Weidmuller 7760056081 DRM570110 110 V DC 4CO Relay
Description
Weidmuller 7760056081 DRM570110: four contacts on a 110 V DC coil
Weidmuller 7760056081 is the DRM570110, the four-pole member of the DRM plug-in relay range with a 110 V DC coil. It provides four changeover contacts in AgNi with flash gold plating, each rated 5 A at 250 V AC. Housing size is identical to the two-pole relay at 21 x 27.4 x 35.7 mm, weight is 34.3 g, and the cover is transparent with a mechanical position indicator. The 110 V DC rating makes it relevant in substations, switchgear control circuits and older power plant panels that run on 110 V battery systems.
Reading the datasheet of 7760056081
The coil data are 110 V DC, 10 mA, 1.2 W and a coil resistance of 11000 ohm plus or minus 10 percent. The contacts handle 5 A continuous, 10 A inrush for 50 ms, 1250 VA resistive AC and 120 W at 24 V DC. Switching delays are below 20 ms in both directions, and the mechanical service life is 20 million cycles. Minimum switching power is 10 mA at 12 V and 100 mA at 5 V. Insulation values are the same as other DRM relays: 250 V rated, 1.8 kV coil to contacts, 1 kV between neighbouring contacts and across an open contact, 6 kV impulse withstand, clearance and creepage 5.5 mm or more.
Technical table for 7760056081
| Parameter | Value |
|---|---|
| Order No. / Type | 7760056081 / DRM570110 |
| Coil | 110 V DC; 10 mA; 1.2 W; 11000 ohm plus or minus 10 percent |
| Contacts | 4 CO, AgNi flash gold-plated |
| Continuous current | 5 A at 250 V AC |
| Inrush | 10 A for 50 ms |
| AC capacity | 1250 VA resistive |
| DC capacity | 120 W at 24 V |
| Minimum load | 10 mA at 12 V; 100 mA at 5 V |
| Delay on / off | below 20 ms |
| Mechanical life | 20 x 10^6 cycles |
| Indicator | mechanical position indicator; no LED |
| Isolation | 1.8 kV coil to contact; 6 kV impulse |
| Dimensions / weight | 21 x 27.4 x 35.7 mm / 34.3 g |
| Temperature | ambient minus 40 to 60 C; storage minus 40 to 70 C |
| Humidity | 35 to 85 percent, no condensation |
| Approval | cURus E312083 |
| Pack | 20 items |
How 7760056081 differs from the DRM270024
The 2-pole DRM270024 (7760056051) offers 10 A contacts and 2500 VA but only two poles and a 24 V DC coil. The DRM570110 doubles the pole count to four, halves the current to 5 A and raises the coil voltage to 110 V DC. Coil current falls from 37.8 mA to 10 mA while coil power rises slightly from 0.9 W to 1.2 W, and the coil resistance increases from 650 ohm to 11000 ohm. Choose the four-pole relay when many independent circuits must be switched at once, such as interlock chains, indication and alarm circuits in one operation.
Typical use of 7760056081
Protection and control panels in utility substations in the Gulf often use 110 V DC auxiliary supplies. Four changeover contacts allow one relay to provide trip, alarm, indication and interlock outputs. Maintenance departments also keep this relay as a replacement for older panels where the relay is soldered into a socket that is still manufactured, avoiding re-engineering.
Installation advice for 7760056081
Fit the relay into a matching socket and check the DC operating voltage range graph in the datasheet. The coil should be driven by a stable 110 V DC supply, and a suppression device across the coil is advised to protect upstream contacts. Do not mix the maximum current of all four contacts without considering heating: the datasheet includes a derating curve in combination with a base.
Servicing 7760056081
Inspect contacts through the transparent cover, verify coil resistance with an ohmmeter (about 11000 ohm) and replace the relay if the reading is far outside tolerance or contacts show wear.
Specification advice for 7760056081
Choosing a 110 V DC relay is common in older electricity-industry installations where the battery system is a 110 V station battery. The coil is designed for the DC operating voltage range shown in the datasheet graph, and operation outside that range can cause chattering or failure to drop out. Since all four poles are changeover contacts, you can wire two contacts in series for higher breaking duty on DC loads, though the datasheet does not provide a rating for that arrangement and you should rely on load-limit curves instead. Minimum load requirements of 10 mA at 12 V and 100 mA at 5 V should be observed so that the contacts remain clean.
