West Control Solutions KS 94 96 x 96 Industrial Process Controller

Description

Overview

West Control Solutions KS 94 is a 96 x 96 mm industrial and process controller from the PMA brand of West Control Solutions, aimed at loops that need tight tolerances and high plant availability. Where compact controllers handle one process value, the KS 94 can be configured for ratio control, three-element control, mean-value calculation from two process values, and cascade or override schemes, and it adds a programmer with search function and a real-time clock. Menu-guided operation with plain-text displays and a spray-water proof IP65 front make it a favourite for boiler houses, blending lines and combustion control where several signals meet in one instrument.

Seven Star LLC is an independent supplier serving Oman and the GCC, and the notes on this page follow the manufacturer datasheet for the KS 94.

Control modes unique to the KS 94

  • Ratio control: suited to stoichiometric combustion, mixing ratios, additives, batching and inline blending.
  • Three-element control: for example level control in a steam boiler using level, steam flow and feed-water flow.
  • Mean value calculation: two process values are averaged, with a weighting factor.
  • Feed-forward and override: line out disturbances in steam plants, or let several controllers act on one actuator.
  • Setpoint, setpoint/cascade and programmer control, each with a possible offset that is additive, such as a reduced standby setpoint, or multiplicative, such as an oxygen correction.

The output function can be set to delta/star/off, position control, split-range control and many three-point combinations of switching and continuous outputs. DAC, short for Digital Actuator Control, monitors the actuator on three-point stepping and continuous controllers with position feedback, and can detect a blocked actuator, a defective motor or a failed capacitor before large deviations develop.

Technical data of West Control Solutions KS 94

Item Value
Front / cut-out 96 x 96 mm, panel cut-out 92 +0.8 mm each way; plug-in module inserted from the front
Input INP1 Universal: thermocouples L, J, K, N, S, R, T, W(C), E, B; Pt100 and 2 x Pt100 difference; potentiometer; 0/4-20 mA; 0/2-10 V; measurement cycle 200 ms
Accuracy examples K 0 to 1350 C error up to 2 K; S and R 0 to 1760 C up to 3 K; Pt100 -200 to 850 C up to 0.5 K; voltage 0.1%
Further inputs INP5 differential amplifier, INP6 potentiometer or current, optional INP3 and INP4, up to 12 digital inputs
Programmer 3 programs of 20 segments each, one analog output and four switching outputs
Relay outputs Changeover, 500 VA, 250 V, 2 A at 48-62 Hz; minimum 12 V, 10 mA
Continuous output 0/4 to 20 mA configurable, load 600 ohm, resolution 12 bit
Transmitter supply 17.5 V DC / 22 mA (optional, galvanically isolated)
Display Multi-function LC display with red backlight, 4-digit value and setpoint, bargraph, up to 12 user texts of 16 characters
Interfaces Front interface standard; TTL or RS422/485 (ISO 1745, 2400-19200 bit/s, 32 units), PROFIBUS-DP or INTERBUS options
Supply 90 to 260 V AC 48-62 Hz, about 10 VA, or 24 V UC (24 V AC / 24 V DC), tolerance +10 / -15%
Environment Operation 0 to 60 C, specified accuracy 0 to 55 C, storage -20 to 60 C, 75% annual mean humidity
Protection / housing Front IP65, housing IP20, terminals IP00; Makrolon 9415, UL 94 V0; weight up to 1.5 kg with all options
Real-time clock Optional, buffered for at least 2 days
EMC / safety EN 50081-2 and EN 50082-2; EN 61010-1, overvoltage category III, contamination class 2

How KS 94 differs from other KS 9x variants

  • Compared with the KS 90-1 and KS 92-1, it uses a backlit plain-text LC display rather than a 7-segment day and night display, and its input cycle is 200 ms instead of 100 ms.
  • It offers ratio, three-element and mean-value controllers and a built-in programmer of 3 programs with 20 segments, which the standard KS 90-1 and KS 92-1 do not.
  • Its fieldbus options are PROFIBUS-DP and INTERBUS next to RS422/485, whereas the KS 9x-1 series lists Modbus RTU and Profibus-DP.
  • It is the older platform. The product page refers to the KS 98-2 as the equivalent multi-function device.

