Brand: Bürkert
Bürkert 423913 Type 8030 SE30 Hall Paddle Wheel Flow Sensor
Description
Overview
Bürkert 423913 is the Hall variant of the SE30 flow sensor electronics from the Bürkert Type 8030 Inline flowmeter. The module generates a frequency signal proportional to flow velocity and offers two open-collector transistor outputs, NPN and PNP, so it can feed a PLC input, a counter or a Bürkert universal transmitter or controller directly. It is operated from 12 to 36 V DC and connects through a female cable plug to DIN EN 175301-803. Seven Star LLC is an independent supplier serving Oman and the GCC.
How Bürkert 423913 measures
A paddle wheel flowmeter places a small wheel with magnets in the stream. The liquid turns the wheel, a magnetic sensor in the electronics generates a pulse train, and the frequency is proportional to velocity. A K factor, specific to the pipe and fitting size, converts that frequency to a flow rate in litres per minute. The K factors are listed in the instructions of the Inline sensor-fitting Type S030, and a teach-in procedure with a known volume can improve accuracy to plus or minus 1 percent of the reading at the teach-in flow.
Technical data of Bürkert 423913
| Parameter | Value |
|---|---|
| Article | 423913, SE30 Hall variant |
| Principle | Paddle wheel with Hall sensor |
| Supply | 12 to 36 V DC plus or minus 10 percent, SELV and LPS |
| Current consumption | 30 mA or less with sensor |
| Outputs | 2 open-collector transistors, NPN and PNP, max. 100 mA |
| Frequency | 0 to 300 Hz, duty cycle 1/2 plus or minus 10 percent |
| Flow range | 0.5 to 1000 l/min, 0.3 to 10 m/s |
| Deviation | teach-in plus or minus 1 percent; standard K factor plus or minus 2.5 percent |
| Linearity and repeatability | 0.5 percent of full scale; 0.4 percent of reading |
| Pipe size | DN 06 to DN 65 with Type S030 fitting |
| Wetted parts | PVDF paddle wheel, ceramic axis and bearing, FKM or EPDM seal |
| Ambient temperature | minus 15 to plus 60 degrees C |
| Connection | Female cable plug DIN EN 175301-803, 3P plus PE |
| Protection | IP65 when wired |
What Bürkert 423913 does differently from other Type 8030 variants
The Type 8030 data sheet describes three electronics versions. 423913 is the standard Hall variant with two transistor outputs. The Hall Low Power variant, article 423914, has one NPN output, draws only 0.8 mA and takes its power from a connected Bürkert transmitter. The high temperature variant, article 449694, uses a coil transducer and a stainless steel paddle wheel for fluids up to 125 degrees C. Use 423913 when the sensor is powered from its own 12 to 36 V DC supply and connected to a PLC or counter.
Fitting selection with the Inline sensor-fitting S030
The Type 8030 electronics do not touch the liquid. They clip into a Bürkert Type S030 Inline sensor-fitting by a bayonet system, and the fitting defines the pipe size from DN 06 to DN 65, the connection type and the wetted materials. Plastic fittings in PVC, PP or PVDF reach PN 10, while metal fittings in stainless steel 316L or brass reach PN 16. The fluid temperature limits depend on the fitting: 0 to 50 degrees C for PVC, 0 to 80 degrees C for PP, and minus 15 to plus 100 degrees C for PVDF, stainless steel or brass. The fitting is a separate item and must be ordered in addition to the electronics.
Straight run and installation position
Paddle wheel meters are sensitive to disturbed flow. Allow a straight inlet of at least ten pipe diameters after elbows or reducers, and a longer run after pumps or partly closed valves, with five diameters on the outlet side. The pipe must be full and free of air bubbles, so install in a rising line or a low point. Avoid mounting at the top of a horizontal pipe where air can collect, and keep solids below 1 percent by volume with a maximum particle size of 0.5 mm. Fluid viscosity should not exceed 300 cSt.
Environment and wiring
The device is rated for indoor and outdoor use up to 2000 m altitude, with relative humidity up to 80 percent without condensation. IP65 applies only when the device is wired and the cable plug is mounted and tightened. Use shielded cable up to 50 m long with external wire diameter of 5 to 8 mm and wire cross section of 0.25 to 1.5 mm2, rated above 80 degrees C. Protect the electronics from ultraviolet radiation when installed outdoors, for example with a shade. The supply should be an SELV limited power source.
