- Automation & ControlView all 3,031 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Isolator & Barrier
- Controllers & Data Acquisition
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: GESTRA
GESTRA MK 25-2 Multi-Capsule Thermostatic Steam Trap DN40-50
Description
GESTRA MK 25-2: a multi-capsule steam trap in DN 40 and DN 50
Most thermostatic traps in the MK range are small. The GESTRA MK 25-2 is different: it is a PN 40 / Class 300 forged-steel trap in DN 40 and DN 50 (1½ and 2 inch) that fits four thermostatic capsules type 5H2 into one body, so that a single trap can pass condensate flows that would otherwise need a battery of DN 15 traps. The datasheet quotes up to 2800 kg/h at a differential pressure of 5 bar.
Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. We summarise the datasheet here so that you can verify the MK 25-2 against a plant list before asking for a quotation.
Technical data of MK 25-2
| Parameter | Value |
|---|---|
| Type | GESTRA MK 25-2 (written MK 25/2 in the datasheet) |
| Nominal sizes | DN 40, DN 50 (1½ and 2 inch) |
| Capsules | Four thermostatic capsules 5H2 |
| Capacity | Up to 2800 kg/h at 5 bar differential pressure (example in datasheet) |
| Max. differential pressure | 22 bar (319 psig) |
| PN 40 flange ratings | 40 barg at 20 °C, 35 at 200 °C, 28 at 300 °C, 21 at 400 °C, 14.5 at 450 °C |
| Class 300 ratings | 51 barg at 20 °C, 43.9 at 200 °C, 38.9 at 300 °C, 34.6 at 400 °C, 20.2 at 450 °C |
| Class 150 ratings | 19.7 barg at 20 °C down to 4.6 barg at 450 °C |
| Body and cover | C 22.8 (1.0460) / ASTM A 105 |
| Bolts | 42CrMo4 (1.7225) / A 193 B7 |
| Gasket | Graphite |
| Capsule material | Hastelloy / stainless steel |
| Flange face-to-face | 230 mm; flange to DIN 2635 form C PN 40 or ASME B16.5 150 RF and 300 RF |
| Weight (flanged) | About 11 kg for DN 40, 12.5 kg for DN 50 |
| Installation | Any position; integral strainer |
Why four capsules matter on MK 25-2
A membrane capsule responds to the evaporation temperature of the filling, so each capsule opens and closes independently. With four capsules in parallel the trap behaves like four small traps in one, and the flow area opens progressively as condensate load rises. That is a good match for large heaters, evaporator steam chests and bulk water heaters whose load swings with production.
How MK 25-2 differs from the MK 25-2 S
The datasheet covers both designs. The MK 25-2 has four 5H2 capsules and is quoted at 2800 kg/h at 5 bar. The MK 25-2 S has nine capsules, a cast cover in GP240GH (1.0619) / A 216 Gr WCB, and is quoted at 5000 kg/h. Both carry the same 22 bar differential limit and body rating. Choose the MK 25-2 where flow does not exceed the lower curve, and the S version where the larger chest or heat exchanger needs the higher capacity. The H capsule discharges roughly 5 K below saturation, which keeps the heating surface flooded as little as possible.
Application guidance for MK 25-2
Large-bore thermostatic traps like this are used on steam-heated storage tanks for heavy fuel and bitumen, on process air heaters, on tank-farm tracing manifolds and on plate and shell heat exchangers in utility rooms. In Oman and across the Gulf, buyers meet the MK 25-2 when upgrading ageing float traps or when a plant replaces several small traps with a single unit. The datasheet capacity chart plots hot condensate (10 K below saturation) and cold condensate at 20 °C for start-up, so you can read both normal and start-up flow.
Reading the MK 25-2 ratings
For a header or heater built to PN 40, the datasheet allows 40 barg at 20 °C, 35 barg at 200 °C, 28 barg at 300 °C, 21 barg at 400 °C and 14.5 barg at 450 °C. If the line uses ASME flanges, Class 300 starts at 51 barg and falls to 20.2 barg at 450 °C, while Class 150 starts at 19.7 barg and falls to 4.6 barg at 450 °C. The differential pressure limit of 22 bar applies on top of these, so a high-pressure header discharging to atmosphere still sits inside the trap limits only if the drop is under 22 bar. Check both numbers, not just the body rating, when comparing the MK 25-2 with older traps you plan to replace.
Body dimensions follow the nominal size. A DN 40 flanged unit weighs about 11 kg and a DN 50 unit about 12.5 kg, so two people or a hoist are sensible for installation at height, and pipe supports should be checked on either side of the trap.
Fitting MK 25-2
Allow 70 to 100 mm headroom for opening the trap, as shown in the datasheet drawings, and keep a strainer-friendly line upstream. The trap can be installed in any position because the capsules are not float-driven. For welded lines, socket-weld or butt-weld versions are listed; screwed BSP and NPT versions also exist. Ordering information should include steam pressure, back pressure, condensate quantity, type, size, connection and mounting position.
Spare parts and inspection of MK 25-2
The listed spares are the regulator with cover gasket (stock code 098770), the 5H2 capsule (376174) and the gasket 92.7 x 102 x 1 (087095). Test certificates to DIN EN 10204 type 2.2 and 3.1 can be issued on request at extra cost, and the requirement has to be stated with the order because certification cannot be established after supply.
Documents and quotation
A manufacturer datasheet for the MK 25-2 accompanies this page. Please send an RFQ with the part number MK 25-2, quantity, nominal size, flange standard and steam data; we will confirm availability for Oman and the GCC.
