Moore Industries IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP] Field I/P

Description

Moore Industries IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP] overview

The Moore Industries IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP] is a field-mounted current-to-pressure transmitter from the Moore Industries IPF family, built in a polyetherimide thermoplastic housing. It converts a 4-20 mA input into a 3-15 psig output on a 20 psi supply and includes the -FR1 filter, regulator and gauge.

The housing code WPMP stands for the metric (M20 x 1.5) version of the standard WP housing, with the P suffix adding the steel clamp set for mounting on a 2-inch pipe. The enclosure is designed for NEMA 4X and IP55 conditions and offers high heat, flame and chemical resistance.

The IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP] is useful where corrosive atmospheres or chemical washdown make a metal housing less attractive, for example coastal process areas, and where the plant uses metric conduit.

The part number written as IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP] is the model string given in the manufacturer datasheet as a worked ordering example for the IPF family, so it describes one complete, orderable configuration rather than a loose product family. Every field of the string (unit, input, output, supply or power, option and housing) can be changed when a different configuration is needed, and the datasheet table lists the allowed choices. If your plant standard differs from this example, send the configuration you need with your RFQ and we will check it against the table.

Key features of the Moore Industries IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP]

  • Polyetherimide thermoplastic housing with superior heat, flame and chemical resistance and high impact strength.
  • Housing material rated UL94V-0 flame retardant.
  • Vibration-resistant sensor, with less than 0.5% effect up to 10 g and 80 Hz.
  • Inherent RFI/EMI immunity without extra filters or terminals.
  • Surface mounting or 2-inch pipe mounting (P suffix adds two steel clamps).
  • -FR1 option: coalescing filter, miniature regulator and gauge in psi (0-60) and bar (0-4).

Technical specifications for IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP]

Parameter Value
Model string IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP]
Input 4-20 mA into 260 ohms nominal
Output 3-15 psig
Supply pressure 20 psi
Accuracy Less than 0.5% of span including linearity, hysteresis and repeatability (3-27 psig: not to exceed 1% of span)
Step response 0.3 seconds into 100 ml (6 cubic inches) at 90% of output span
Supply pressure effect Maximum 0.3% per 1.4 psig (0.3% per 0.1 bar)
Air consumption 0.1 SCFM, dead-ended
Air capacity 1.4 SCFM maximum
Ambient range -40 to +60 degrees C (-40 to +140 degrees F)
Electrical entry WPM: M20 x 1.5 female; WP: 1/2-inch NPT female
Enclosure size About 96 mm x 96 mm x 140 mm high, excluding the filter/regulator
Weight Approximately 1 lb 12 oz (800 grams)
Certifications CSA general location; CSA and FM non-incendive Class I, Division 2 (WP housing); ATEX Type N; TUV intrinsically safe transducer on WPM/N; SAA Type N; CE conformant

The values above come from the manufacturer datasheet for the IPF family. Specifications can depend on the option and housing chosen, so always read the matching page of the datasheet before you finalise a purchase specification, and keep the full model string on your purchase documents.

Typical applications in Oman and the GCC

Current-to-pressure converters sit between an electronic control system and a pneumatic device. Common uses in the region include:

  • Oil and gas wellhead, pipeline and processing sites, where pneumatic control valves and actuators are driven from a DCS or PLC.
  • Power and desalination plants, for dampers, steam and water control valves and other pneumatic final elements.
  • Water and wastewater facilities, for pneumatic valves on dosing, aeration and distribution lines.
  • Manufacturing plants that retrofit electronic control onto older pneumatic actuators and positioners.

Running a two-wire signal cable instead of long runs of instrument tubing reduces installation effort, and the converter can be placed next to the valve or actuator for a short, fast pneumatic connection.

Selection and compatibility notes

The datasheet lists several options besides -FR1: -TF1 (plastic tubing fitting for 1/4-inch O.D. tubing, not available with -FR1), -FMD2 (FM non-incendive), -ISE (TUV intrinsically safe), -NA (SAA Type N) and -NE (Moore Type N, requires the WPM housing). The IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP] carries -FR1 only.

