- Automation & ControlView all 3,067 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Isolator & Barrier
- Controllers & Data Acquisition
- Safety Switches & Guard Locking
- Motor Soft Starters
- Encoders
- CCTV & Security
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Pizzato
Pizzato CS AR-01V120 Safety Module 2NO+1NC, 120 Vac
Description
Overview
Emergency stop buttons and guard switches only protect people when something monitors them and cuts the power reliably. The Pizzato CS AR-01V120 is a safety relay module that does that job: it watches one or two safety channels, checks them for faults and drives two forcibly guided normally open safety contacts plus one normally closed auxiliary contact. It is the 120 Vac member of the CS AR-01 family. Seven Star LLC is an independent supplier serving Oman and the GCC.
What the module does
According to the operating instructions, the module monitors gates and emergency stop devices, using category 4 architecture and reaching PL e under EN ISO 13849-1 and SIL 3 under EN IEC 62061 when it is wired with two redundant channels. A single channel hookup is possible, but the maximum level is reduced, so the circuit diagram you choose determines the safety integrity you can claim. Automatic and monitored start modes are provided through the start terminals, and three LEDs show supply and the state of both channels.
Technical data of Pizzato CS AR-01V120
| Item | Value |
|---|---|
| Supply voltage | 120 Vac, 50 to 60 Hz, tolerance plus or minus 15 percent |
| Power consumption AC | less than 5 VA |
| Safety outputs | 2NO forcibly guided contacts, plus 1NC auxiliary contact |
| Contact material | gold-plated silver alloy |
| Maximum switching voltage | 230/240 Vac, 300 Vdc |
| Maximum current per contact | 6 A; total sum of Ith squared 72 A squared |
| Minimum current / contact resistance | 10 mA / up to 100 milliohm |
| External protection fuse | 4 A |
| Maximum switching load | 1380 VA/W |
| AC-15 / DC-13 | 230 V 3 A / 24 V 4 A |
| Response time tA | less than 300 ms |
| Release time tR1 | less than 20 ms |
| Safety data | up to SIL 3, PL e, category 4; MTTFD 227 years; DC high; PFHD 1.18E-10; mission time 20 years |
| Ambient temperature | minus 25 to plus 55 degrees C; storage minus 25 to plus 70 degrees C |
| Housing | polyamide PA 66, self-extinguishing V0 per UL 94; IP40 housing, IP20 terminals |
| Terminals | wires 0.2 to 2.5 square mm (24 to 12 AWG), torque 0.5 to 0.6 Nm |
| Insulation | Ui 250 V, Uimp 4 kV, overvoltage category II, pollution degree external 3 and internal 2 |
| Endurance | over 10 million mechanical and over 100,000 electrical cycles |
How CS AR-01V120 differs from other CS AR-01 modules
The family shares one safety function but differs in supply: the CS AR-01 with code letter 024 runs on 24 Vac/dc, the 120 version here on 120 Vac, the 230 version on 230 Vac, and the E02 type on 10 to 30 Vdc with a faster response time below 150 ms. The 120 Vac supply means the module can be fed from a mains-derived control supply, whereas the 12 and 24 V versions must be fed from a SELV or PELV source. Typical power consumption for the AC versions is below 5 VA.
Where it is used in Oman and the GCC
Machine builders and plant maintenance teams use modules like this on presses, packaging lines, conveyors, robot cells and processing plant where an emergency stop must disconnect contactors. The 120 Vac input suits panels built to US-style control voltages that are still common on imported skids in the Gulf. Because the outputs switch up to 6 A per contact, they are normally used to drive external contactors with forcibly guided contacts, which are then monitored in the feedback loop.
Wiring and commissioning the Pizzato CS AR-01V120
Always place the 4 A protection fuse in series with the output contacts and a protection device in the supply. Wire emergency stop contacts to the input terminals as shown in the diagrams, connect the start circuit, and add the feedback contacts of the external contactors if monitored start is required. After power-up, test each safety input and verify that both channels drop the outputs. Pizzato stresses that a functional test must be repeated at regular intervals and that the module should be replaced entirely if the housing is damaged. Discharge static before handling and mount the module on a DIN rail with the clip provided.
Fault finding
The manual relates LED patterns to causes. If the power LED is off, look for wiring faults, a broken fuse or a cut supply conductor. If channel LEDs stay off, check for stuck emergency stop contacts, cross-faults or broken wires, then for welded external contactor contacts. If the fault persists, the module must be replaced.
Standards and marks
The module is listed against EN 60204-1, EN ISO 13855, EN ISO 14118, EN ISO 12100, EN ISO 13850, EN 60529, EN 61000-6-2, EN 61000-6-3, EN 61326-1, EN 60664-1, EN 60947-1, EN IEC 63000, EN ISO 13849-1, EN ISO 13849-2, EN IEC 62061, UL 508 and CSA C22.2 No. 14, with conformity to the Machinery, EMC and RoHS directives. Utilization category per UL 508 is C300.
