Brand:

Pepperl+Fuchs KFD2-WAC2-Ex1.D Strain Gauge Converter

Description

Pepperl+Fuchs KFD2-WAC2-Ex1.D overview

The Pepperl+Fuchs KFD2-WAC2-Ex1.D is a one-channel isolated barrier from the K-System of Pepperl+Fuchs for strain gauges, load cells and resistance measuring bridges installed in a hazardous area. It provides a 5 V excitation voltage, and its A/D converter also allows its use with devices needing 10 V. Up to four 350 ohm strain gauges connected in parallel can be powered and evaluated.

The datasheet released on 31 May 2023 lists a current output of 0 to plus or minus 20 mA or a voltage output of 0 to plus or minus 10 V, two relay contact outputs with programmable high and low alarms, line fault detection and an RS-485 interface. Measured values can be transmitted over RS-485 with 20-bit resolution, with up to 31 converters on the Power Rail.

Key features of the Pepperl+Fuchs KFD2-WAC2-Ex1.D

  • Strain gauge input for full or half bridges, load cells and measuring bridges
  • 5 V excitation, up to four 350 ohm gauges in parallel
  • Output 0 to plus or minus 20 mA or 0 to plus or minus 10 V
  • Two relay outputs with programmable high and low alarm
  • RS-485 interface with 20-bit resolution, up to 31 converters
  • Line fault detection and a collective error message output
  • Tare adjustment of 0 to 500 percent of span
  • Powered from 20 to 35 V DC via Power Rail or terminals 23 and 24

KFD2-WAC2-Ex1.D technical specifications

The values below are taken from the manufacturer datasheet of the KFD2-WAC2-Ex1.D, release date 2023-05-31. Always confirm the current datasheet and the certificates before final engineering.

Parameter Value
Model KFD2-WAC2-Ex1.D, Strain Gauge Converter, 1-channel isolated barrier
Signal type Analog input
Supply 20 to 35 V DC, Power Rail or terminals 23+, 24-
Power consumption Up to 3 W
Interface RS-485 via Power Rail or terminals 19+, 20 GND, 21-; programming socket
Field circuit Terminals 1+, 2-, 3+, 4-, 5+, 6-; lead resistance up to 25 ohm per line
Strain gauge resistance Resulting resistance 116 ohm to 10 kilohm
Input I signal Minus 100 to 100 mV; input resistance above 1 megohm
Tare Programmable 0 to 500 percent of span
Relay outputs I and II 253 V AC / 2 A / 500 VA / cos phi at least 0.7; 40 V DC / 2 A resistive
Analog output III Minus 20 to 20 mA; resolution and accuracy up to 0.05 percent
Ambient temperature Minus 20 to 60 degrees C
Dimensions / mass 40 x 119 x 115 mm (W x H x D), housing type C2 / about 250 g

The hazardous-area parameters are listed per terminal pair in the datasheet. Use the entity values of the exact terminals you wire, and refer to the certificate for the permitted cable parameters of your installation.

Typical applications in oil and gas, utilities, water and manufacturing

Many hazardous-area measurements need more than a simple repeater: temperature sensors, load cells and HART devices all need conditioning, scaling or trip alarms close to the signal source. The KFD2-WAC2-Ex1.D combines the intrinsically safe interface with that processing in a single K-System module, which keeps cabinets compact.

In refineries, gas plants, power stations, water works and manufacturing sites in Oman and the GCC, such modules are used on furnace and bearing temperatures, tank weighing, batching and loop monitoring. Configuration through the keypad or PACTware allows technicians to set ranges, alarms and fault behaviour without rewiring.

Selection and compatibility notes for KFD2-WAC2-Ex1.D

Confirm that the input and output types of the KFD2-WAC2-Ex1.D match your loop. The datasheet lists the accepted sensor types, ranges and output signals, and any output that is not intrinsically safe must be wired in the safe area. Check the supply method and the housing width against your cabinet layout.

Check the relay or analog output against the receiving device, and decide how you will configure the module. If you need a different input type, number of outputs or functional safety level, send us your loop data and we will compare neighbouring variants against the KFD2-WAC2-Ex1.D.

