MTL MTL5522 Loop-Powered Solenoid Driver, IIB
Description
Role of the MTL5522 in a hazardous-area control loop
When a plant control system has to energise a solenoid valve, a beacon or an alarm horn in a gas-classified area, the signal has to pass through an intrinsically safe interface. The MTL MTL5522 does exactly that in a single 16 mm wide DIN-rail module, drawing its energy from a 20 to 35 V dc supply and delivering a limited output to a certified low-power load. This particular type is rated for group IIB gases, which allows a higher output than the IIC sibling.
The control switch that decides whether the field device is on or off is a plain contact in the safe area. Because input and output are galvanically isolated, the contact can sit on the positive or the negative side of the supply, which gives wiring freedom in marshalling cabinets.
MTL5522 features taken from the datasheet
- Single channel, loop-powered solenoid or alarm driver for IIB
- Output voltage of at least 22.2 V open circuit with a 158 ohm maximum equivalent source
- Output current limited to at least 70 mA, with 10.7 V available at that current
- Safety description Uo = 25 V, Io = 166 mA, Po = 1.04 W, Um = 253 V rms or dc
- Yellow LED lit while the output is active
- Output ripple below 0.5 percent of maximum output, peak to peak
- Output reaches within 10 percent of its final value inside 100 ms
- Assessed under the certified Functional Safety Management programme (IEC 61508:2010)
MTL5522 technical specification
| Model | MTL5522 |
|---|---|
| Function | solenoid / alarm driver, loop powered |
| Channels | one |
| Load location | Zone 0, IIB, T4-T6; Division 1, Group C |
| Input voltage | 20 to 35 V dc |
| Minimum output voltage | 22.2 V open circuit; 10.7 V at 70 mA |
| Equivalent output source | 158 ohm maximum |
| Current limit | 70 mA minimum |
| Safety description | Uo 25 V, Io 166 mA, Po 1.04 W, Um 253 V |
| Supply current | 125 mA typical at 24 V |
| Power dissipation | 1.4 W at 24 V |
| Response | within 10 percent of final value in 100 ms |
| Ripple | less than 0.5 percent of maximum output, peak to peak |
| Operating temperature | -20 to +60 degrees C |
| Mounting | 35 mm DIN rail |
| Weight | about 150 g (MTL5500 range) |
How MTL5522 differs from MTL5521 and MTL5523
The MTL5521 is the IIC version of the loop-powered driver. Its output sits at 22.2 V open circuit with a 180 ohm equivalent source, 13.6 V at 48 mA, and its safety description is 25 V, 147 mA, 0.92 W, with 90 mA supply current. The MTL5522 lowers the source resistance to 158 ohm, raises the short-circuit allowance to 166 mA and 1.04 W, and delivers 10.7 V at 70 mA, which is why it is approved only for IIB. If you must choose between them, let the gas group of the hazardous area decide: IIC means MTL5521, IIB allows the stronger MTL5522.
The MTL5523 is a different concept again, with line fault detection added to the solenoid driver, so it is chosen when the control system must know the field wiring is intact.
Typical solenoid and alarm duties in Oman and GCC plants
Emergency shutdown valves on process skids, fire-water deluge solenoids, tank high-level alarms and flashing beacons at loading bays are standard examples. In IIB areas such as many hydrocarbon storage and fuel handling sites, the MTL5522 supplies the extra drive current that a stronger solenoid coil or a brighter lamp may need.
Utilities and power stations, desalination units with chemical dosing in classified spaces, and manufacturing plants with solvent handling all use similar duty.
Selection and compatibility for MTL5522
Check three things. First, confirm the load is certified for IIB or better and that its input parameters allow 25 V, 166 mA and 1.04 W. Second, make sure the solenoid operates at 10.7 V and 70 mA, since the datasheet worst case output is lower than the open-circuit 22.2 V. Third, decide whether the safety function is de-energise-to-trip, in which case the SIL3 capability applies, or energise-to-act, which carries a SIL1 capability.
The datasheet lists no MTL4500 backplane counterpart for this type, so the MTL5522 is available as a DIN-rail unit only.
Installing and proving the MTL5522
Clip the module on 35 mm rail, observe that hazardous-area wiring uses the plug-in terminals marked in blue, and supply the 20 to 35 V dc power through the plug terminals 13 and 14 or the optional bus. Test with the load disconnected and measure the open-circuit voltage; it should be close to 22.2 V or above. Then connect the load and confirm that the yellow LED lights when the control contact closes.
The EMC standards quoted for the range are EN 61326 and NE21, and a power interruption of 20 ms needs a suitable power supply to ride through.
Maintaining MTL5522 and keeping spares
Galvanic isolators need little care. Periodically verify the output with a meter, record LED behaviour and retighten terminals. Keep a spare for each driver type used on the site. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.
Cabinet heat and supply sizing with MTL5522
Plan the cabinet using the numbers in the table. Each MTL5522 dissipates 1.4 W at 24 V and draws about 125 mA, so ten modules on one rail dissipate 14 W and need roughly 1.25 A from the 24 V supply when all outputs are active. A solenoid that needs more than 70 mA cannot be driven reliably, because the current limit is a minimum of 70 mA at a terminal voltage of 10.7 V, and the voltage falls as current rises. Check the coil resistance as well: a 24 V coil of 350 ohm would draw about 69 mA at 24 V, but at the output the available voltage is lower, so confirm the pull-in voltage of the valve against the 10.7 V figure.
The ripple specification of less than 0.5 percent of maximum output, peak to peak, means the output is smooth enough for LED beacons and quiet relays. A response within 100 ms to reach 10 percent of final value is more than adequate for solenoid control.
Documents and quotation
The MTL4500 and MTL5500 range dataset describes the MTL5522 and its companions. To order, send an RFQ giving the part number MTL5522, quantity and your delivery location in Oman or the GCC.
Other Models in the MTL5500 Drivers Range
Seven Star LLC supplies models from the MTL5500 Drivers range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| MTL MTL5549 Two-Channel HART Isolating Driver | Isolator & Barrier | View details |
| MTL MTL5522 Loop-Powered Solenoid Driver, IIB | Isolator & Barrier | You are viewing this model |
Datasheets & