by voltage
Short-circuit breaking capacity falls as system voltage rises, which is the reason to read the whole table instead of a single headline value. The service breaking capacity Ics is shown as a percentage of Icu.
| Voltage | Icu | Ics as % of Icu |
|---|---|---|
| 230/240 V AC | 100 kA | 100 % |
| 400/415 V AC | 100 kA | 100 % |
| 440 V AC | 50 kA | 100 % |
| 500 V AC | 12 kA | 50 % |
| 690 V AC | 6 kA | 50 % |
At 400/415 V AC the rating is 100 kA, which is the figure that matters on most Gulf 400 V distribution boards; compare it with the prospective fault level at the point of installation and with any upstream protection before relying on it.
Motor ratings listed for the GV3P18
The datasheet ties this breaker to specific motor sizes at each supply voltage. These figures are the rated motor powers for the AC-3 category and are what a motor schedule should be matched against, not only the current.
| Supply voltage | Motor power in datasheet |
|---|---|
| 400/415 V AC | 7.5 kW |
| 500 V AC | 9 kW |
| 690 V AC | 15 kW |
Rated duty is uninterrupted, and the durability figures are given in the table of specifications.
Dimensions, terminals and mounting of the GV3P18
The GV3P18 is a larger frame: 55 mm wide, 132 mm high and 136 mm deep, weighing 0.96 kg. It clips to a 35 mm DIN rail or is screwed to a plate with three M4 screws, and it is mounted horizontally or vertically. Terminals are EverLink type with a tightening torque of 5 N.m – on screw clamp terminal.
Environmental limits from the datasheet are -20 to 60 °C in operation and -40 to 80 °C in storage, an altitude limit of 3000 m, and protection IP20. Power dissipation is 8 W per pole, so the heat released inside the enclosure at full load is about 24 W for the three poles; add this to the enclosure thermal budget in a Gulf plant room.
Selection checklist and RFQ details for the GV3P18
- Motor nameplate current and voltage, checked against the 12–18 A range and the motor kW table
- Required control style: rotary handle
- Confirm the dial can be set to the motor full-load current with margin for the start-up duty
- Prospective short-circuit current at the board against the 100 kA rating at 400/415 V
- Terminals: EverLink terminals; check the cable size and ferrule practice
- Space for a 55 mm wide device, 136 mm deep, and ambient heat inside the enclosure
- Accessories such as auxiliary contacts, trip indicators or busbar links if the design uses them
When requesting a quotation, include the following with the part number:
- Part number GV3P18 and quantity
- Motor power, voltage and full-load current
- Replacement or new build, and the existing breaker marking
- Delivery location and required date
How the GV3P18 protects the motor feeder
The thermal element is adjustable from 12–18 A, and the user sets the dial to the motor nameplate current rather than to the top of the range. The magnetic element is fixed at 252 A, which is about 14.0 times the 18 A upper setting; below that level the thermal element handles overloads, above it the breaker opens instantly.
The datasheet confirms phase failure sensitivity, so a motor losing one phase is tripped by the unbalance rather than being left to overheat. A dial set too high defeats the protection and one set too low causes nuisance trips at start, so allow for the starting duty of the load and finish the adjustment at commissioning with a clamp meter.
Documents and quotation
The Schneider Electric manufacturer datasheet for the GV3P18 is attached on this page as a PDF. It is the reference for every rating quoted above, and it is worth checking the revision against your project documents before an order is placed. The utilisation categories, breaking capacity table and environmental limits are all in it.
Seven Star LLC is an independent supplier in Muscat that serves buyers in Oman and the GCC. Send the part number GV3P18, the quantity and the delivery site, and we will reply with a quotation and the availability we can confirm.
Datasheets & Documents
- Datasheet Schneider Electric GV3P18 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric GV3P18 TeSys GV3 12-18 A Motor
Answers from our engineering team on installation, compatibility and integration.
01What current range does the GV3P18 cover?
The thermal setting range is 12–18 A, with a magnetic tripping current of 252 A. Set the dial to the motor nameplate current.
02What is the breaking capacity of the GV3P18 at 400/415 V?
The datasheet gives 100 kA Icu at 400/415 V AC, with the service breaking capacity shown as a percentage of Icu in the table above.
03Does the GV3P18 provide overload protection?
Yes, it has an adjustable thermal element and is sensitive to phase failure, plus a magnetic element for short circuits.
04How is the GV3P18 operated and mounted?
It uses a rotary handle and mounts on a 35 mm DIN rail or on a panel. Size is 55 mm wide, 132 mm high and 136 mm deep.
05What motor powers is the GV3P18 listed for?
7.5 kW at 400/415 V; 9 kW at 500 V; 15 kW at 690 V.