Samson 3214 Balanced Globe Valve with Fail-safe Actuator
Description
SAMSON Type 3214 pressure-balanced globe valve with fail-safe actuator
The SAMSON Type 3214 is a single-seated globe valve balanced by a corrosion-resistant metal bellows. Combined with an electric actuator that has a safety function, it forms a control valve for heating systems that must shut down on excess temperature or pressure. It covers DN 15 to DN 250, PN 16 to PN 40 and medium temperatures up to 220 °C, for water and steam. Seven Star LLC supplies SAMSON valves in Oman and the GCC as an independent supplier in Muscat.
The datasheet T 5869 describes two valve types together. The Type 3213 is the unbalanced version and the Type 3214 is the balanced one, so the 3214 is the choice when large differential pressures act on the plug. The control valves are tested by the German technical surveillance association TUV according to DIN EN 14597 and are defined as shut-off and control devices; the register number is available from the manufacturer on request.
Decoding the 3213 and 3214 type designations
The designation has two parts separated by a slash: valve first, actuator second.
| Designation | Meaning | Size and pressure |
|---|---|---|
| 3213/5827-A | Unbalanced valve with Type 5827 electric actuator | DN 15 to 25 at PN 25, DN 32 to 50 at PN 16 |
| 3213/5725-3 | Unbalanced valve with TROVIS 5725-3 actuator with process controller (domestic hot water) | DN 15 to 25 at PN 25, DN 32 to 50 at PN 16 |
| 3213/5725-8 | Unbalanced valve with TROVIS 5725-8 actuator (heating and cooling, two PID modules) | DN 15 to 25 at PN 25, DN 32 to 50 at PN 16 |
| 3214/5827-A | Balanced valve with Type 5827 electric actuator | DN 15 to 50, PN 16 to 40 |
| 3214/3374 | Balanced valve with Type 3374 electric actuator | DN 65 to 250, PN 16 to 40 |
| 3214/5725-3 | Balanced valve with TROVIS 5725-3 | DN 15 to 50, PN 16 to 40 |
| 3214/5725-8 | Balanced valve with TROVIS 5725-8 | DN 15 to 50, PN 16 to 40 |
Type 3214 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | SAMSON / Type 3214 globe valve with electric fail-safe actuator (datasheet T 5869 EN) |
| Nominal size | DN 15 to 250 |
| Pressure rating | PN 16 to 40 |
| Maximum temperature | Standard 150 °C; ordering option for a version up to 220 °C; upright installation |
| Medium | Water and steam |
| Pressure balancing | Metal bellows (1.4571); optional flow divider ST 1 from DN 65 |
| Rated travel | 6 mm (DN 15 to 25), 12 mm (DN 32 to 50), 15 mm (DN 65 to 100), 30 mm (DN 125 to 250) |
| Rangeability | 50:1 (DN 15 to 50), 40:1 (DN 65 to 100), 30:1 (larger sizes) |
| Leakage class (DIN EN 60534-4) | Class I; 0.05 % of KVS in the smaller sizes and 0.01 % of KVS in the larger sizes |
| Valve body | PN 16: EN-GJL-250; PN 25: EN-GJS-400-18-LT or 1.0619; PN 40: 1.0619 |
| Seat and plug | CrNi steel (DN 15 to 100); CrNiMo steel with EPDM soft seal (DN 125 to 250) |
| Plug stem / bellows housing | 1.4301 / 1.0425 |
| Packing | Guide nipple with EPDM seal (DN 15 to 50); PTFE with carbon V-ring packing (DN 65 to 250) |
| Sizing terms | FL = 0.95, xT = 0.75 |
How the balanced Type 3214 and its safety function work
Medium flows through the valve in the direction of the arrow, and the area between seat and plug is set by the position of the plug stem. In the Type 3214, the pressure upstream of the plug is transferred through a hole in the plug stem to the outside of the balancing bellows, while the downstream pressure acts on the inside. The forces created by the differential pressure on the plug cancel out, so a small actuator can position the plug against a large pressure drop.
The safety function sits in the actuator. If the supply voltage fails, or if the temperature or pressure limiting equipment interrupts the control signal, a safety mechanism releases compression springs and the valve closes. Because the valve can act as a shut-off device inside safety interlock circuits, the datasheet requires a strainer (for example Type 2 NI) upstream of the valve in those circuits, so debris cannot keep the plug off the seat.
