Schneider Electric A9L16482 Acti9 iPRD1 12.5 Surge Arrester

Description

A9L16482 iPRD1 12.5 surge arrester, three-phase plus neutral (3P + N)

The A9L16482 is Schneider Electric’s iPRD1 12.5 from the Acti9 line: a Type 1 + 2 combined surge arrester with a pluggable cartridge, built around an impulse-current rating (Iimp) of 12.5 kA in differential mode and 50 kA in common mode N/PE. It is a 3P + N device for 230/400 V AC (± 10 %) at 50/60 Hz networks, with a remote-signalling contact, and it is built for the TT, TN-S earthing arrangements named in its datasheet. Seven Star LLC supplies the A9L16482 in Oman and the GCC as an independent supplier based in Muscat.

This page reads the official datasheet of the A9L16482 and turns it into selection notes: what the ratings mean for a distribution board, which upstream protection the maker pairs with it, how it differs from the neighbouring models in the range, and what to send us when you ask for a quotation. It is a fixed-ratings component, so every number on this page is taken from the datasheet and nothing is inferred beyond it.

What the A9L16482 ratings mean in practice

The headline figure of this unit is its combined test class. A Type 1 + 2 arrester is rated with the impulse-current waveform used for lightning-current testing as well as the nominal and maximum discharge currents of Type 2 devices. The datasheet gives Iimp of Common mode: 50 kA N/PE; Differential mode: 12.5 kA L/N, a nominal discharge current of 20 kA and a maximum of 50 kA. Voltage protection level is stated as 1.5 kV type 1 + 2.

Because A9L16482 combines MOV and GDT technology, the neutral-to-earth path uses a spark-gap element, which is why its N/PE common-mode rating is the larger 50 kA while L/N is 12.5 kA. The rated continuous voltages are Differential mode: 350 V L/N; Common mode: 255 V N/PE, and the temporary-overvoltage behaviour is listed as 337 V L/N 5 s withstand; 1200 V N/PE 200 ms safe failure mode.

A9L16482 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / A9L16482
Range / product name IPRD1 (Acti9 iPRD1)
Product type Surge arrester with pluggable cartridge
Device short name iPRD1 12.5
Poles 3P + N
Remote signalling With (1 SD (1 C/O))
Surge arrester class Type 1 + 2
Technology MOV + GDT
Rated operational voltage 230/400 V AC (± 10 %) at 50/60 Hz
Earthing system TT / TN-S
Nominal discharge current 20 kA
Maximum discharge current 50 kA
Impulse current Iimp Common mode: 50 kA N/PE; Differential mode: 12.5 kA L/N
Maximum continuous operating voltage Uc Differential mode: 350 V L/N; Common mode: 255 V N/PE
Voltage protection level Up (maximum) 1.5 kV type 1 + 2
Temporary overvoltage Ut 337 V L/N 5 s withstand; 1200 V N/PE 200 ms safe failure mode
Standards EN 61643-11:2012 and IEC 61643-11:2011
Certifications / labels CE, EAC, VDE
Mounting Clip-on (DIN rail); 8 modules of 9 mm
Dimensions H x W x D 89 mm x 72 mm x 69 mm
Net weight 619 g
Terminals Tunnel type terminal (phase) 10–25 mm² flexible; Tunnel type terminal (phase) 10–35 mm² rigid; Tunnel type terminal (earth) 16–25 mm² flexible; Tunnel type terminal (earth) 16–35 mm² rigid
Tightening torque 3.5 N.m
Operating temperature -25–60 °C
Storage temperature -40–80 °C
Warranty 18 months

Poles, earthing and wiring of the A9L16482

The three line conductors and the neutral are all protected by the same unit, which is why it is two modules wide at nine-millimetre pitch. This is the arrangement for a standard three-phase four-wire board.

The earthing arrangement named on the datasheet is TT and TN-S. Terminals are Tunnel type terminal (phase) 10–25 mm² flexible; Tunnel type terminal (phase) 10–35 mm² rigid; Tunnel type terminal (earth) 16–25 mm² flexible; Tunnel type terminal (earth) 16–35 mm² rigid, tightened to 3.5 N.m. The wire-stripping length is 14 mm. Keep the earth conductor between the arrester and the main earth bar as short and straight as the board layout allows, because inductance in the lead adds directly to the let-through voltage.

Backup protection paired with the A9L16482

A surge arrester needs short-circuit protection in series so that a failed cartridge or element is isolated from the network. The datasheet of this unit names the associated devices below. The ampere figure shown is the rating of that breaker or fuse, and Icu is the breaking capacity quoted for it.