For documentation, note the approval cURus E312083, the RoHS compliance without exemption, and the absence of SVHC above 0.1 percent by weight. Temperature limits are minus 40 C to 60 C ambient and minus 40 C to 70 C storage, humidity 35 to 85 percent without condensation, which should be checked against the switchroom conditions in hot Gulf summers, especially in rooms without air-conditioning where cabinet temperatures can approach the limit.
The DRM relays are lightweight and require a socket with a retaining device in installations that vibrate; the relay should be restrained by the clip supplied with the socket to avoid contact bounce during transport and in service. Record the coil voltage on the panel schedule so that nobody replaces it with a 24 V relay by mistake, a fault that is easy to make because the bodies of all DRM relays look the same from the front.
Documents and quotation
The datasheet for 7760056081 is included with this page. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Please send an RFQ with 7760056081, quantity and delivery location to receive a quotation.
Installation and Commissioning Planning
Planning ahead shortens downtime when a Weidmüller 7760056081 goes into service. Confirm the available mounting space, cable entry or process connection, and the tools and spare seals needed on the day. Keep the existing configuration or calibration data so the new unit can be set up to match, and check that loop drawings and the asset register are updated after the swap. If the installation has to fit a short shutdown window, tell us the date when you request a quotation so that delivery of the Weidmüller equipment can be planned around it.
Typical Questions From Maintenance Teams
Maintenance engineers replacing a Weidmüller 7760056081 usually ask whether the new unit is a direct fit, whether settings can be copied from the old one, and whether any accessories must be ordered separately. The answer depends on the exact order code and the generation of the installed automation accessories, so the nameplate details are the best starting point. Send them with your request and we will check the match, point out any differences in connections or options, and list the parts needed so that the job can be finished in one visit.
Datasheets & Documents
- Datasheet Weidmuller 7760056081 DRM570110 110 V DC 4CO Relay Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Weidmüller is a German family-owned maker of electrical connection and industrial electronics products, headquartered in Detmold. The company dates from 1850 and was re-established in Detmold in 1948; it specialised in terminal blocks from the 1940s onward. Weidmüller makes Klippon terminal blocks, power supplies, remote I/O and enclosures, and reported over one billion euros in revenue in 2023.
Seven Star LLC lists Weidmüller PRO MAX power supplies and SAK terminal blocks, and supplies Weidmüller components to panel shops and plants in Oman and the GCC.
Weidmüller company profile
| Founded | 1850, Germany |
|---|---|
| Headquarters | Detmold, Germany (since 1948) |
| Ownership | Family-owned |
| Revenue | Over €1 billion (2023) |
| Product families | Klippon Connect terminal blocks, PRO MAX and PRO TOP power supplies, u-remote I/O and fieldbus couplers, Klippon enclosures, connectors and tools |
Milestones
- 1850: Weidmüller is founded.
- 1948: The company is re-established in Detmold.
Weidmüller products listed here
The listed power supplies are DIN rail switch-mode units with 24 V DC output: a PRO MAX single-phase unit rated 180 W and 7.5 A (85 to 277 V AC input), and a PRO MAX3 three-phase unit rated 240 W and 10 A (320 to 575 V AC input). The SAK series is the screw clamp feed-through terminal block family found in many existing panels. Weidmüller now flags several SAK types as being phased out and names a replacement for some of them.
Weidmüller products we list
Ordering Weidmüller parts: what we need
Weidmüller identifies every item by a ten-digit order number, and that number is the surest way to quote. Without it, send the type printed on the part. For power supplies add input voltage and phases, output voltage and current. For terminal blocks add the conductor cross-section, color, and the end plates, cross-connections and markers you need, since accessories are specific to each series.
Facts checked against Weidmüller milestone lists and distributor profiles, October 2026.
Browse Weidmüller products by category: Electrical & Power Modules.
FAQ
Questions about the Weidmuller 7760056081 DRM570110 110 V DC 4CO Relay
Answers from our engineering team on installation, compatibility and integration.
01How many contacts has 7760056081?
Four changeover contacts in AgNi with flash gold plating, each carrying 5 A at 250 V AC.
02What coil voltage does the DRM570110 use?
110 V DC, drawing 10 mA at 1.2 W, with a coil resistance of 11000 ohm plus or minus 10 percent.
03What is the inrush rating?
10 A for 50 ms, with resistive capacity of 1250 VA AC or 120 W at 24 V DC.
04How does it differ from DRM270024?
It has four poles instead of two, 5 A instead of 10 A contacts and a 110 V DC coil instead of 24 V DC.
05What is the pack quantity and weight?
The datasheet lists 20 items per pack and a net weight of 34.3 g per relay.