Schneider Electric A9F94325 iC60L 3P 25A C Breaker
Description
A9F94325: three-pole 25 A C-curve iC60L breaker
The A9F94325 is a Schneider Electric Acti9 iC60L miniature circuit breaker, listed as iC60L – miniature circuit breaker – 3P – 25A – C curve. The datasheet describes a 3P thermal-magnetic device rated 25 A with a C trip curve for AC and DC networks, standardised to EN/IEC 60947-2 and EN/IEC 60898-1. Its headline breaking capacity is 50 kA Icu in the 220–240 V AC band. Seven Star LLC supplies the A9F94325 in Oman and the GCC as an independent supplier based in Muscat.
The datasheet for the A9F94325 is dated 8 Nov 2026 and shows no lifecycle warning in its header, but availability should still be confirmed before an order is placed. A 25 A rating is typical for water heaters, larger appliance circuits and feeders to small sub-boards. Add-on residual current protection listed as compatible: Vigi iC60 single terminal add-on residual current device 25/40/63 A; Quick Vigi iC60 single terminal add-on residual current device 25/40 A.
Technical specifications of the A9F94325
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / A9F94325 |
| Range / product name | Acti9 / Acti9 iC60 |
| Device short name | iC60L |
| Poles | 3P (3 protected poles) |
| Rated current [In] | 25 A |
| Curve / trip unit | C curve, thermal-magnetic |
| Network type / frequency | DC and AC, 50/60 Hz |
| Magnetic tripping limit | 8 x In ± 20 % |
| Rated operational voltage [Ue] | 12–133 V AC 50/60 Hz; 220–240 V AC 50/60 Hz; 380–415 V AC 50/60 Hz; 440 V AC 50/60 Hz; up to 180 V DC |
| Rated insulation voltage [Ui] | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Impulse withstand [Uimp] | 6 kV conforming to EN/IEC 60947-2 |
| Standards | EN/IEC 60947-2 and EN/IEC 60898-1 |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 / Yes conforming to EN/IEC 60898-1 |
| Dimensions (H x W x D) | 85 mm x 54 mm x 78.5 mm |
| Rail pitches / weight | 6 pitches of 9 mm; 0.375 kg |
| Terminals | Single terminal, top or bottom: 25 mm² rigid and 16 mm² flexible copper |
| Stripping length / torque | 14 mm; 2 N.m |
| Durability | 20000 cycles mechanical, 10000 cycles electrical |
| Protection degree | IP20 (IEC 60529); IP40 in modular enclosure |
| Operating temperature / altitude | -35–70 °C; 0–2000 m |
| Storage temperature | -40–85 °C |
| Relative humidity | 95 % at 55 °C |
| Colour | White |
Environmental and logistics data for the A9F94325
The datasheet lists operation from -35–70 °C, storage from -40–85 °C, relative humidity of 95 % at 55 °C and tropicalisation class 2, with pollution degree 3. Country of origin is shown as FR and the contractual warranty as 18 months. A total lifecycle carbon footprint of 52 kg CO2 eq. is declared, with a recyclability potential of 54 %. A single unit packs at about 345.500 g, with 4 units in the intermediate carton.
Installation and maintenance of the A9F94325
The A9F94325 clips onto a 35 mm DIN rail. Strip conductors to 14 mm and tighten with a calibrated screwdriver to 2 N.m. Because heavy fault energy is possible, keep conductors short and supported near the terminals.
Inspect periodically for discoloured terminals, a free-moving handle and a clear trip indicator. Mechanical life is 20000 cycles and electrical life 10000 cycles. A breaker that has cleared a large fault should be inspected and normally replaced instead of assumed intact. As a stocked reference, keeping a spare is prudent for critical boards.
3P construction of the A9F94325
A three-pole device opens all three phases together and takes six 9 mm pitches (54 mm). It is intended for three-phase outgoing ways at 380 to 415 V AC. A common trip matters for motors and other three-phase loads, because a phase left energised alone can overheat connected equipment.
The body is 54 mm wide, 85 mm high and 78.5 mm deep and weighs 0.375 kg. A layout should reserve 54 mm of rail per device. Terminals take 25 mm² rigid or 16 mm² flexible copper, tightened to 2 N.m, and the datasheet lists comb busbar and distribution block compatibility at top or bottom.
Reading the C curve and the 25 A rating
The C curve is the general-purpose choice. Its magnetic trip sits at 8 times In (±20 %), high enough to ignore the moderate inrush of lighting drivers, small motors and power supplies, yet low enough to clear most short circuits in ordinary distribution boards. It is the setting most panel builders keep in stock, which is why this family contains so many C-curve references.
On the A9F94325 the datasheet states a magnetic tripping limit of 8 x In ± 20 %, which for 25 A corresponds to an instantaneous trip region starting around 200 A, subject to the ±20 % tolerance. The thermal element handles slower overloads. DC use is also listed (20 kA at up to 180 V DC), so check polarity and voltage against the real circuit before using it on a DC supply.