  • Associated fuse gG 160 A 120 kA standard
  • Associated circuit breaker Compact NSX160E 80 A 25 kA standard

A9L16482 against the other models in the range

The table compares this unit with related Acti9 surge arresters, using the figures printed in each datasheet. Pole count, remote contact and maximum discharge current are the three differences that drive most selections.

Part number Device Poles Remote contact Type Imax
A9L08601 iPRD8r 3P + N With Type 2 + 3 8 kA
A9L15688 iPF K 3P + N Without Type 2 40 kA
A9L15693 iPF K 3P + N Without Type 2 20 kA
A9L16282 iPRD1 12.5 1P + N With Type 1 + 2 50 kA (Iimp 12.5 kA L/N)
A9L16482 (this page) iPRD1 12.5 3P + N With Type 1 + 2 50 kA (Iimp 12.5 kA L/N)
A9L20600 iPRD20 3P + N Without Type 2 20 kA

Installation and maintenance of the A9L16482

  • Fit the arrester with its associated breaker or fuse on the same DIN rail (clip-on (din rail)), using the 8 module positions the unit occupies.
  • Observe the operating window of -25–60 °C; a board in direct sun or with little ventilation can exceed it.
  • Tighten to 3.5 N.m and re-torque after the first thermal cycles of commissioning.
  • Wire the remote contact (1 SD (1 C/O), ) to a PLC input or a building-management point so that a failed cartridge raises an alarm instead of waiting for an inspection.
  • The datasheet describes mechanical indicators: white while operating and red at end of life, on the device itself.

After a major lightning event or a supply fault, inspect surge protection even when no alarm has been raised. Keep a spare cartridge or a complete spare A9L16482 for plants where downtime is expensive; send us the part number and we will confirm what can be supplied.

Selection checklist for the A9L16482

  • Confirm the system: 230/400 V AC (± 10 %) at 50/60 Hz, earthing TT and TN-S.
  • Confirm pole count (3P + N) against the board: single-phase, three-phase with neutral, or four-pole.
  • Decide whether a remote contact is needed (this version has one).
  • Check the class: Type 1 + 2; match it to the position in the installation and to the lightning exposure.
  • Check the voltage protection level (1.5 kV type 1 + 2) against the withstand level of the loads downstream.
  • Choose the backup breaker or fuse from the list on this page and confirm it fits the board’s short-circuit level.

Where the A9L16482 is used in Oman and the GCC

The Type 1 + 2 rating suits boards at the service entrance of buildings that have an external lightning protection system or overhead supply lines, such as villas, small commercial premises, mosques, schools and clinics, which is also the market segment named on the datasheet (residential and small commercial). Lightning activity in the mountains, long overhead feeders to remote sites and hot, dusty switchrooms make surge protection and good board ventilation worth planning together. Check the ambient range on the datasheet against the real temperature inside the cabinet, not the room.

Documents and quotation

The official Schneider Electric datasheet of this unit is attached on this page for download, so the ratings above can be checked against the source.

To request a quotation, send us the part number A9L16482 with the quantity and delivery location through the RFQ form. Seven Star LLC replies with availability and lead time.

Other Models in the Se Surge Iprd1 Range

Seven Star LLC supplies models from the Se Surge Iprd1 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric A9L16282 Acti9 iPRD1 12.5 Surge ArresterSwitchgear, Enclosures & DistributionView details
Schneider Electric A9L16482 Acti9 iPRD1 12.5 Surge ArresterSwitchgear, Enclosures & DistributionYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric A9L16482 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric A9L16482 Acti9 iPRD1 12.5 Surge

Answers from our engineering team on installation, compatibility and integration.

01What is the A9L16482?
It is the Schneider Electric Acti9 iPRD1 12.5, a 3P + N Type 1 + 2 surge arrester for 230/400 V AC systems, with a remote-signalling contact. It clips onto a DIN rail and occupies 8 modules of 9 mm.
02What discharge ratings does the A9L16482 have?
The datasheet lists 20 kA as nominal and 50 kA as maximum discharge current, with an impulse current of Common mode: 50 kA N/PE; Differential mode: 12.5 kA L/N.
03Which backup protection is listed for the A9L16482?
The datasheet names associated breakers and fuses, for example Associated fuse gG 160 A 120 kA standard. The full list is on this page, and the choice depends on the short-circuit level at the board.
04Does the A9L16482 have a remote contact?
Yes. It has a remote-signalling output described as 1 SD (1 C/O), rated , which can report cartridge status to a PLC or monitoring system.
05What operating temperature range applies to the A9L16482?
The datasheet gives -25…60 °C in operation and -40…80 °C in storage, with relative humidity of 5…95 % and an altitude up to 2000 m.