Tyco Fire Products DV-5A Electric Actuated Deluge Valve DN40-DN200
Description
Overview
Tyco Fire Products DV-5A, in its electric actuated deluge form, is a diaphragm-type automatic water control valve for deluge fire protection systems. A deluge system has open nozzles or sprinklers, so the valve is the only thing holding water back until a detection system calls for it. In this version the call comes from electrical devices such as thermostats, smoke detectors or manual pull stations that energise a solenoid valve, which in turn releases the pressure that keeps the DV-5A diaphragm closed.
The valve is made in sizes 1 1/2 to 8 inch (DN40 to DN200) for vertical installation and is rated for service pressures of 20 psi to 300 psi (1,4 bar to 20,7 bar). It carries UL, C-UL and FM listings, and VdS and LPCB approvals where the EMEA assemblies with the required water column prevention drain components are chosen.
Why the diaphragm design matters
A deluge valve with a latch or clapper normally has to be opened up at its handhole cover before it can be reset. The DV-5A avoids that. Its resetting is external: you simply re-pressurise the diaphragm chamber, and the valve closes again. The double seat design also lets the valve drive the system alarms when it trims out properly. The body and diaphragm cover are epoxy coated ductile iron, coated inside and out, which the manufacturer positions for the corrosive atmospheres of industrial processing plants and outdoor installations.
Tyco Fire Products DV-5A specifications
| Item | Datasheet information |
|---|---|
| Valve type | Diaphragm style deluge valve, electric actuation |
| Sizes | 1 1/2, 2, 3, 4, 6 and 8 inch (DN40 to DN200); 165,1 mm groove also listed |
| Service pressure | 20 to 300 psi (1,4 to 20,7 bar) |
| Approvals | UL and C-UL Listed, FM Approved, VdS and LPCB for EMEA assemblies |
| Body and cover | Epoxy coated ductile iron, ASTM A536 Grade 65-45-12 |
| Diaphragm | Polyester fabric reinforced, TEFLON coated EPDM rubber per ASTM D2000 |
| Cover fasteners | Aluminum zinc coated steel |
| Orientation | Vertical |
| Diaphragm chamber restriction | 1/8 inch (3,2 mm) |
| Weight, groove x groove | 25 lb (11,3 kg) for DN40 and DN50; 60 lb (27,2 kg) DN80; 95 lb (43,1 kg) DN100; 177 lb (80,3 kg) DN150; 327 lb (148,3 kg) DN200 |
| Weight, flange x flange | 72 lb (32,7 kg) DN80; 116 lb (52,6 kg) DN100; 204 lb (92,5 kg) DN150; 365 lb (165,6 kg) DN200 |
| Take-out dimension | 16-3/4 inch (425 mm) DN80; 22-3/8 inch (569 mm) DN100; 27-7/16 inch (697 mm) DN150 |
What sits around the valve
The valve body is only part of an assembly. The electric actuation trim forms part of the laboratory approval and is needed for correct operation, so the datasheet shows it fitted as a semi-assembled package with galvanised pipe fittings, Schedule 40 nipples, brass compression fittings and Type L copper tubing. The solenoid valve, pressure switches, water pressure gauges and, where chosen, a BFV-300 butterfly valve as the system main control valve complete the riser. Pressure drop through the valve is given as a nominal loss against flow graph for each size, which the designer uses in the hydraulic calculation.
Operation in a deluge system
With the valve set, water from the supply side of the main control valve fills the diaphragm chamber and holds the diaphragm against the seats. When the detection circuit, typically a 24 volt DC circuit, energises the normally closed solenoid valve, it trips the Model MRA-1 manual reset actuator. Water then leaves the diaphragm chamber faster than the 1/8 inch restriction can replace it, the holding force falls below the trip point, and supply pressure pushes the diaphragm open so water reaches the piping and the alarm port. The MRA-1 stays open and vents the chamber, hydraulically latching the DV-5A in the tripped position until someone resets it by hand.
Because of this latching action, the releasing panel need only keep the solenoid energised for the typical ten minutes of alarm. Even if the solenoid closes later, for example during battery backup, the valve cannot re-pressurise itself and shut during a fire.