Information to send with an RFQ for the A9F94325
- Full reference (A9F94325), quantity and whether it is a spare or a new installation
- System voltage, frequency, and AC or DC use at the installation point
- Prospective short-circuit current and the cable or load being protected
- Existing board, neighbouring devices and any add-on residual current device
- Delivery location and required timing
The A9F94325 among iC60L 3P references
The closest neighbours by rating are A9F94320 (C 20 A) and A9F94332 (C 32 A); they share the housing and differ in thermal setting and, in some cases, in curve and breaking-capacity figures. The table lists the 3P references of this iC60L batch.
| Reference | Curve / rating | Icu at 220–240 V AC | Status in datasheet |
|---|---|---|---|
| A9F94310 | C / 10 A | 50 kA | Active |
| A9F94316 | C / 16 A | 50 kA | Discontinued |
| A9F94320 | C / 20 A | 50 kA | Active |
| A9F94325 (this page) | C / 25 A | 50 kA | Active |
| A9F94332 | C / 32 A | 36 kA | Discontinued |
| A9F94340 | C / 40 A | 36 kA | Active |
| A9F94363 | C / 63 A | 30 kA | Discontinued |
| A9F95332 | K / 32 A | 36 kA | Active |
Breaking capacity of the A9F94325 across voltage bands
Icu is the ultimate breaking capacity and Ics the service capacity, quoted as a share of Icu. The iC60L is the high-breaking-capacity member of the iC60 family, and the table shows how the figure changes with voltage for this 3P 25 A reference. The first listed band is 12–133 V AC 50/60 Hz at 70 kA Icu, while the 380–415 V AC band gives 25 kA.
| Voltage band | Icu | Ics |
|---|---|---|
| 12–133 V AC 50/60 Hz | 70 kA | 35 kA (50 % of Icu) |
| 220–240 V AC 50/60 Hz | 50 kA | 25 kA (50 % of Icu) |
| 380–415 V AC 50/60 Hz | 25 kA | 12.5 kA (50 % of Icu) |
| 440 V AC 50/60 Hz | 20 kA | 10 kA (50 % of Icu) |
| up to 180 V DC | 20 kA | 20 kA (100 % of Icu) |
The datasheet also gives a household-standard Icn of 15000 A at 400 V AC 50/60 Hz under EN/IEC 60898-1, and limitation class 3, which describes how strongly the device limits let-through energy. Compare every figure with the prospective fault current at the installation point; if the supply can exceed the band that applies, a different device or upstream back-up is required.
Documents and quotation
A datasheet for the this unit is attached on this page. It lists the electrical, mechanical and environmental data summarised above and should be read with the manufacturer’s installation instructions.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Other Models in the Se Ic60l 3p C Range
Seven Star LLC supplies models from the Se Ic60l 3p C range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric A9F94310 iC60L 3P 10A C Breaker | Circuit Breakers | View details |
| Schneider Electric A9F94316 iC60L 3P 16A C Breaker | Circuit Breakers | View details |
| Schneider Electric A9F94320 iC60L 3P 20A C Breaker | Circuit Breakers | View details |
| Schneider Electric A9F94325 iC60L 3P 25A C Breaker | Circuit Breakers | You are viewing this model |
| Schneider Electric A9F94332 iC60L 3P 32A C Breaker | Circuit Breakers | View details |
| Schneider Electric A9F94340 iC60L 3P 40A C Breaker | Circuit Breakers | View details |
| Schneider Electric A9F94363 iC60L 3P 63A C Breaker | Circuit Breakers | View details |
Datasheets & Documents
- Datasheet Schneider Electric A9F94325 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric A9F94325 iC60L 3P 25A C Breaker
Answers from our engineering team on installation, compatibility and integration.
01What is the rated current and curve of the A9F94325?
The datasheet gives 25 A with a C curve and a thermal-magnetic trip unit. The magnetic tripping limit is 8 x In plus or minus 20 %.
02What breaking capacity does the A9F94325 have at 230 V AC?
The datasheet lists 50 kA Icu in the 220 to 240 V AC band, with a service capacity of 25 kA. Compare it with the prospective fault current at the installation point.
03How wide is the A9F94325 and how many poles does it have?
It is a 3P device, 54 mm wide, 85 mm high and 78.5 mm deep, using 6 pitches of 9 mm on the rail.
04What conductors fit the A9F94325 terminals?
Single terminals at top or bottom accept 25 mm2 rigid and 16 mm2 flexible copper, with a tightening torque of 2 N.m.
05Can the A9F94325 be used on DC circuits?
The datasheet lists AC and DC network types. DC ratings: 20 kA Icu at up to 180 V DC. Verify polarity and voltage against the real circuit.