Moore Industries HDM/HSM/2X4-20MA/12-42DC/-3M [D3LCP]: display and output half of the HTZ

Moore Industries HDM/HSM/2X4-20MA/12-42DC/-3M [D3LCP] is the HDM humidity and temperature display module of the HTZ Smart HART transmitter. It receives the measured values from an HSM sensor module over a 3 m cable (the -3M option), shows them on a 2 x 5 character display, and drives two isolated 4-20 mA outputs. One HDM is required per installation, and it sits in a D3LCP NEMA 4X, IP66 enclosure supplied with 2-inch pipe-mount hardware.

The two outputs are user selectable: each can follow relative humidity, temperature or the calculated dew point. HART communication rides on output 1, which makes the module easy to integrate into a DCS or PLC that already supports HART.

What HDM/HSM/2X4-20MA/12-42DC/-3M [D3LCP] offers

  • Dual analog outputs, so one device can deliver two process variables to the control system.
  • A readable alphanumeric display that shows humidity, temperature, dew point, output 1, output 2 or scrolls through them at four-second intervals.
  • Programmable failure behaviour for each output: drive upscale, downscale or hold the last value if a sensor fails or the cable is disconnected.
  • Remote placement: the HDM can sit up to 30 m from the sensor module, so the display can be at eye level in a control area.
  • Setup with a HART communicator, a HART-based system or a PC on the 4-20 mA wires of output 1.

The module is loop-powered, with the supply of 12-42 V DC taken at the output terminals.

HDM/HSM/2X4-20MA/12-42DC/-3M [D3LCP] specification table

These values come from the HTZ datasheet.

Parameter Value for HDM/HSM/2X4-20MA/12-42DC/-3M [D3LCP]
Model code HDM/HSM/2X4-20MA/12-42DC/-3M [D3LCP]
Unit HDM humidity and temperature display module of the HTZ
Input HSM sensor module
Outputs Two isolated, scalable 4-20 mA outputs, each user-selectable for relative humidity, temperature or dew point; HART on output 1
Supply 12-42 V DC at the output terminals
Cable option -3M: 3 m (10 ft) cable between HDM and HSM; options 1, 3, 6, 9, 15, 25 and 30 m
Housing D3LCP: surface or pipe-mount enclosure, NEMA 4X, IP66, with 2-inch pipe-mount hardware
Isolation 500 Vac between each output and between outputs and case
Output accuracy Plus or minus 2 microamps
Linear region 3.8 to 21.4 mA; hardware limits 3.6 to 23.6 mA
Display LCD 2 x 5 14-segment characters; range -99999 to 99999
Load capability 500 ohms at 24 V; (supply voltage minus 12 V) divided by 0.024 A
Weight HDM 918 g (32.4 oz); cable 3 m 196 g
Start-up time Less than 5 seconds
Analog output response 500 ms to 90% of final value
Ambient -40 to +85 C, 0 to 95% RH non-condensing

Notice how the table lists the analog output accuracy as a small absolute current, 2 microamps, and then separately gives a 0.009% of span per degree C ambient effect and long-term stability figures of 0.012% after one year, 0.020% after three years and 0.026% after five years. Added together, these set the loop error that you should compare with the tolerance of your process.

How HDM/HSM/2X4-20MA/12-42DC/-3M [D3LCP] differs from the HSM sensor code

The HSM/PT-RH/HDM/HDM/-CL12 -VTB [LH3Z] order holds probes; this HDM order holds the electronics, the display and the outputs. An HTZ installation needs both: the HSM measures, the HDM computes dew point, scales and outputs. A replacement HDM electronics module in a hockey-puck housing is a separate option without cable selection.

The cable choice also separates the two: the HSM-HDM cable length (1, 3, 6, 9, 15, 25 or 30 m) is declared in this order, here as -3M, and weights range from 82 g for 1 m up to 1100 g for 25 and 30 m cables.

Applications

Use it for HVAC supervision, cleanroom and laboratory conditions, store rooms for electronic and pharmaceutical products, and instrument air monitoring. In the humid coastal climate of the Gulf it is helpful in control rooms and switchgear rooms, where trends of dew point warn of condensation.

Factories can also use the two outputs to feed a PLC for dehumidifier control and a data logger for quality records.

Selection

Pick the cable length that reaches from the sensing point to the display location with some slack, since only one cable option may be selected. Decide which two variables you want on outputs 1 and 2; they can be changed later with HART or PC software.

Use the -1ST or -2ST stainless steel tag options if tagging is required by your plant standard.

Installation

Mount the D3LCP on a surface or a 2-inch pipe, connect the HSM cable, connect the 12-42 V DC loop supply and the two output loops, and power up. Configure the sensor ranges, output assignments, damping (0 to 30 s) and failure modes.

The HART address and tag can be entered during the same session.

Maintenance

Check the enclosure seals, the cable and the display. Keep records of any trim adjustments performed with the configuration software, and calibrate the humidity channel against a reference environment at the interval your quality system defines.

Replacement connection cables are listed by length in the datasheet.

At commissioning, check that both output loops read plausible values with the process at rest, and that the humidity and temperature shown on the display match a portable reference. Where the dew point is used for protection, record the calculation method: the datasheet gives the equation based on saturation vapour pressure, so the logic can be reviewed by quality staff.