Compare the IPF with the aluminum IPH or the explosion-proof IPX if your area classification requires a metal or explosion-proof enclosure.

Check the pneumatic side first. The output range (for example 3-15 psig, 0.2-1 bar or 20-100 kPa) must suit the actuator or positioner, and the supply pressure given in the model string must match the output range, because the datasheet states that the output must match the supply pressure to its right in the ordering table. Reverse-acting ranges such as 15-3 psig are available when the valve logic requires them.

Then check the electrical side: the loop must be able to drive the stated input impedance, and any hazardous-area certification you need must be present in the option field. Mounting style, conduit entry thread (NPT or metric) and whether pipe-mounting hardware is required are set by the housing designator at the end of the model string.

Questions to settle before ordering IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP]:

  • What pneumatic output range and supply pressure does the actuator need?
  • Is a direct or reverse output required?
  • Is a filter/regulator or pressure gauge option required?
  • Which conduit thread and mounting arrangement suit the site?
  • Which hazardous-area approval is required, if any?

Installation and commissioning

The polymer housing should be protected from impact and from solvents that are not listed as compatible in the datasheet or by the manufacturer.

Mount the transmitter close to the pneumatic device it serves, supply it with clean, dry, regulated instrument air only, and connect the pneumatic output port to the actuator. The datasheet notes that the unit can be mounted in any position but should be calibrated in its final orientation, so do the zero and span adjustments after the unit is fixed in place.

Wire the two-wire 4-20 mA loop with the correct polarity, seal the conduit entry as required by the area classification, then apply a 4 mA signal and adjust zero, followed by 20 mA and adjust span. Repeat until both points are within tolerance, then check mid-range.

Maintenance and service life

Most field problems with I/P converters are caused by contaminated or wet supply air. Keep the supply filter and regulator serviced, drain moisture regularly and confirm the supply pressure still matches the model string. The datasheet describes an optional coalescing filter and regulator for this purpose.

At scheduled shutdowns, run a five-point calibration check against a reference pressure gauge and mA source. Replace the unit or send it for repair if it cannot be brought within the published accuracy.

Related products and ordering notes

Related Moore Industries current-to-pressure products on this site include the IPT2 transmitter. Other housings in the same family (DIN-rail, polymer field-mount, aluminum field-mount and explosion-proof) cover different environments, so tell us where the unit will be installed if you are unsure which one to quote.

State the complete model string, including options and housing, when you ask for a price, and mention whether a datasheet or certificate is required with the delivery.

Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Product names and model designations belong to their owners and are used here only to identify the equipment you are asking about.

Frequently asked questions in brief

  • What does the IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP] do? It converts 4-20 mA to 3-15 psig using a 20 psi supply, in a polyetherimide field housing with a filter/regulator.
  • What does WPMP mean in the IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP]? WPM is the metric M20 x 1.5 version of the housing and P adds clamps for a 2-inch pipe.
  • What is the enclosure rating of the IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP]? The datasheet describes the housing as designed to NEMA 4X, IP55 requirements.
  • What is the weight of the IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP]? The family weighs approximately 800 grams (1 lb 12 oz).
  • How do I get a quotation for the IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP]? Send an RFQ with the part number, quantity and delivery location in Oman or the GCC.

Documents and quotation

The manufacturer datasheet for the IPF family is available for download from this page, and it contains the full ordering table, dimensional drawings and wiring diagrams referred to above. To request a quotation, send an RFQ that includes the part number IPF/4-20MA/3-15PSIG/20PSI/-FR1 [WPMP], the quantity you need, the delivery location in Oman or the GCC and any special requirements such as certification or documentation. We will confirm availability and lead time and reply with a written offer. Please check the datasheet and your own hazardous-area and safety requirements before you place an order.

