Brand:

Bürkert 560201 Type 8619 multiCELL Conductivity Controller

Description

Overview

Conductivity is the quickest indicator of dissolved salts in water, and Bürkert 560201 brings that measurement into the Bürkert multiCELL family. The article is a Type 8619 panel-mounted transmitter and controller with the main module and one conductivity module, which accepts two or four electrode cells and a Pt100 or Pt1000 temperature probe. It also keeps two flow inputs, two transistor outputs and two 4 to 20 mA outputs. Seven Star LLC is an independent supplier serving Oman and the GCC.

Measuring ranges of Bürkert 560201

Parameter Value
Article 560201, main module plus 1 conductivity module
Conductivity 0 microS/cm to 2 S/cm, depending on the cell; resolution 1 nS/cm
Resistivity 0.5 ohm cm to 100 Mohm cm, depending on the cell
Deviation plus or minus 0.5 percent of reading plus probe error
Temperature input Pt100/Pt1000, minus 40 to plus 200 degrees C, 0.1 degree resolution
Resistance range without cell 5.0 ohm to 1 Mohm
Module power 0.25 VA
Outputs 2 transistor, 2 x 4 to 20 mA
UL approval No (UL version is 560209)
Housing Panel-mounted multiCELL, 1/4 DIN, 92 x 92 mm cutout, PPO housing
Supply 12 to 36 V DC plus or minus 10 percent, max. 2 A, via external SELV and LPS supply
Power consumption max. 1.5 VA for the main module alone
Display LC graphic display, 128 x 168 pixels, light blue backlight, English, German, French
Keys 4 soft keys and 1 central navigation key
Module slots 6
Data logger up to 16 values, SD or SDHC card up to 8 GB
Ambient temperature minus 10 to plus 70 degrees C with main module only; up to plus 60 degrees C with an additional module
Protection IP65 or NEMA 250 4X in front of a closed cabinet; IP20 behind the panel
Altitude and humidity max. 2000 m, below 85 percent without condensation

Why conductivity control with Bürkert 560201

Conductivity is used to control cooling tower blowdown, to monitor reverse osmosis permeate, to verify rinse completeness in CIP cycles and to detect product or water mixing. Because the module reads both conductivity and resistivity, one device can serve a brine line in the milliSiemens range or ultrapure water in the megaohm range, provided the right cell constant is chosen for the cell. A Pt100 or Pt1000 element gives automatic temperature compensation over a wide range from minus 40 to plus 200 degrees C.

How Bürkert 560201 differs from other multiCELL articles

The conductivity input replaces the pH input of 560200, and the temperature range widens from minus 25 to plus 130 degrees C to minus 40 to plus 200 degrees C. The module draws 0.25 VA instead of 0.1 VA. Against 560203 there is only one conductivity channel and two outputs of each type. The UL Recognized twin of this article carries the number 560209.

Outputs and control functions

Transistor outputs can be wired in PNP or NPN mode, are short-circuit protected, switch up to 36 V DC and can run at up to 2000 Hz. Operating modes include on and off, hysteresis, window, PWM and PFM, so the same hardware can dose a pump, drive a proportional valve or switch an alarm lamp. The 4 to 20 mA outputs have a resolution of 6 microamps and an uncertainty of plus or minus 0.5 percent of the transmitted value, with a maximum loop impedance of 610 ohms at 24 V DC.

Data logging and diagnostics

A real-time clock and an SD or SDHC memory card up to 8 GB give the multiCELL a data logger for up to 16 values. With eight values recorded every ten seconds, an 8 GB card runs for more than 500 days of continuous recording. The data sheet recommends the tested Bürkert card because other cards may not run reliably, and notes that with a card inserted the storage range narrows to minus 10 to plus 70 degrees C. The sensor monitor shows raw measured values directly, which helps commissioning engineers check wiring and verify probes before the control loop is closed.

Spare strategy and lifecycle

Because the factory configuration cannot be changed in the field, one device is not a perfect spare for another. Make a table of installed multiCELL articles by tag number, note the module list from the nameplate, and keep one spare for each distinct article that controls a critical process. Pair spares with a backup of the parameter set exported to the SD card so that a replacement can be commissioned in minutes.