KVS values and differential pressure for the Type 3214
| Size | KVS | Rated travel (mm) | Max. differential pressure (bar) |
|---|---|---|---|
| DN 15 | 4 | 6 | 25 |
| DN 20 | 6.3 | 6 | 25 |
| DN 25 | 8 | 6 | 25 |
| DN 32 | 16 | 12 | 25 |
| DN 40 | 20 | 12 | 25 |
| DN 50 | 32 | 12 | 25 |
| DN 65 | 50 | 15 | 20 |
| DN 80 | 80 | 15 | 20 |
| DN 100 | 125 | 15 | 16 |
| DN 125 | 200 | 30 | 16 |
| DN 150 | 320 | 30 | 12 |
| DN 200 | 500 | 30 | 10 |
| DN 250 | 600 | 30 | 10 |
From DN 65, the optional flow divider ST 1 reduces KVS to 38, 60, 95, 150, 210, 315 and 375 respectively. The unbalanced Type 3213 offers KVS 4 to 32 up to DN 50 with a much lower permitted differential pressure (10 bar for DN 15 to 25, 2.9 bar for DN 32 and 40, 1.6 bar for DN 50), which shows why the balanced 3214 is preferred for hot-water mains with high pressure drops.
Actuators that match the Type 3214
- Type 5827-A1 / -A2: electric actuators for DN 15 to 25 (A1) and DN 32 to 50 (A2).
- Type 3374-21: fail-safe electric actuator for DN 65 to 100.
- Type 3374-27: fail-safe electric actuator for DN 125 to 250.
- TROVIS 5725-310, -313, -320, -323: actuators with process controller for domestic hot water heating; the -313 and -323 are half-transit-time versions.
- TROVIS 5725-810 and -820: actuators with two PID control modules for heating and cooling applications.
Electric control is by three-step signals or, for positioner versions, 0/4 to 20 mA or 0/2 to 10 V. The standard Type 3214 and 3213 valves without the DIN EN 14597 test, paired with electric or pneumatic actuators, are covered by a different SAMSON datasheet (T 5868).
Selection and ordering checklist for the 3214
Sizing follows DIN EN 60534: calculate the required KVS, select DN and KVS from the table, check the permitted differential pressure, then check temperature and valve version, and finally choose the actuator. The ordering text asks for:
- Type designation, for example 3214/3374 or 3214/5827-A, and whether the valve is for steam.
- Version up to 220 °C: yes or no.
- DN, PN, KVS coefficient, maximum differential pressure and maximum temperature.
- Body material.
- Electric actuator details: control signal, supply voltage and electrical accessories.
Installation and servicing of the 3214 fail-safe valve
Install the valve with the actuator in the upright position; other mounting positions only on request. Where the medium temperature is between -10 and +5 °C, or in networks with a constant temperature above 135 °C using certain actuators, an intermediate insulating piece (1990-1712) is specified. Fit a strainer upstream, keep the bellows housing free of insulation that traps heat against the actuator, and test the safety action after commissioning by interrupting the signal.
Keep the mounting and operating instructions EB 5868/5869 with the plant documents. Typical spares are packing, guide-nipple seals and the plug assembly; give the serial number and valve size when requesting parts.
Typical uses of the 3214 in Oman and the GCC
District-heating style hot-water networks are less common in the Gulf than in Europe, but the 3214 still fits hotel and hospital heating, process heating loops in food and chemical plants, steam-to-water heat exchangers and sterilisation or humidification systems fed by steam. In desalination and power plants, it can serve auxiliary heating loops where an independent over-temperature shutdown is required. Dust and high ambient temperature make it important to check the actuator ambient limits and to protect actuators from direct sun.
Information for your 3214 RFQ
- Full designation (valve and actuator) and DN, PN.
- Medium (water or steam), temperature and pressure, flow and differential pressure.
- Safety function required: temperature or pressure limiter, fail-safe direction.
- Supply voltage and control signal.
- Existing nameplate data if replacing a valve.
- Quantity and delivery location.
Documents and quotation
The SAMSON datasheet T 5869 EN covering the Types 3213 and 3214 is attached on this page.
Send the designation, DN, PN and duty details and we will confirm what can be supplied in Oman and the GCC.
