Brand: TLV
TLV JH5RL-P Free Float Steam Trap for High Pressure
Description
A cast steel Free Float trap for medium to high pressure process steam
The TLV JH5RL-P is a cast steel Free Float steam trap for small to medium-size process equipment and steam mains running at higher pressures. A self-modulating, precision-ground float gives continuous, low-velocity condensate discharge as load changes, and a constant water seal with three-point seating keeps the trap steam-tight even under no-load conditions. The P in the model code means there is no automatic air vent: TLV positions the JH-P type for steam mains and processes over 4.6 MPaG with extended continuous operation and little entrained air. The same specification sheet covers the JH5RH-P for pressures up to 8.0 MPaG.
Technical specifications
| Parameter | Specification |
|---|---|
| Model | JH5RL-P (cover carbon steel A105) and JH5RH-P (cover cast steel A216 Gr.WCB) |
| Connection and size, JH5RL-P | Screwed 15, 20, 25 mm; socket welded 15 to 50 mm; flanged 15 to 50 mm |
| Orifice numbers, JH5RL-P | 2, 5, 10, 14, 22, 32, 40, 46, 65 (JH5RH-P: 80) |
| Max. operating pressure PMO | 0.2 to 6.5 MPaG depending on orifice (JH5RH-P: 8.0 MPaG) |
| Max. differential pressure | Equal to PMO for each orifice number |
| Minimum operating pressure | 0.01 MPaG |
| Max. operating temperature TMO | 425 °C |
| Pressure shell PMA / TMA | 6.5 MPaG (JH5RL-P) or 8.0 MPaG (JH5RH-P) / 425 °C |
| Body | Cast steel, ASTM A216 Gr.WCB |
| Float | Stainless steel SUS316L (AISI316L), precision ground |
| Screen | Stainless steel SUS430, built in, large surface area |
| Cover gasket | Graphite/stainless steel |
| Cover bolts | Alloy steel, ASTM A193 Gr.B16 |
| Face-to-face L, screwed or socket weld | 234 mm (15), 246 mm (20), 258 mm (25) |
| Weight, screwed or socket weld | 6.5 to 6.7 kg for 15 to 25 mm |
| Flanged length, Class 600 RF | 239 mm (15), 264 mm (20), 309 mm (25), 290 mm (40), 300 mm (50); weights 8.4 to 19 kg |
How it fits within the JH series
TLV groups the JH series by venting type. JH-X models carry an X-element air vent for processes up to 3.2 MPaG that need hot air discharged, JH-B models use a bimetal vent for steam processes above 3.2 MPaG, and JH-P models are plain float traps for the highest pressures. A manual air vent or a pressure balancing tube can be fitted at the threaded connection on the cover. Neighbouring models on TLV’s list include the JH5RL-B (4.6 MPaG), JH5RL-X (3.2 MPaG) and the JH7 series for up to 12 MPaG.
| Model | PMO | TMO | Air venting |
|---|---|---|---|
| JH5RL-X | 3.2 MPaG | 240 °C | X-element air vent |
| JH5RL-B | 4.6 MPaG | 425 °C | Bimetal air vent |
| JH5RL-P | 6.5 MPaG | 425 °C | No automatic vent |
| JH5RH-P | 8.0 MPaG | 425 °C | No automatic vent |
Selection and documents
Choose the orifice number from the actual differential pressure, since PMO and the allowable differential pressure change with the orifice fitted. Check the weld or flange standard against the line, and confirm that the application suits a trap without an automatic air vent. For a clean-steam alternative see the steam trap category, or compare with the
. The attached TLV specification sheet lists parts by material, dimensions for each end connection and the discharge capacity charts. Send steam conditions and the end connection with your enquiry, and confirm the model code against current TLV documents before ordering.
Datasheets & Documents
- Datasheet TLV JH5RL-P / JH5RH-P specification sheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
TLV is a Japanese manufacturer of steam system equipment whose range centres on steam traps, with pressure reducing valves, control valves, condensate recovery pumps and related products for steam and condensate lines. The company traces its origin to Fujiwara Manufacturing, founded in Kakogawa in 1950 and renamed TLV in 1972. Seven Star LLC, an independent supplier in Muscat, offers TLV products to industrial buyers on request.
TLV steam traps and steam system products
TLV steam traps are grouped by operating principle: Free Float mechanical traps for process equipment and steam mains, PowerDyne and thermodynamic disc traps, thermostatic traps and clean steam traps. The catalogue also lists cyclone separators, separator filters, check valves, strainers, air vents, manifolds, steam trap stations and condensate recovery pumps. Each product has a numbered specification sheet that gives pressure and temperature limits, materials by part, dimensions and a discharge capacity chart.
Choosing a TLV product
Selection starts from steam pressure, back pressure, condensate load and the type of equipment being drained. Send the operating conditions and the model code with your enquiry and Seven Star LLC will confirm the model and documents before you order.
Related products
Frequently Asked Questions
It denotes the plain float version without an automatic air vent, aimed at steam mains and processes over 4.6 MPaG.
Up to 6.5 MPaG depending on the orifice number; the JH5RH-P goes to 8.0 MPaG.
425 degrees C for both JH5RL-P and JH5RH-P.
Screwed (15, 20, 25 mm), socket welded and flanged (15 to 50 mm).
Yes. A manual air vent or pressure balancing tube can use the threaded connection on the cover.