Inputs, alarms and the operator display

Inputs INP1, INP5 and INP6 are galvanically connected, and each has a configurable filter with a time constant from 0 to 999.9 seconds. Every input and output signal can be scaled, linearised with seven segments or square-rooted, so a differential-pressure flow signal can be turned into a flow reading without extra hardware. Sensor and lead monitoring detects break and short circuit, and the action on failure is configurable: outputs switch off, hold a minimum or maximum value, or move to a fixed second output value. Four alarms can monitor the process values, control deviation, setpoints, controller output, position feedback, programmer times and, on fieldbus versions, bus status, with optional suppression during start-up or after a setpoint change.

The red backlit LC display shows the effective process value and the setpoint in four digits, with a bargraph for output, deviation, elapsed program time or status. An engineering unit or a five-character tag number can be shown, and up to twelve user-defined texts of sixteen characters can be triggered by alarms, control outputs or digital inputs, so an operator reads a sentence such as a fault description instead of a code. An extended operating level can hold twelve parameters and signals that the operator is permitted to change. Select the measurement correction function if a field sensor needs a trim, and the extended function set if the programmer is required.

Programmer and timing functions

The programmer stores three programs of 20 segments, drives one analog output that can serve as an external setpoint, and offers four switching outputs. Program selection comes from the front panel, the interface or control inputs. After a power failure the controller can continue, switch to a fixed setpoint, search automatically for the point on the profile, or continue at the time mark when the real-time clock returns. At the end of a program it can pause, reset, continue with the next program or reset and start the next. Timer functions on the RS 485 version include single-shot events by minute, hour, day, month and year.

Ordering structure of West Control Solutions KS 94

The ordering block for West Control Solutions KS 94 chooses the connector type (flat pin or screw terminals), the basic version with or without transmitter power supply and the mains or 24 V supply with four relays or three relays plus a current or logic output, the serial interface option (none, TTL, RS422, PROFIBUS-DP or INTERBUS), extension option C with inputs INP3 and INP4, OUT3 and digital inputs, extra functions (none, measurement correction, or correction plus programmer) and a pre-configuration such as a two-point heating controller, a motorised stepping controller, a continuous controller, a three-point controller or a three-element controller. A code beginning 9407 appears in the datasheet configuration examples. Confirm the complete code from the nameplate before ordering.

Where it works in Oman and the GCC

Power and desalination boilers use three-element drum level control, burner houses use ratio control for fuel and air, and chemical plants use it for blending and dosing recipes. The programmer suits furnaces, autoclaves and test chambers with profile control. The IP65 front is resistant to splashes, and the 0 to 60 degree C operating range covers most control rooms and enclosures when ventilation is adequate.

Installation, engineering and spare strategy

Mount the module in the 92 mm cut-out with two clamps. Use the Engineering Tool ET/KS 94 and a PC adapter on the front interface for configuration and commissioning, and the SIM/KS 94 simulation program to test settings against a simulated loop before running the plant. For the bus, an interface module is needed when TTL signals have to be converted to RS 422/485. Keep a spare of the exact variant because the options are factory-installed, and store the engineering file for each loop so that a replacement can be configured quickly.

Related items you may also need: Fuji Electric France PDA312C1-BCYCD-10 Compact Controller M (CC-M) | Woodward easYgen-3500XT Genset and Breaker Controller | Lovato LVM40A240 LVM40 Level Control Relay | All West Control Solutions products.

Documents and quotation

The manufacturer datasheet for the KS 94 is attached to this page. Please send an RFQ with part number KS 94, the full order code, quantity and delivery location in Oman or the GCC. Mention the connector style, supply, interface option and pre-configuration, and we will reply with availability and lead time.

Datasheets & Documents
  • PDF Datasheet West Control Solutions KS 94 96 x 96 Industrial Process Controller Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

West Control Solutions is the temperature and process control company that brings four long-established European and American instrument brands under one name: West, PMA, Partlow and CAL. Its controllers, limit devices, indicators, transmitters and recorders are built for plastics machinery, ovens, furnaces, laboratory equipment, packaging machines and food processing. West Control Solutions describes itself as part of Gems Sensors & Controls and is based in Brighton, United Kingdom, with offices around the world. The oldest roots go back to Partlow in 1920 and PMA in 1929, while West Instruments, established in 1946, is the group's centre of excellence for developing and manufacturing temperature and process controllers.

