Moore Industries STZ/PRG/4-20MA/12-42DC [BH2NGP] SIL Transmitter

Description

Moore Industries STZ/PRG/4-20MA/12-42DC [BH2NGP]: SIL-capable transmitter with local readout

Moore Industries STZ/PRG/4-20MA/12-42DC [BH2NGP] adds the integral display of the HP module to the STZ functional safety platform and houses it in a BH aluminum explosion-proof case. The operator sees the process value in 10 mm digits, while the SIS engineer has an exida-certified instrument for SIL 2 single or SIL 3 redundant temperature measurement.

The P suffix delivers the base plate and U-bolts for a 2-inch pipe, making it a ready-to-install package for field points.

The BH case solves a practical problem on safety loops: a trip transmitter is often installed at a point that nobody visits except during rounds, yet operators still want a quick look. With the 10 mm display they can verify that the safety transmitter and the basic process control sensor agree, a simple cross-check that catches drift early.

Capabilities

  • Safety certification to IEC 61508:2010 with FMEDA data on request.
  • Display with auto decimal point and user-defined engineering units.
  • Dual input with failover and averaging, plus diagnostic alerts for sensor drift and corrosion.
  • HART 7 communication, with access control to hold the configuration during the safety function.
  • Namur 43 failure signalling and a damping range of up to 60 seconds.

Together these make it the local-indicating counterpart of the STZ head and DIN versions.

STZ/PRG/4-20MA/12-42DC [BH2NGP] data summary

The table lists STZ values for the BH housing.

Parameter Value for STZ/PRG/4-20MA/12-42DC [BH2NGP]
Model code STZ/PRG/4-20MA/12-42DC [BH2NGP]
Safety integrity exida certified to IEC 61508:2010: systematic capability to SIL 3, random integrity to SIL 2; single use up to SIL 2, redundant (1oo2, 2oo3) up to SIL 3
Unit STZ with integral display in BH enclosure
Housing BH2NGP: aluminum explosion-proof BH, two 1/2-inch NPT entries, glass cover, base plate and U-bolts for 2-inch pipe
Input PRG: single or dual input; 14 RTD types, 9 thermocouple types (J, K, E, T, R, S, B, N, C), 0 to 4000 ohm, -50 to 1000 mV, potentiometer
Output 4-20 mA, HART 7, addresses 0 to 63
Supply 12-42 V DC
Display Top row 10 mm, bottom row 6 mm, HART address; range -99999 to 99999
Weight 1.4 kg (50.2 oz) HP in BH; 182 g HP alone; 3.2 kg HP in SB
Isolation 500 Vrms input to output; 500 Vac for one minute
RFI/EMI 20 V/m at 80-1000 MHz for STZ HP
Step response 460 ms single, 650 ms dual input
Output accuracy 3 microamps (0.019% of the 4-20 mA span)
HART access control Read Only or Off
Damping 0 to 60 seconds
Ambient -40 to +85 C

Reading the table, notice how the weight rows differ: 182 g for the bare HP module, 1.4 kg in the BH enclosure and 3.2 kg in the stainless SB enclosure. The BH choice is a balance between robustness and mass, important when the transmitter is mounted on a thin pipe near a vibrating machine. The base plate and U-bolts included with the P suffix help spread the load.

How STZ/PRG/4-20MA/12-42DC [BH2NGP] differs from the other STZ codes

The LH2NS code is a head-mounted module without display; the DIN -AIS code is for cabinets and weighs 221 g. This BH code is the only one in the trio with a local display and a 1.4 kg weight, and its RFI immunity is 20 V/m compared with 10 V/m for the HPP module.

On isolation, the DIN and HPP versions are rated at 500 Vrms and tested at 1350 Vac for one minute, while the HP display module used in this BH case is rated at 500 Vrms and tested at 500 Vac.

Applications

Field-mounted SIL temperature points that must be locally readable: reboiler outlets, hot oil loops, steam superheater outlets and high-temperature cut-out points on gas compression skids. Operators can confirm the reading and the diagnostic state without a handheld.

In the GCC, the BH case suits outdoor installations with its glass cover and flameproof construction.

The display range of -99999 to 99999 and the minimum display span of 1.00 mean that even unusual engineering units can be shown. The decimal point can be set automatically or fixed at one, two or three places, which is handy when the same transmitter is re-ranged for a different service during a plant revamp.

Selection

Pick 12-42DC for general hazardous-area loops; the 12-30DC code serves intrinsically safe loops. Choose BH2MG instead for M20 entries or SB2NG for stainless steel where corrosion demands it. Request the FMEDA report when you order if your safety file requires it.

Decide in advance how HART access control will be used during operation.

Installation

Mount the base plate on the pipe, set the enclosure, fit certified glands and connect the sensors and loop. Configure and verify, then close the glass cover. Apply access control and record the final setup.

Verify the displayed value against the loop current at the logic solver.

At commissioning write down the HART address, tag, descriptor and message so the plant asset tools list this transmitter under the right name. After the validation test, enable HART access control, close the glass cover firmly, and attach a label giving the safety function and the date of the last proof test.

Maintenance and proof testing

Use the FMEDA data to choose a proof-test interval. During the test, simulate both inputs, confirm the diagnostics, and check the 4-20 mA output at several points. Inspect the BH enclosure for corrosion and damage to the glass.

