- Automation & ControlView all 2,523 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Motor Soft Starters
- Safety Switches & Guard Locking
- Encoders
- HMI Displays
- Pneumatic Cylinders
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Siemens
Siemens 6EP1337-3BA00 SITOP PSU100M 24V/40A Power Supply
Description
6EP1337-3BA00: SITOP PSU100M 24 V / 40 A stabilized power supply, explained
The Siemens 6EP1337-3BA00 is a high-current single-phase modular supply that delivers 40 A at 24 V. It is the 24 V DC, 40 A version in the catalog. The SITOP PSU100M delivers 40 A at 24 V (960 W) from single-phase 120/230 V mains. It is the largest unit in this selection: 240 mm wide, 125 mm high, about 2.9 kg, with an inrush limit of 125 A and a heat loss of about 131 W.
The article number is simply the catalog identifier for this rating of the SITOP PSU100M group; it does not describe the build in a way that can be decoded digit by digit without the manufacturer’s tables, so always quote the full number 6EP1337-3BA00 when ordering. Seven Star LLC supplies the 6EP1337-3BA00 in Oman and the GCC as an independent supplier in Muscat.
Technical specifications of the 6EP1337-3BA00
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Siemens / 6EP1337-3BA00 |
| Product line | SITOP PSU100M (SITOP modular line) |
| Rated output | 24 V DC, 40 A |
| Input | 120/230 V AC, set with a wire jumper on the unit (ranges 85 – 132 V / 176 – 264 V) |
| Input current | 15 A at 120 V; 8 A at 230 V |
| Switch-on current limit (+25 °C) | max. 125 A |
| Mains buffering at rated load | min. 20 ms; at Vin = 230 V |
| Output voltage adjustment | 24 – 28.8 V via potentiometer |
| Output tolerance (static) | ±3 % |
| Residual ripple (peak-peak, max.) | 100 mV |
| Efficiency at rated load, approx. | 88 % |
| Power loss at rated load, approx. | 131 W |
| Start-up delay, max. | 0.1 s |
| Short-circuit / overload response | Selectable: constant-current characteristic (approx. 46 A) or latching shutdown |
| Parallel operation for more power | Yes; switchable |
| Signalling output | Via the optional SITOP modular signalling module 6EP1961-3BA10 |
| Protection class | Class I |
| Approvals listed | cULus listed (UL 508, CSA C22.2 No. 107.1) |
| Hazardous-area listings | IECEx / ATEX category 3G (Ex nA) and cCSAus Class I Div. 2 listings appear in the catalog for this series; confirm the marking and temperature class on the exact unit |
| Ambient temperature (operation) | 0 – 70 °C, natural convection |
| Derating note (catalog) | +60 – +70 °C: Derating 2.5%/K |
| Humidity class | Climate class 3K3, no condensation |
| EMC | Emissions EN 55022 Class B; noise immunity EN 61000-6-2 |
| Degree of protection | IP20 |
| Dimensions (W × H × D) | 240 × 125 × 125 mm |
| Weight, approx. | 2.9 kg |
| Mounting | Snap-on to DIN rail EN 60715 35 × 7.5/15; side-by-side mounting permitted |
| MTBF at 40 °C | 540 249 h (catalog value) |
Values are taken from the manufacturer’s SITOP catalog (KT 10.1, 2016) and apply at rated input voltage and +25 °C unless stated otherwise; check the current data sheet of the exact unit before design freeze.
How the 6EP1337-3BA00 regulates and protects its 24 V output
The 6EP1337-3BA00 is a switch-mode converter for single-phase 120/230 V mains, with the range set by a wire jumper. It regulates 24 V with an adjustable output (24 – 28.8 V) and supplies a 125 A switch-on surge limit that the upstream breaker must be able to carry. Power Boost provides up to 120 A for 25 ms.
Short-circuit behaviour can be set to constant current (approx. 46 A) or latching shutdown, and parallel operation can be switched for symmetrical load sharing. Signalling is provided by the optional signalling module 6EP1961-3BA10.
Where the 6EP1337-3BA00 fits in the control system
In a typical cabinet the 6EP1337-3BA00 sits right behind the incoming breaker and feeds a 24 V distribution rail. In the catalog this is the only SITOP PSU100M version, so there is no smaller or larger sibling to fall back on within the same group; for other ratings look at the SITOP smart and modular ranges.
For this series the catalog lists the SITOP modular signalling module 6EP1961-3BA10 (output voltage OK, readiness for operation OK, remote on/off), the PSE201U buffer module 6EP1961-3BA01, the PSE202U redundancy modules (6EP1961-3BA21, 6EP1962-2BA00, 6EP1964-2BA00) and the PSE200U selectivity modules in 3 A and 10 A versions.
As an independent supplier, Seven Star LLC can help you match the supply to the rest of the bill of materials, for example by checking that the redundancy or buffer module suits the output current, but the final electrical design remains with your engineering team.
Selection and ordering checklist for the 6EP1337-3BA00
- Load current: add the continuous demand of all 24 V consumers and compare it with the 40 A rating of the 6EP1337-3BA00, leaving margin for inrush and future additions.