Gulf climate considerations

Cabinets in direct sun on Gulf sites can exceed the 60 or 70 degree limits of the multiCELL once any additional module is fitted, so mount the unit on the shaded side or in an air-conditioned room, and avoid mounting it directly above heat sources such as drives. Fine desert dust is kept out of the front by the IP65 rating only when the door seal is intact, so inspect gaskets at each shutdown. Condensation after night-time cooling is limited by the humidity specification of below 85 percent without condensation.

Buying checklist before you send an RFQ

State the article number, the number of units, whether UL approval is mandatory, the intended supply voltage, the probes and flow sensors that will be connected and whether a network protocol is needed. Add the cable lengths and the type of cabinet. With this information a quotation can be prepared without back-and-forth, and delivery planning for Oman and the wider GCC can begin early.

Cell selection and set-up

Choose a conductivity cell whose constant matches the measuring range: low constants for pure water, higher constants for brines. Use shielded cable of moderate length, calibrate against a standard solution and set temperature compensation. Define blowdown setpoints with hysteresis so that valves do not chatter, and log values to the card during commissioning to see seasonal trends.

Related items you may also need: Bürkert Type 8681 Control Head for Hygienic Process Valves | Bürkert Type 6026 Direct-Acting 2/2-Way Plunger Solenoid Valve | Thorlabs MDT693B 3-Channel Open-Loop Piezo Controller | All Bürkert products.

Documents and quotation

The Type 8619 data sheet covering Bürkert 560201 is attached with its ordering chart and module data. Send your RFQ with part number 560201, quantity and delivery location in Oman or the GCC.

Other Models in the 8619 Range

Seven Star LLC supplies models from the 8619 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Bürkert 560205 Type 8619 multiCELL Flow Transmitter ControllerControllers & Data AcquisitionView details
Bürkert 560200 Type 8619 multiCELL pH/ORP ControllerControllers & Data AcquisitionView details
Bürkert 560201 Type 8619 multiCELL Conductivity ControllerControllers & Data AcquisitionYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Bürkert 560201 Type 8619 multiCELL Conductivity Controller Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Bürkert is a German family-owned maker of fluid control systems, headquartered in Ingelfingen, Baden-Württemberg. Christian Bürkert founded the company in 1946, and it is known for solenoid valves, process and control valves, flow and analytical sensors, and mass flow controllers. Its products serve water treatment, hygienic processing, gas handling and laboratory applications.

Seven Star LLC lists Bürkert valves and valve automation devices and supplies Bürkert solenoid valves and spare parts to plants in Oman as an independent supplier.

Bürkert company profile

Founded 1946, by Christian Bürkert
Headquarters Ingelfingen, Germany
Ownership Family-owned
Product families Solenoid valves, angle seat process valves, positioners, flow meters, mass flow controllers

Bürkert types listed on this page

Two types are listed. Type 6026 is a direct-acting 2/2-way plunger solenoid valve, with a stainless steel bellows that separates the medium from the coil, and as a direct-acting valve it switches without needing a pressure difference. Type 8681 is the Bürkert control head that mounts on top of hygienic process valves to pilot the actuator and report valve position to the control system. Control heads of this kind are common in food, beverage and pharmaceutical plants in the GCC.

Ordering Bürkert valves: what we need

The type number alone is not enough. Send the identification number from the label, or else the type with orifice, port connection, body and seal material, coil voltage and frequency, circuit function and pressure range. For a Type 8681 control head add the communication variant and the make and model of the process valve it sits on.

Facts checked against Bürkert's published company history, October 2026.

FAQ

Questions about the Bürkert 560201 Type 8619 multiCELL Conductivity

Answers from our engineering team on installation, compatibility and integration.

01What does Bürkert 560201 measure?
It measures conductivity or resistivity through one conductivity module with a Pt100 or Pt1000 temperature input, and offers flow inputs and control outputs.
02What conductivity range does 560201 cover?
The module range is 0 microS/cm to 2 S/cm depending on the cell, with a resolution of 1 nS/cm and deviation of 0.5 percent of reading.
03Which temperature range does Bürkert 560201 support?
The Pt100 or Pt1000 input measures from minus 40 to plus 200 degrees C with a deviation of plus or minus 1 degree C plus probe error.
04Does 560201 have a UL version?
Yes. The ordering chart lists article 560209 as the UL version of this configuration; 560201 itself is without UL approval.
05How is 560201 powered?
It operates on 12 to 36 V DC from an external SELV supply, with the main module consuming up to 1.5 VA.