Commissioning Bürkert 423913
After installation, confirm the polarity and voltage at the plug, then connect the PNP or NPN output according to the input type of the receiving device. Enter the K factor of the selected fitting, or perform a teach-in with a measured volume. Check zero flow for stray pulses and verify the total against a known batch.
Connecting Bürkert 423913 to a PLC or counter
The two transistor outputs are open collector. An NPN output sinks current to ground and needs a pull-up resistor or a PLC input that supplies one, while the PNP output sources the supply voltage and suits sinking inputs. Pick the output that matches the input card, leave the other unconnected, and keep the cable length under 50 m. Typical counting inputs accept up to 300 Hz easily, but check the filter time of the card, since a slow input filter can miss the highest pulse rates of a 1000 l/min flow.
Flow in litres per minute is the frequency divided by the K factor, multiplied by sixty. Scale the PLC accordingly, add a low-flow cut-off to suppress noise at standstill, and totalise in the PLC if the highest accuracy is wanted.
Related items you may also need: Bürkert Type 6026 Direct-Acting 2/2-Way Plunger Solenoid Valve | Bürkert Type 8681 Control Head for Hygienic Process Valves | Hydac EVS 3106-A-0060-000 Turbine Flow Transmitter, 15.9 gpm | All Bürkert products.
Documents and quotation
The Type 8030 data sheet covering Bürkert 423913 is attached and holds ordering information, dimensions and pressure-temperature diagrams. Send an RFQ with the part number 423913, quantity and delivery location in Oman or the GCC. Mention the pipe size so that a matching Inline fitting can be quoted.
Datasheets & Documents
- Datasheet Bürkert 423913 Type 8030 SE30 Hall Paddle Wheel Flow Sensor Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Bürkert is a German family-owned maker of fluid control systems, headquartered in Ingelfingen, Baden-Württemberg. Christian Bürkert founded the company in 1946, and it is known for solenoid valves, process and control valves, flow and analytical sensors, and mass flow controllers. Its products serve water treatment, hygienic processing, gas handling and laboratory applications.
Seven Star LLC lists Bürkert valves and valve automation devices and supplies Bürkert solenoid valves and spare parts to plants in Oman as an independent supplier.
Bürkert company profile
| Founded | 1946, by Christian Bürkert |
|---|---|
| Headquarters | Ingelfingen, Germany |
| Ownership | Family-owned |
| Product families | Solenoid valves, angle seat process valves, positioners, flow meters, mass flow controllers |
Bürkert types listed on this page
Two types are listed. Type 6026 is a direct-acting 2/2-way plunger solenoid valve, with a stainless steel bellows that separates the medium from the coil, and as a direct-acting valve it switches without needing a pressure difference. Type 8681 is the Bürkert control head that mounts on top of hygienic process valves to pilot the actuator and report valve position to the control system. Control heads of this kind are common in food, beverage and pharmaceutical plants in the GCC.
Ordering Bürkert valves: what we need
The type number alone is not enough. Send the identification number from the label, or else the type with orifice, port connection, body and seal material, coil voltage and frequency, circuit function and pressure range. For a Type 8681 control head add the communication variant and the make and model of the process valve it sits on.
Facts checked against Bürkert's published company history, October 2026.
Browse Bürkert products by category: Solenoid Valve, Control Valves.
FAQ
Questions about the Bürkert 423913 Type 8030 SE30 Hall Paddle Wheel
Answers from our engineering team on installation, compatibility and integration.
01What outputs does Bürkert 423913 have?
It has two open-collector transistor pulse outputs, NPN and PNP, each up to 100 mA, with frequency from 0 to 300 Hz.
02What supply does 423913 need?
The Hall variant operates on 12 to 36 V DC plus or minus 10 percent from a SELV supply and draws 30 mA or less.
03What flow range does Bürkert 423913 cover?
The data sheet gives 0.5 to 1000 l/min or 0.3 to 10 m/s, depending on the Type S030 Inline fitting size from DN 06 to DN 65.
04Is a fitting included with 423913?
No. The SE30 electronics mount on a separate Inline sensor-fitting Type S030, which defines pipe size, connection and materials.
05How accurate is Bürkert 423913?
With teach-in the deviation is plus or minus 1 percent of the reading, and with the standard K factor it is plus or minus 2.5 percent.