- Mains: confirm that the site supply matches the input data (120/230 V AC, set with a wire jumper on the unit (ranges 85 – 132 V / 176 – 264 V)) and check the input current figures given in the specification table.
- Cabinet temperature: the operating range is 0 – 70 °C and derating applies at the upper end; compare it with the worst-case temperature inside the enclosure.
- Space: allow 240 mm width on the rail plus 125 mm of height and 125 mm of depth; vertical clearance for convection is required.
- Protection: for 1-phase operation the catalog recommends a 20 A characteristic C breaker; remember the 125 A switch-on surge.
- Signalling: decide whether to add the optional signalling module 6EP1961-3BA10 for the status contacts.
- Add-ons: decide early whether a redundancy, buffer or selectivity module is needed; the catalog lists compatible modules for the series.
- Select it for heavy single-phase loads where three-phase is not available; use a 20 A characteristic C breaker as recommended for 1-phase operation, and check that the supply can deliver 15 A at 120 V or 8 A at 230 V.
Installation, commissioning and maintenance
Mount the 6EP1337-3BA00 on a 35 mm DIN rail; it is 240 mm wide, so plan the rail length and the cable routing for 40 A output cables (the output terminals take up to 10 mm²). Set the 120/230 V wire jumper before energising.
Choose constant current or latching shutdown and decide whether to fit the signalling module 6EP1961-3BA10. Check cabinet temperature under full load, since the unit dissipates about 131 W.
Make sure the cabinet can dissipate about 131 W; set the 120/230 V wire jumper correctly before energising.
- Inspect terminals for tightness and discolouration at each shutdown.
- Clean dust from the vents with dry compressed air; do not block the convection path.
- Compare the output voltage with the value recorded at commissioning.
- Keep one spare of the same article number for critical cabinets, since lead times for individual SITOP models can vary.
Typical applications in Oman and the GCC
In Oman and the GCC, the 6EP1337-3BA00 fits heavy-load control cabinets, test benches and systems where only a single-phase supply is available but 40 A at 24 V is required. At 131 W of heat loss, cabinet ventilation or air conditioning must be considered in desert climates.
Typical uses are heavy-load control cabinets and test benches that require 40 A at 24 V from a single-phase feeder.
SITOP PSU100M group at a glance
The table lists the SITOP PSU100M versions found in the catalog so you can compare ratings and size before selecting the 6EP1337-3BA00.
| Article number | Output | Width | Weight | Efficiency |
|---|---|---|---|---|
| 6EP1337-3BA00 | 24 V / 40 A | 240 mm | 2.9 kg | 88 % |
Information to send with an RFQ for the 6EP1337-3BA00
- Exact article number (6EP1337-3BA00) and quantity, including whether you need identical replacement or an equivalent.
- Supply system at site: voltage, frequency and number of phases, plus whether a DC feed is possible.
- Output requirement: voltage, continuous current, peak or inrush loads and the number of parallel units if redundancy is planned.
- Ambient conditions inside the cabinet: maximum temperature, dust, humidity and any hazardous-area classification.
- Required accessories, for example redundancy, buffer or selectivity modules, terminals or labeling plates.
- Delivery location (Muscat or elsewhere in Oman or the GCC) and required delivery time.
- Any document requirement such as a datasheet or manual in English.
Documents and quotation
Send us the part number 6EP1337-3BA00 and we will confirm which manufacturer documents are available for it. The figures on this page come from the manufacturer’s SITOP catalog and should be checked against the data sheet of the exact unit before design freeze.
Seven Star LLC is an independent supplier based in Muscat and is not affiliated with the manufacturer. To request a quotation for the 6EP1337-3BA00, send the information listed above through the request-for-quotation form or by email; we will reply with availability and lead time.
Reviews (0)
How would you rate this product? Cancel reply
About brand
Siemens is the German technology group whose industrial products include SIMATIC controllers and HMIs, SINAMICS drives, SIRIUS and SENTRON switching and protection devices, SIPROTEC protection relays, SITRANS process instruments, SCALANCE networks and process analysers. It was founded in Berlin on 12 October 1847 by Werner von Siemens and the precision mechanic Johann Georg Halske as Telegraphen-Bauanstalt von Siemens & Halske, to build Siemens's newly designed pointer telegraph. Siemens AG is headquartered in Munich and listed on the Frankfurt Stock Exchange; its energy business was spun off as Siemens Energy in 2020.
Siemens company profile
| Founded | 12 October 1847, Berlin, Germany, as Telegraphen-Bauanstalt von Siemens & Halske, with 10 employees |
|---|---|
| Founders | Werner von Siemens (1816–1892) and Johann Georg Halske (1814–1890) |
| First product | The pointer telegraph designed by Werner von Siemens |
| Headquarters | Munich, Germany (Siemens AG) |
| Ownership | Public company listed in Frankfurt; Siemens Energy (2020) and Siemens Healthineers are separately listed companies |
| Businesses acquired that appear in our range | Moore Products (bought in 2000; APACS and QUADLOG control systems), Applied Automation (Maxum process gas chromatographs); small industrial gas turbines such as the SGT-300 came with Alstom's industrial turbine business in 2003 |
| Product families | SIMATIC S7 PLCs, ET 200 distributed I/O and HMI panels, TIA Portal software, SINAMICS drives, SIMOTICS motors, SIRIUS and SENTRON low voltage devices, SIVACON switchboards, SIPROTEC relays, SITRANS instruments, SCALANCE network components, building technology valves and sensors |
Milestones
- 1847: Siemens & Halske starts work in Berlin with 10 employees.