Spare modules can be configured from the saved file.

Supply of STZ/PRG/4-20MA/12-42DC [BH2NGP]

When you send an enquiry, quote STZ/PRG/4-20MA/12-42DC [BH2NGP] in full and say if FMEDA data is needed.

Seven Star LLC is an independent supplier serving Oman and the wider GCC and is not affiliated with the manufacturer; all names and part numbers are used only to identify the product being requested.

Documents and quotation

The datasheet for Moore Industries STZ/PRG/4-20MA/12-42DC [BH2NGP] can be sent with our quotation. Please provide part number, quantity and delivery location in your RFQ.

Other Models in the STZ Range

Seven Star LLC supplies models from the STZ range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Moore Industries STZ/PRG/4-20MA/12-30DC [LH2NS] SIL TransmitterTemperature TransmittersView details
Moore Industries STZ/PRG/4-20MA/12-42DC/-AIS [DIN] SIL TransmitterTemperature TransmittersView details
Moore Industries STZ/PRG/4-20MA/12-42DC [BH2NGP] SIL TransmitterTemperature TransmittersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Moore Industries STZ/PRG/4-20MA/12-42DC [BH2NGP] SIL Transmitter Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Moore Industries is an American manufacturer of signal interface instruments, founded in 1968 by engineer Leonard W. Moore in North Hills, California. Its first product was the SCT signal converter, built in a friend's workshop. The company has been at its North Hills headquarters since 1974 and still designs and builds its products there, known for rugged aluminium housings.

Seven Star LLC, an independent supplier in Oman, lists Moore Industries temperature transmitters, limit alarm trips, isolators and a PID backup controller, and sources units and replacements by full model number.

Moore Industries company profile

Founded 1968, North Hills, California, USA, by Leonard W. Moore
Headquarters North Hills, California, since 1974
Ownership Privately owned (Moore Industries-International, Inc.)
First product SCT signal converter
Product families Signal isolators and converters (ECT, SCT), temperature transmitters (TRY, THZ), alarm trip units (SPA), miniMOORE multichannel signal conditioners, HART interfaces, SIL-rated safety logic solvers (STA)

Milestones

  • 1968: Leonard W. Moore founds the company and builds the first SCT signal converter.
  • 1974: The company moves into its North Hills headquarters.
  • 2009: miniMOORE wins a Control Engineering Engineers' Choice Award.

Moore Industries product families on this page

The manufacturer's catalog is arranged by function, and many of the items listed here map onto it directly:

  • Temperature transmitters: the TRX, and the STZ functional safety dual input smart HART transmitter
  • Alarm trips: the SPA2 programmable limit alarm trip, including an SPA2 with HLPRG input and four relay outputs
  • Signal isolators, repeaters and converters: the SIX
  • PID controllers and backup stations: the 535 in 1/4 DIN format

Other catalog groups include temperature assemblies and sensors, I/P and P/I converters, remote I/O, HART gateways and interfaces, indicators, and fieldbus device couplers.

Where Moore Industries instruments are used

These are control room and marshalling cabinet devices, plus field-mounted transmitters. Typical jobs are isolating a 4-20 mA loop between two systems, converting a thermocouple or RTD signal for a DCS input, adding an independent high or low trip next to the control system, and keeping a control loop running on a backup station when the main controller is out of service. Process plants in oil and gas, chemicals and power across the GCC use them for exactly these tasks.

Moore Industries products we list

Family Examples
Controllers & Data Acquisition Moore 535-21120BD000 | Industrial PID Ba…, SPA2 Programmable Limit Alarm Trip, Moore-SPA2HL Associated IS Programmable…
Isolator & Barrier HIM Smart HART Loop Interface and Monitor, SIX Signal Isolator, SLA SIL 2/3 Safety Logic Solver and Alarm
Temperature Instrumentation STZ Functional Safety Dual Input Smart H…, TRX Temperature Transmitter
Industrial Communications HES HART to Ethernet Gateway
Valve Positioners IPT2 Current-to-Pressure I/P Transmitter

Ordering Moore Industries instruments: what we need

Moore Industries model numbers are built from fields separated by slashes: unit, input, output, power and options, followed by the housing code in brackets. Every field matters. Send the complete string from the label, the serial number, and for programmable units the input type and range you want set. State any hazardous area or functional safety requirement, because approved versions are ordered with their own option codes.

Facts checked against trade press obituaries of Leonard W. Moore (Control Engineering, Control Global), October 2026.

FAQ

Questions about the Moore Industries STZ/PRG/4-20MA/12-42DC [BH2NGP]

Answers from our engineering team on installation, compatibility and integration.

01Does the STZ BH version have a display?
Yes, a two-row display with 10 mm and 6 mm digits and a HART address indicator.
02What does the P in BH2NGP mean?
The enclosure comes with a base plate and U-bolts for mounting on a 2-inch pipe.
03What is the weight?
The HP module in a BH enclosure weighs 1.4 kg (50.2 oz).
04What step response applies?
Typical 460 ms for a single input and 650 ms for dual input.
05Is the FMEDA data included?
Exida certified FMEDA data is available on request for safety applications of the STZ.