Datasheets & Documents
  • PDF Datasheet IPF Field-Mounted Current-to-Pressure Transmitter Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Moore Industries is an American manufacturer of signal interface instruments, founded in 1968 by engineer Leonard W. Moore in North Hills, California. Its first product was the SCT signal converter, built in a friend's workshop. The company has been at its North Hills headquarters since 1974 and still designs and builds its products there, known for rugged aluminium housings.

Seven Star LLC, an independent supplier in Oman, lists Moore Industries temperature transmitters, limit alarm trips, isolators and a PID backup controller, and sources units and replacements by full model number.

Moore Industries company profile

Founded 1968, North Hills, California, USA, by Leonard W. Moore
Headquarters North Hills, California, since 1974
Ownership Privately owned (Moore Industries-International, Inc.)
First product SCT signal converter
Product families Signal isolators and converters (ECT, SCT), temperature transmitters (TRY, THZ), alarm trip units (SPA), miniMOORE multichannel signal conditioners, HART interfaces, SIL-rated safety logic solvers (STA)

Milestones

  • 1968: Leonard W. Moore founds the company and builds the first SCT signal converter.
  • 1974: The company moves into its North Hills headquarters.
  • 2009: miniMOORE wins a Control Engineering Engineers' Choice Award.

Moore Industries product families on this page

The manufacturer's catalog is arranged by function, and many of the items listed here map onto it directly:

  • Temperature transmitters: the TRX, and the STZ functional safety dual input smart HART transmitter
  • Alarm trips: the SPA2 programmable limit alarm trip, including an SPA2 with HLPRG input and four relay outputs
  • Signal isolators, repeaters and converters: the SIX
  • PID controllers and backup stations: the 535 in 1/4 DIN format

Other catalog groups include temperature assemblies and sensors, I/P and P/I converters, remote I/O, HART gateways and interfaces, indicators, and fieldbus device couplers.

Where Moore Industries instruments are used

These are control room and marshalling cabinet devices, plus field-mounted transmitters. Typical jobs are isolating a 4-20 mA loop between two systems, converting a thermocouple or RTD signal for a DCS input, adding an independent high or low trip next to the control system, and keeping a control loop running on a backup station when the main controller is out of service. Process plants in oil and gas, chemicals and power across the GCC use them for exactly these tasks.

Moore Industries products we list

Family Examples
Controllers & Data Acquisition Moore 535-21120BD000 | Industrial PID Ba…, SPA2 Programmable Limit Alarm Trip, Moore-SPA2HL Associated IS Programmable…
Isolator & Barrier HIM Smart HART Loop Interface and Monitor, SIX Signal Isolator, SLA SIL 2/3 Safety Logic Solver and Alarm
Temperature Instrumentation STZ Functional Safety Dual Input Smart H…, TRX Temperature Transmitter
Industrial Communications HES HART to Ethernet Gateway
Valve Positioners IPT2 Current-to-Pressure I/P Transmitter

Ordering Moore Industries instruments: what we need

Moore Industries model numbers are built from fields separated by slashes: unit, input, output, power and options, followed by the housing code in brackets. Every field matters. Send the complete string from the label, the serial number, and for programmable units the input type and range you want set. State any hazardous area or functional safety requirement, because approved versions are ordered with their own option codes.

Facts checked against trade press obituaries of Leonard W. Moore (Control Engineering, Control Global), October 2026.

FAQ

Questions about the Moore Industries IPF/4-20MA/3-15PSIG/20PSI/-FR1

Answers from our engineering team on installation, compatibility and integration.

01What does the {pn} do?
It converts 4-20 mA to 3-15 psig using a 20 psi supply, in a polyetherimide field housing with a filter/regulator.
02What does WPMP mean in the {pn}?
WPM is the metric M20 x 1.5 version of the housing and P adds clamps for a 2-inch pipe.
03What is the enclosure rating of the {pn}?
The datasheet describes the housing as designed to NEMA 4X, IP55 requirements.
04What is the weight of the {pn}?
The family weighs approximately 800 grams (1 lb 12 oz).
05How do I get a quotation for the {pn}?
Send an RFQ with the part number, quantity and delivery location in Oman or the GCC.