West Control Solutions company profile

Founded Brand heritage from Partlow (1920), PMA (1929), West Instruments (1946) and CAL Controls (1963), combined under the West Control Solutions name
Headquarters Brighton, United Kingdom, with offices worldwide
Ownership Part of Gems Sensors & Controls; the two companies merged in 2020
Core technology Microprocessor PID temperature and process controllers with self-tuning, limit controllers, indicators, transmitters and recorders
Typical applications Plastics and extrusion, ovens and furnaces, heat treatment, laboratory and test equipment, packaging machinery, food and beverage processing
Standards CE, UL, ULC and FM approvals on models such as the 6700+ limit controller; Modbus, Profibus and DeviceNet compatibility listed; EN 14597 type tests on the KS 9x-1 and KS 5x-1 series

Milestones

  • 1920: Partlow is established, later split into mechanical products and the electronic products that joined West Control Solutions.
  • 1929: PMA is established; it later belonged to Withof and Philips Industrial Electronic Corporation.
  • 1946: West Instruments is established and becomes one of the first makers of microprocessor-based temperature controllers.
  • 1963: CAL Controls is established in Hertfordshire and introduces the first 1/16 DIN controllers.
  • 2005: PMA joins the Danaher Corporation.
  • 2020: West Control Solutions merges with its sister company Gems Sensors & Controls.

How a self-tuning PID temperature controller works

A PID controller compares the measured temperature with the setpoint and computes an output from three terms: the proportional term reacts to the present error, the integral term removes the remaining offset over time, and the derivative term damps overshoot by watching how fast the error changes. The output then drives a relay, a solid-state relay, a triac or a linear signal to a heater, valve or damper. The practical difficulty is finding good tuning values for each process. West Control Solutions controllers offer pre-tune and self-tune routines that identify the response and set the terms automatically, and the KS 90-1 and KS 50-1 can tune to the actual setpoint without forcing the process to oscillate. Selection tip: use a solid-state or linear output for fast-cycling heaters and keep a separate limit controller on its own sensor for safety.

Where West Control Solutions products are used in Oman and the GCC

These controllers are found in plastics extruders and moulding machines, bakery and food ovens, desalination and utility skids, heat-treatment furnaces, laboratory chambers, bitumen and thermal-oil heating, boiler houses, packaging lines and compact electrical panels. Small 1/16 DIN units fit space-limited panels, while 1/4 DIN controllers handle ratio and three-element boiler loops.

West Control Solutions models we list

Family Examples
West Plus Series temperature controllers P6100, P8100
West limit controllers P6700
PMA KS 9x advanced line KS 90-1, KS 92-1, KS 94
PMA KS 5x universal line KS 50-1

Ordering West Control Solutions products: what we need

Controller order codes are built digit by digit, so the nameplate code matters more than the short model name. Please send the full code, the supply voltage, the input type and range, the output type in each slot, the communications option and the front format. For spares and replacements, add a photo of the nameplate and the machine type. Seven Star LLC is an independent supplier serving Oman and the GCC, and will confirm availability and lead time after your request for quotation.

Facts checked against West Control Solutions company, brand and news pages and the published product datasheets, November 2026.

FAQ

Questions about the West Control Solutions KS 94 96 x 96 Industrial

Answers from our engineering team on installation, compatibility and integration.

01Which control functions does the KS 94 add beyond a basic PID controller?
It can be configured for ratio control, three-element control, mean-value calculation, feed-forward, override control, cascade and a programmer with offset functions.
02How many programs does the KS 94 programmer store?
The built-in programmer holds 3 programs with 20 segments each, with one analog output and four switching outputs, plus an optional real-time clock buffered for at least 2 days.
03Which fieldbus options does the KS 94 offer?
Option B can be TTL, RS422/485 following ISO 1745, PROFIBUS-DP or INTERBUS, and RS422/485 supports 2400 to 19200 bit/s with up to 32 controllers per bus.
04What supply voltages does the KS 94 accept?
Versions are available for 90 to 260 V AC at 48-62 Hz or a universal 24 V supply, with a voltage tolerance of +10 / -15% and about 10 VA consumption.
05What is the front protection of the KS 94?
The front has IP65 spray-water protection, the housing is IP20 and the terminals IP00, with a Makrolon housing rated UL 94 V0.