Installation and commissioning of the KFD2-WAC2-Ex1.D

Before mounting the KFD2-WAC2-Ex1.D, confirm the field device and cable parameters against the entity values in the datasheet and the certificate, and decide whether the module will be powered from a Power Rail, a termination board or its own supply terminals. Mount it in a clean, ventilated cabinet in the safe area, keep hazardous-area and safe-area wiring physically separated and labelled, and respect the spacing and marking required by your site rules for intrinsically safe circuits.

Wire the KFD2-WAC2-Ex1.D only to the terminal assignment printed in the wiring diagram, tighten the screws and check that no strands are left outside the clamp. After applying the supply, check the power indication, then simulate the field signal and prove the complete loop from field to control system before the plant is handed over. Record the as-found readings so that later loop checks of the KFD2-WAC2-Ex1.D can be compared with the commissioning values.

Maintenance and service life

The KFD2-WAC2-Ex1.D has no serviceable parts, so maintenance is mostly inspection. During planned shutdowns, check terminals for looseness and corrosion, verify the supply voltage at the module, and repeat the loop check that was recorded at commissioning. In coastal and humid locations such as Muscat, Sohar and Duqm, a clean, dry and sealed cabinet greatly extends the life of any electronic interface.

If a loop drifts out of tolerance or the unit shows no power indication with a healthy supply, replace the module instead of attempting a repair, and keep the replacement documentation in the loop folder. Certified intrinsically safe equipment must not be modified, and any change to cabling, load or field device should be re-assessed against the KFD2-WAC2-Ex1.D entity parameters before it returns to service.

Related products and ordering notes

Customers who ask for the KFD2-WAC2-Ex1.D often need neighbouring models or accessories from the same system, such as other K-System isolated barriers, the Power Rail and power feed modules, KFA6 power supplies and the matching NAMUR sensors. If you are standardising a cabinet or a spare parts list on one family, send us the loop list or the equipment list and we can quote the matching items together.

When you send an enquiry for the KFD2-WAC2-Ex1.D, quote the full part number exactly as printed on the nameplate, the quantity and the intended application. If you are replacing an installed unit, a photograph of the nameplate helps us confirm the exact variant you need. We can arrange a quotation with delivery to Oman and across the GCC.

Frequently asked questions about KFD2-WAC2-Ex1.D

The KFD2-WAC2-Ex1.D is a strain gauge converter for hazardous areas with 5 V excitation, a 0 to plus or minus 20 mA or 10 V output, two relays, RS-485 and a 40 mm wide housing.

Documents and quotation

A copy of the manufacturer datasheet for the KFD2-WAC2-Ex1.D is attached to this page for your engineering review. To request a quotation, send the RFQ with the part number KFD2-WAC2-Ex1.D, the quantity, the delivery location and any certification or documentation requirements, and we will reply with availability and lead time. Please check the specification against your loop or system requirements before ordering.

Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with Pepperl+Fuchs. Product names and part numbers are used only to identify the item you ask for.

Datasheets & Documents
  • PDF Datasheet KFD2-WAC2-Ex1.D Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFD2-WAC2-Ex1.D Strain Gauge Converter

Answers from our engineering team on installation, compatibility and integration.

01What can be connected to the KFD2-WAC2-Ex1.D?
Strain gauges, load cells and resistance measuring bridges, including up to four 350 ohm strain gauges in parallel.
02What outputs does it provide?
A current output of 0 to plus or minus 20 mA or a voltage output of 0 to plus or minus 10 V, two relay outputs and an RS-485 interface.
03How is it powered?
With 20 to 35 V DC from the Power Rail or from terminals 23+ and 24-.
04Which documents are available for the KFD2-WAC2-Ex1.D?
The manufacturer datasheet is attached to this page, and certificates or manuals can be requested together with your RFQ for the KFD2-WAC2-Ex1.D.
05How do I order the KFD2-WAC2-Ex1.D?
Send an RFQ with the part number KFD2-WAC2-Ex1.D, the quantity and the delivery location in Oman or the GCC, and Seven Star LLC will reply with availability and lead time.