Choosing the right input circuit
The operating instructions describe several connections: a single channel emergency stop, a dual channel emergency stop with or without cross-fault detection, and gate monitoring. Pick the one that matches the risk assessment of the machine. A dual channel connection with forcibly guided contacts allows the highest level to be claimed, while a single channel hookup accepts a lower level because a single fault in the field wiring might not be detected. Simultaneity time between channels is unlimited, which makes the module tolerant of slow-closing guards. The input current per channel is typically 30 mA, so long cable runs with a few contacts in series are generally fine.
Output loading
Do not exceed the limits per contact and in total. The sum of squared currents across the contacts is limited to 72 A squared, which for two contacts at full 6 A just fits. For inductive loads, use external contactors rather than loading the relay contacts directly, and add suppression across coils so that contact life is not shortened. Minimum current is 10 mA, which makes the gold-plated contacts suitable for low-level signals when needed, such as feeding a safety input of a PLC.
Related items you may also need: Pizzato FK 301 Position Switch with Plunger, Snap Action | Pizzato FR 1007 Position Switch, Adjustable Roller | Pizzato FD 1001 Metal Position Switch with Plunger | All Pizzato products.
Pizzato CS AR-01V120 ordering checklist
- When the Pizzato CS AR-01V120 replaces an installed unit, check the existing nameplate against the code on this page before ordering.
- Every enquiry for the Pizzato CS AR-01V120 is answered with a written confirmation of the code and expected lead time.
- Use the attached datasheet to check the Pizzato CS AR-01V120 ratings, dimensions and connection details against your drawings.
- We supply the Pizzato CS AR-01V120 as part of our safety switches & guard locking range to plants in Oman and the GCC.
- For critical duty, keeping one Pizzato CS AR-01V120 as a site spare shortens downtime after a failure.
Documents and quotation
The operating instructions for the CS AR-01 modules are attached to this page and include wiring diagrams, technical data and fault finding tables. Send your RFQ with Pizzato CS AR-01V120, the quantity and your delivery location in Oman or the GCC.
Datasheets & Documents
- Datasheet Pizzato CS AR-01V120 Safety Module 2NO+1NC, 120 Vac Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Pizzato Elettrica is an Italian maker of position switches and safety devices, founded in 1984 as a manufacturer of position switches and based in Marostica, near Vicenza. It took the name Pizzato Elettrica in 1988 and added safety modules around 2002. The company designs and assembles its products in Marostica, where it opened a new 25,000 m² headquarters in 2019.
Seven Star LLC is an independent supplier in Muscat. We list Pizzato switches for machine builders and maintenance teams in Oman and the GCC.
Pizzato company profile
| Founded | 1984, Italy |
|---|---|
| Headquarters | Marostica, Italy |
| Name since | 1988 |
| Catalogue | More than 7,000 standard products |
| Product families | FR, FD and FK position switches, NG and NS safety interlocks, NX RFID safety switches, safety modules, foot switches |
Milestones
- 1984: Pizzato is founded.
- 1988: The company becomes Pizzato Elettrica.
- 2019: A new headquarters opens in Marostica.
Pizzato product series
Position switches include the FD 1001 metal switch with plunger, the FK 301 switch with plunger and snap action contacts, and the FR 1007 switch with adjustable roller lever.
Switches are chosen by the housing (metal or technopolymer), actuator, contact block and electrical connection. Snap action contacts switch quickly regardless of actuator speed, and positive opening contacts are used in safety circuits.
Plunger actuators suit short, straight movements against a cam or stop, while adjustable roller levers let the operating point be set on site and suit cams and moving parts that pass the switch. Metal housings stand up to heavy duty and impacts, and each data sheet states the IP rating, mechanical life and operating temperature range.
Where Pizzato switches are used
End of travel detection on machines, conveyors, doors and guards, cranes and lifting equipment.
Pizzato products we list
| Family | Examples |
|---|---|
| Automation Accessories | FD 1001 Metal Position Switch with Plunger, FK 301 Position Switch with Plunger, FR 1007 Position Switch |
Ordering Pizzato switches: what we need
Send the full article code, or the actuator type, contacts, housing and cable entry.
Facts checked against Pizzato's own timeline and EtherCAT member profile, October 2026.
Browse Pizzato products by category: Automation Accessories.
FAQ
Questions about the Pizzato CS AR-01V120 Safety Module 2NO+1NC, 120 Vac
Answers from our engineering team on installation, compatibility and integration.
01What supply voltage does the Pizzato CS AR-01V120 use?
It uses 120 Vac at 50 to 60 Hz with a tolerance of plus or minus 15 percent and consumes less than 5 VA.
02What outputs does the CS AR-01V120 provide?
It provides two forcibly guided normally open safety contacts and one normally closed auxiliary contact, each safety contact rated 6 A.
03What safety level can the CS AR-01V120 reach?
With two redundant channels it reaches category 4, PL e per EN ISO 13849-1 and SIL 3 per EN IEC 62061, with PFHD of 1.18E-10.
04What is the response time of this module?
The response time tA is below 300 ms for this version and the release time tR1 is below 20 ms, per the operating instructions.
05What fuse protects the contacts of the CS AR-01V120?
The operating instructions call for an external protection fuse of 4 A in series with the output contacts.


















Reviews