Other Models in the Samson Hvac Valves Range
Seven Star LLC supplies models from the Samson Hvac Valves range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| SAMSON Type 3222 HVAC Globe Valve DN 15-50 PN 25 | Control Valves | View details |
| Samson 3214 Balanced Globe Valve with Fail-safe Actuator | Control Valves | You are viewing this model |
Datasheets & Documents
- Datasheet Samson 3214 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
SAMSON is a German manufacturer of control valves, actuators, positioners and self-operated regulators. Hermann Sandvoss founded the company in Düsseldorf on 1 April 1907, and its first important product was a thermostatic valve that controlled temperature without external power. After moves to Mannheim, SAMSON settled in Frankfurt am Main in 1916, where SAMSON AG is still headquartered.
Seven Star LLC supplies Samson control valves, pneumatic actuators and positioners to process plants in Oman, including the types listed on this page and their replacement units.
Samson company profile
| Founded | 1 April 1907, Düsseldorf, by Hermann Sandvoss, as VULCAN Technische Apparate Baugesellschaft; products sold under the SAMSON name |
|---|---|
| Headquarters | Frankfurt am Main, Germany, since 1916 |
| Legal form | SAMSON AG |
| First product | A self-operated thermostatic valve |
| Group brands | SAMSON together with PFEIFFER, LEUSCH, VETEC and AIR TORQUE |
| Product families | Globe valves such as Type 3241, rotary and butterfly valves, 3271 and 3277 pneumatic actuators, 3730 and 3731 positioners, self-operated pressure and temperature regulators |
Milestones
- 1907: Hermann Sandvoss founds the company in Düsseldorf.
- 1909: It is re-established as SAMSON Apparatebau GmbH.
- 1916: After a period in Mannheim, the company moves to Frankfurt am Main.
- 1975: The name becomes SAMSON Mess- und Regeltechnik.
Samson valve, actuator and positioner types
Samson builds a control valve from modules. The Type 3241 globe valve is the general-service body of Series 240, and the Type 3251 is the Series 250 body for higher pressure ratings. Either one is combined with a Type 3271 pneumatic diaphragm actuator or a Type 3277, whose yoke allows the positioner to be attached directly with a concealed travel linkage.
Among the positioners listed are the Type 3725 and the Type 3730 family: the 3730-1 as the basic electropneumatic version, sold in its current generation as TROVIS 3730-1, and the 3730-3 with HART communication and valve diagnostics. Samson also makes PROFIBUS PA and FOUNDATION fieldbus variants in the same family, plus self-operated pressure and temperature regulators.
Where Samson valves are used
Samson control valves throttle steam, gas and liquids in chemical and petrochemical units, refineries, gas processing, power stations, water and desalination plants, and food production. Many reach site as part of a skid or package, so the plant instrument team often meets them first when a positioner or actuator needs replacing. We supply these items to end users and contractors throughout the GCC.
Samson products we list
Ordering Samson parts: what we need
Every Samson device has a nameplate with the type, a configuration ID (Var-ID) and a serial number. A photo of that plate is the surest route to an exact match. Without it, please send:
- Valve: type, DN or NPS, pressure rating, body and trim material, Kvs or Cv, plug and seat style, packing and bonnet type
- Actuator: type, effective area in cm², bench range, fail action and travel
- Positioner: full type code including Ex protection, communication and options such as limit switches or position transmitter
We check the code against Samson documentation and provide the manufacturer's data sheet on request.
Facts checked against SAMSON's corporate chronicle and press material, October 2026.
Browse Samson products by category: Control Valves, Valve Positioner, Valve Actuator.
FAQ
Questions about the Samson 3214 Balanced Globe Valve with Fail-safe
Answers from our engineering team on installation, compatibility and integration.
01What is the difference between the Type 3213 and 3214?
Both are single-seated globe valves from datasheet T 5869. The 3213 has no pressure balancing, while the 3214 is balanced by a metal bellows, so differential pressure forces on the plug are cancelled and larger pressure drops can be handled.
02What does the fail-safe function do?
When the supply voltage fails or the limiting equipment interrupts the control signal, springs in the actuator close the valve. This lets the valve act as a shut-off device in safety interlock circuits against excess temperature or pressure.
03Which standard are these control valves tested to?
The datasheet states that the actuators with fail-safe action are tested by TUV according to DIN EN 14597 together with the listed valves. The register number is available from the manufacturer on request.
04Which actuator is used above DN 50?
For the Type 3214 the datasheet pairs the Type 3374-21 with DN 65 to 100 and the Type 3374-27 with DN 125 to 250. DN 15 to 50 use the Type 5827-A or TROVIS 5725 actuators.
05Is a strainer needed?
Yes in safety interlock circuits. The datasheet states that a strainer, for example Type 2 NI, must be installed upstream of the valve in the flow direction.