Supply of HDM/HSM/2X4-20MA/12-42DC/-3M [D3LCP]

Please quote HDM/HSM/2X4-20MA/12-42DC/-3M [D3LCP] in full in your enquiry and say which cable length is required.

Seven Star LLC is an independent supplier serving Oman and the wider GCC and is not affiliated with the manufacturer; all names and part numbers are used only to identify the product being requested.

Documents and quotation

The datasheet for Moore Industries HDM/HSM/2X4-20MA/12-42DC/-3M [D3LCP] can accompany our quotation. Submit an RFQ with part number, quantity and delivery location.

Other Models in the HTZ Range

Seven Star LLC supplies models from the HTZ range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Moore Industries HSM/PT-RH/HDM/HDM/-CL12 -VTB [LH3Z] SensorHumidity & Dew Point InstrumentsView details
Moore Industries HDM/HSM/2X4-20MA/12-42DC/-3M [D3LCP] DisplayHumidity & Dew Point InstrumentsYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Moore Industries HDM/HSM/2X4-20MA/12-42DC/-3M [D3LCP] Display Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Moore Industries is an American manufacturer of signal interface instruments, founded in 1968 by engineer Leonard W. Moore in North Hills, California. Its first product was the SCT signal converter, built in a friend's workshop. The company has been at its North Hills headquarters since 1974 and still designs and builds its products there, known for rugged aluminium housings.

Seven Star LLC, an independent supplier in Oman, lists Moore Industries temperature transmitters, limit alarm trips, isolators and a PID backup controller, and sources units and replacements by full model number.

Moore Industries company profile

Founded 1968, North Hills, California, USA, by Leonard W. Moore
Headquarters North Hills, California, since 1974
Ownership Privately owned (Moore Industries-International, Inc.)
First product SCT signal converter
Product families Signal isolators and converters (ECT, SCT), temperature transmitters (TRY, THZ), alarm trip units (SPA), miniMOORE multichannel signal conditioners, HART interfaces, SIL-rated safety logic solvers (STA)

Milestones

  • 1968: Leonard W. Moore founds the company and builds the first SCT signal converter.
  • 1974: The company moves into its North Hills headquarters.
  • 2009: miniMOORE wins a Control Engineering Engineers' Choice Award.

Moore Industries product families on this page

The manufacturer's catalog is arranged by function, and many of the items listed here map onto it directly:

  • Temperature transmitters: the TRX, and the STZ functional safety dual input smart HART transmitter
  • Alarm trips: the SPA2 programmable limit alarm trip, including an SPA2 with HLPRG input and four relay outputs
  • Signal isolators, repeaters and converters: the SIX
  • PID controllers and backup stations: the 535 in 1/4 DIN format

Other catalog groups include temperature assemblies and sensors, I/P and P/I converters, remote I/O, HART gateways and interfaces, indicators, and fieldbus device couplers.

Where Moore Industries instruments are used

These are control room and marshalling cabinet devices, plus field-mounted transmitters. Typical jobs are isolating a 4-20 mA loop between two systems, converting a thermocouple or RTD signal for a DCS input, adding an independent high or low trip next to the control system, and keeping a control loop running on a backup station when the main controller is out of service. Process plants in oil and gas, chemicals and power across the GCC use them for exactly these tasks.

Moore Industries products we list

Family Examples
Controllers & Data Acquisition Moore 535-21120BD000 | Industrial PID Ba…, SPA2 Programmable Limit Alarm Trip, Moore-SPA2HL Associated IS Programmable…
Isolator & Barrier HIM Smart HART Loop Interface and Monitor, SIX Signal Isolator, SLA SIL 2/3 Safety Logic Solver and Alarm
Temperature Instrumentation STZ Functional Safety Dual Input Smart H…, TRX Temperature Transmitter
Industrial Communications HES HART to Ethernet Gateway
Valve Positioners IPT2 Current-to-Pressure I/P Transmitter

Ordering Moore Industries instruments: what we need

Moore Industries model numbers are built from fields separated by slashes: unit, input, output, power and options, followed by the housing code in brackets. Every field matters. Send the complete string from the label, the serial number, and for programmable units the input type and range you want set. State any hazardous area or functional safety requirement, because approved versions are ordered with their own option codes.

Facts checked against trade press obituaries of Leonard W. Moore (Control Engineering, Control Global), October 2026.

FAQ

Questions about the Moore Industries HDM/HSM/2X4-20MA/12-42DC/-3M

Answers from our engineering team on installation, compatibility and integration.

01How many outputs does the HDM have?
Two isolated, scalable 4-20 mA outputs, each assigned to humidity, temperature or dew point.
02What cable lengths are available?
1, 3, 6, 9, 15, 25 and 30 m; the -3M option in this code selects 3 m (10 ft).
03What enclosure does D3LCP describe?
A NEMA 4X, IP66 surface or pipe-mount enclosure supplied with 2-inch pipe-mount hardware.
04Which output carries HART?
HART communication is available on analog output 1.
05What does the display show?
Relative humidity, temperature, dew point, output 1 or output 2, or it scrolls between all variables every four seconds.