- 1848: The company wins the contract for Europe's first long-distance telegraph line, Berlin to Frankfurt am Main.
- 1856: 330 employees, two-thirds of them working on telegraph networks in Russia.
- 1866: Werner von Siemens describes the dynamo-electric principle, the basis of the electric generator.
- 1958 onwards: The SIMATIC name is used for Siemens industrial automation; S7 PLCs follow in the 1990s and S7-1500 in 2012.
- 2020: Siemens Energy is spun off and listed separately.
Choosing Siemens automation products
A Siemens order number (MLFB) identifies the exact product: 6ES7 is SIMATIC automation, 6AV is HMI, 6GK is industrial communication, 6SL is SINAMICS drives, 3R is SIRIUS control and 5SY is SENTRON miniature circuit breakers. For PLCs, S7-1200 is the compact controller for small machines, S7-1500 is the current mid-to-high range controller, and S7-300 and S7-400 are older platforms still running in many plants; S7-300 is being phased out, so spares and migration to S7-1500 are common requests. When replacing a CPU or module, the full order number including the version digits matters, because firmware and hardware versions affect compatibility with the existing project.
Where Siemens products are used
In Oman and the GCC, Siemens automation runs in oil and gas, power and desalination plants, water networks, cement and process industries. Maxum gas chromatographs analyse gas composition in gas plants and refineries, SIPROTEC relays protect substations, SGT-300 turbines drive generators and compressors, and Siemens building valves are used in HVAC systems.
Siemens products we list
| Family | Examples |
|---|---|
| SIMATIC controllers and I/O | S7-1500, CPU 1515-2 PN, S7-1200, CPU 1214C, S7-300, S7-400H CPU 412-5H, ET 200SP, IM 153-2 |
| HMI and networking | KTP700 Basic, TP700 Comfort, TP1200 Comfort, SCALANCE XC208, SCALANCE WAM766, PROFIBUS OLM |
| Drives, motors and power distribution | SINAMICS G120C, SINAMICS G120X, 1LA7 motor, SIVACON S8, SIPROTEC 7SJ85, 5SY4510-7 MCB |
| Process instruments | SITRANS P320, MAG 5100W, SITRANS TH320, SITRANS TS500, SITRANS TR200 |
| Maxum II analyser spares | FID 302A detector, FPD II assembly, filament detector, Model 50 valve, SYSCON kit, air bath heater |
| APACS and QUADLOG spares | QLCCM24AAN, QLSAMBAN, QLSDM024DCCBN, 39SAMCAN, 16137-151 M-BUS cable |
| Building technology | VPI46 PICV, VPF44, QFM1660 sensor |
Ordering Siemens products: what we need
Send the full order number from the label (for example 6ES7214-1AG40-0XB0) and, for PLC and HMI parts, the hardware and firmware version (FS and V numbers). For Maxum II and APACS spares, send the Siemens part number such as 2021651-002. For drives, add the motor power and supply voltage.
Frequently requested Siemens models: Siemens IM 155-6 PN ST ET 200SP Interface Module 6ES7155-6AU02-0BN0, Siemens SGT-300 Industrial Gas Turbine.
Facts checked against Siemens's published history timeline, October 2026.
FAQ
Questions about the Siemens 6EP1337-3BA00 SITOP PSU100M 24V/40A Power
Answers from our engineering team on installation, compatibility and integration.
01How is the 6EP1337-3BA00 set to 120 V or 230 V?
The catalog states that the input range is set with a wire jumper on the unit. Set it before energising. The unit has a 125 A switch-on surge limit, so size the upstream breaker accordingly.
02How efficient is the 6EP1337-3BA00 and how much heat does it release?
The catalog lists an efficiency of about 88 % at rated load, which corresponds to a power loss of 131 W. Include this loss in the cabinet heat balance, especially in hot desert climates.
03What input voltage does the 6EP1337-3BA00 accept?
According to the catalog it accepts 120/230 V AC, set with a wire jumper on the unit (ranges 85 – 132 V / 176 – 264 V). Check this against the site supply and the selector or jumper setting where the series has one, since a mismatch is the most common cause of a dead unit at commissioning.
04How much input current does the 6EP1337-3BA00 draw?
The catalog gives 15 A at the lower rated voltage and 8 A at the higher one, with a switch-on current limit of up to 125 A. Coordinate the upstream breaker with these values, especially when several units start together.
05How does the 6EP1337-3BA00 behave on a short circuit or overload?
The response is: selectable: constant-current characteristic (approx. 46 A) or latching shutdown. Make sure downstream protective devices can operate with this current, and confirm that the load list does not exceed the 40 A rating for long periods.


















Reviews