How Tyco Fire Products DV-5A differs from other DV-5A types
The DV-5A name covers several actuation styles that each have their own datasheet: wet pilot actuated, dry pilot actuated, electric actuated, remote-resetting and remote-resetting pressure-reducing versions, plus preaction versions with single or double interlock. This page covers the electric actuated deluge version, whose trim is built around the solenoid valve and MRA-1 rather than a pilot sprinkler line. If your detection is a pilot sprinkler network filled with water or air, ask for the wet or dry pilot version instead. The older DV-5 valve is a separate, earlier model, with several of its datasheets marked as discontinued in the manufacturer library.
Ordering codes published for the valve
For Americas groove x groove assemblies with galvanised electric actuation trim the manufacturer lists P/N 550010315 (1 1/2 inch), 550010320 (2 inch), 550010330 (3 inch), 550010340 (4 inch), 550010360 (6 inch) and 550010380 (8 inch). Flange x flange ANSI versions are 550020330, 550020340, 550020360 and 550020380. EMEA assemblies use the 5501 prefix, for example 550110340 for 4 inch groove x groove, and VdS and LPCB versions add a VDS suffix. A bare valve without trim, groove x groove, is 530010015 up to 530010080, and a replacement diaphragm for DN100 is 545000040. Specify size, end connection, region and whether a BFV-300 butterfly valve is to be supplied.
Using it in Oman and the GCC
Deluge systems protect hazards where fire spreads quickly: transformer bays, fuel and flammable liquid loading areas, aircraft hangars, process skids and turbine enclosures at oil, gas and power sites. One note from the installation section deserves attention in the Gulf. The DV-5A is designed for freshwater systems, and when the supply is brackish water, seawater, or contains additives such as foam, the limited warranty reduces to one year from installation and inspections must be more frequent. The valve and trim must also be flushed with freshwater and reset after every operation.
Installation, testing and care
Install the valve vertically with the trim shown in the datasheet. When system pressure exceeds 175 psi (12,1 bar), replace the standard 300 psi gauges with 600 psi gauges, P/N 923431004. If the authority asks for an alarm control valve, it must be an electrically supervised, normally open valve. During testing, check that water flows from the solenoid drain, reset the detection panel to de-energise the solenoid, and reset the manual reset actuator until the diaphragm gauge reaches about 15 psi (1,0 bar) and water stops flowing. The solenoid valve is ordered separately according to TFP2180 and the approval the project requires.
Related items you may also need: Elkhart Brass IMS-1000 1000 gpm Master Stream Nozzle | Elkhart Brass X-Stream SM-1250B 1250 gpm Master Stream Nozzle | Minimax Zonecheck Sprinkler Flow Switch Test Unit | All Tyco Fire Products products.
Documents and quotation
The manufacturer datasheet, TFP1321 dated September 2026, is attached. Seven Star LLC is an independent supplier serving Oman and the GCC. To obtain a quotation for the DV-5A, send your RFQ stating the size, end connections, region of trim (Americas, EMEA or APAC), solenoid requirement and quantity.
Datasheets & Documents
- Datasheet Tyco Fire Products DV-5A Electric Actuated Deluge Valve Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Tyco Fire Products is the fire sprinkler and fire protection valve business whose roots go back to the Providence Steam and Gas Pipe Company, founded in Providence, Rhode Island in 1850. Frederick Grinnell took control of that company in 1869 and patented an improved, more sensitive sprinkler system in 1881, an early step toward the modern automatic sprinkler. Tyco Laboratories bought Grinnell Fire Protection Systems in 1976, and the business has been part of Johnson Controls since the merger with Tyco International in 2016. Its technical data sheets are issued from Cranston, Rhode Island.
Tyco Fire Products company profile
| Founded | 1850, Providence, Rhode Island, USA, as the Providence Steam and Gas Pipe Company (the Grinnell predecessor) |
|---|---|
| Headquarters | Cranston, Rhode Island, USA (address printed on the data sheets: 1467 Elmwood Avenue) |
| Ownership | A Johnson Controls business; Johnson Controls completed its merger with Tyco International in September 2016 |
| Core technology | Automatic sprinklers with glass bulb or fusible link elements, plus alarm, deluge, preaction, butterfly and check valves for water-based fire protection |
| Typical applications | Commercial buildings, high-piled storage warehouses, industrial plants and process hazards protected by wet pipe, deluge and preaction systems |
| Standards and approvals | UL and C-UL listings, FM approvals, VdS, LPCB and CE certifications on selected products, designed for NFPA 13 and NFPA 25 practice |
Milestones
- 1850: The Providence Steam and Gas Pipe Company is founded in Providence, Rhode Island.