Delivery to Sites in Oman and the GCC
Delivery of the GESTRA MK 25-2 is arranged to suit the site, whether that is a plant in Sohar or Duqm, an oilfield location in the interior, or a project elsewhere in the GCC. Tell us the delivery point, any site access or gate-pass requirements, and the person who will receive the goods. Goods are packed to protect sensitive steam traps & steam specialties equipment during road or air transport, and shipping details are shared once the order is dispatched so that your stores team can plan receipt and inspection.
Selection Notes for the GESTRA MK 25-2
When comparing the GESTRA MK 25-2 with alternatives, start from the duty it must perform: the measured or controlled variable, the range and accuracy you need, the environment at the mounting point and the interface to your control system. Check the electrical and mechanical connections against the installed equipment, and confirm any hazardous-area or ingress-protection requirements for the location. If any point is unclear, send a photo of the nameplate and a short description of the application, and we will compare it with the GESTRA steam traps & steam specialties range and confirm the correct order code before you commit.
Datasheets & Documents
- Datasheet GESTRA MK 25-2 Multi-Capsule Thermostatic Steam Trap DN40-50 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
GESTRA is the German steam and condensate specialist behind the UNA ball float steam traps, the MPA blowdown valves and a long line of boiler level and conductivity controls. It was founded in Bremen in 1902 by Gustav F. Gerdts, and has been part of Spirax Sarco since 2017.
Seven Star LLC is an independent supplier in Muscat. We list GESTRA steam traps, blowdown valves and boiler control equipment, and supply GESTRA parts and spares to boiler houses and process plants in Oman and the GCC.
GESTRA company profile
| Established | 29 October 1902, Bremen, Germany, by Gustav Friedrich Gerdts; renamed Gustav F. Gerdts KG in 1907 |
|---|---|
| Ownership history | Became a stock corporation (GESTRA AG) in 1987, was taken over by Flowserve in 2002, and has been part of the Spirax Sarco group since 2017 |
| Product families | Steam traps, non-return and check valves, boiler blowdown valves, control valves, and boiler control electronics for level, conductivity and temperature |
| Applications | Steam boilers, steam distribution and condensate return in process plants, power stations, hospitals, food and textile plants |
Milestones
- 1902: Gustav Friedrich Gerdts founds the company in Bremen on 29 October.
- 1907: The company is renamed Gustav F. Gerdts KG.
- 1987: It becomes a stock corporation, GESTRA AG.
- 2002: Flowserve takes over GESTRA.
- 2017: GESTRA becomes part of the Spirax Sarco group.
GESTRA products we list
| Series | Type | What it does |
|---|---|---|
| UNA 45, UNA 16, UNA 38 | Ball float steam traps | Continuous condensate discharge from heat exchangers and process equipment; the UNA 38 is the high-pressure version (PN 100) |
| BK 45 | Bimetallic steam trap | Robust trap for steam main drainage and tracing, resistant to water hammer |
| MK 45, TK 23, SMK 22-81 | Thermostatic steam traps | Air venting and condensate discharge; the SMK 22-81 is the sanitary version for clean steam |
| MPA 46 | Rapid-action blowdown valve | Short, intermittent bottom blowdown that removes sludge from the boiler |
| NRS 1-54, NRR 2-50, NRR 2-60, NRGT 26-2 | Boiler level controls | Water level limiting, feedwater control and continuous level measurement |
| LRGT 16-1, LRR 1-50 | Conductivity measurement and control | Keeps boiler water conductivity in range through continuous blowdown |
| TRS 5-50 | Safety temperature limiter | SIL 3 temperature limiting for boilers and hot water systems |
The type of steam trap follows the duty. Ball float traps discharge condensate as soon as it forms, which suits heat exchangers with changing loads. Thermostatic and bimetallic traps hold condensate back slightly and suit steam mains, tracing and air venting. On the boiler itself, GESTRA level and conductivity electronics work as a system: electrodes or transmitters in the boiler, controllers in the panel, and the feedwater and blowdown valves they drive.
Where GESTRA products are used
In Oman and the GCC, GESTRA equipment is used in boiler houses of refineries, petrochemical and fertiliser plants, power and desalination stations, food and beverage plants, laundries, hotels and hospitals.
Ordering GESTRA parts: what we need
Send the type designation, pressure rating (PN) and connection size (DN), the end connection (flanged, screwed or socket weld), the operating pressure and condensate load for steam traps, and the supply voltage and bus type (CAN bus, 4-20 mA) for control equipment. For electrodes, add the insertion length.
Facts checked against GESTRA company history and Bremen city records, October 2026.
Browse GESTRA products by category: Liquid Analysis Sensors.
FAQ
Questions about the GESTRA MK 25-2 Multi-Capsule Thermostatic Steam
Answers from our engineering team on installation, compatibility and integration.
01How many capsules does the MK 25-2 contain?
Four thermostatic capsules type 5H2, with a datasheet example capacity of up to 2800 kg/h at a differential pressure of 5 bar.
02What sizes is the MK 25-2 made in?
DN 40 and DN 50 (1½ and 2 inch), with flanged, screwed, socket-weld and butt-weld end connections.
03What is the differential pressure limit of the MK 25-2?
The datasheet gives a maximum admissible differential pressure of 22 bar, which is 319 psig.
04How is the MK 25-2 different from the MK 25-2 S?
The S version has nine capsules and a GP240GH cover for up to 5000 kg/h at 5 bar, against four capsules and 2800 kg/h for the MK 25-2.
05Which spare parts are listed for the MK 25-2?
Regulator with cover gasket 098770, capsule 5H2 376174 and body gasket 92.7 x 102 x 1 under code 087095.


















Reviews
There are no reviews yet.