- 1881: Frederick Grinnell patents an improved, more sensitive automatic sprinkler system.
- 1909: The General Fire Extinguisher company, part of the Grinnell history, opens its own foundry and shops in Cranston, Rhode Island.
- 1976: Tyco Laboratories purchases Grinnell Fire Protection Systems.
- 2016: Johnson Controls completes its merger with Tyco International, and Tyco Fire Products documentation carries the Johnson Controls name.
How a Tyco Fire Products automatic sprinkler works
An automatic sprinkler is a closed nozzle held shut by a heat sensitive element, so each sprinkler reacts on its own to the heat above a fire. In a glass bulb sprinkler such as the Series TY-B and TY-FRB, a small sealed bulb contains a coloured liquid that expands as the room warms; at the rated temperature the liquid shatters the bulb, the seal drops away and water flows onto the deflector, which breaks it into a spray. Standard response models use a 5 mm bulb and quick response models a 3 mm bulb, which heats faster. The Early Suppression, Fast Response storage sprinklers use a fusible link instead: two metal halves joined by a thin layer of solder that melts at 165°F or 212°F. Choose the temperature rating from the highest expected ceiling temperature, and the K-factor from the hydraulic design.
Where Tyco Fire Products are used in Oman and the GCC
These sprinklers and valves protect shopping malls, hotels, residential towers and hospitals, tall racked warehouses in industrial zones, and fuel, power and process plants where deluge systems are needed. Poly-Stainless sprinklers suit corrosive coastal air, while epoxy coated deluge valves are made for outdoor industrial installations.
Tyco Fire Products models we list
| Family | Examples |
|---|---|
| Poly-Stainless sprinklers (Series TY-B and TY-FRB) | TY3151 |
| ESFR storage sprinklers | TY7126, TY9226 |
| Alarm and riser check valves | AV-1-300, CV-1FR |
| Deluge valves | DV-5A |
| Butterfly valves | BFV-300 |
Ordering Tyco Fire Products: what we need
Seven Star LLC is an independent supplier serving Oman and the GCC. For sprinklers, send the sprinkler identification number, temperature rating, finish, thread and quantity. For valves, send the model, size, end connections, trim or accessory needs and the approval the project requires. For spares, quote the part number printed in the data sheet or on the nameplate, and we will confirm the full order code before quoting.
Facts checked against Tyco Fire Products technical data sheets published on the Johnson Controls documentation portal, and Wikipedia entries on Grinnell and Tyco International, November 2026.
Browse Tyco Fire Products by category: Fire Fighting.
FAQ
Questions about the Tyco Fire Products DV-5A Electric Actuated Deluge
Answers from our engineering team on installation, compatibility and integration.
01How is Tyco Fire Products DV-5A electric actuated deluge valve reset?
Resetting is external: re-pressurising the diaphragm chamber closes the valve, so the handhole cover does not need to be opened to reposition a clapper or latch.
02What sizes and pressure does the DV-5A cover?
Sizes are 1 1/2 to 8 inch (DN40 to DN200), vertical installation, with a service pressure of 20 psi to 300 psi (1,4 bar to 20,7 bar).
03What triggers the DV-5A electric actuation?
A detection circuit, typically 24 volts DC, energises a separately ordered normally closed solenoid valve, which trips the MRA-1 manual reset actuator and opens the DV-5A.
04Can the DV-5A be used with seawater or foam?
It is designed for freshwater. With brackish water, seawater or foam additives the limited warranty is reduced to one year and more frequent inspection and freshwater flushing are required.
05What are the DV-5A body and diaphragm materials?
The body and cover are epoxy coated ductile iron per ASTM A536 Grade 65-45-12, and the diaphragm is polyester reinforced, TEFLON coated EPDM rubber per ASTM D2000.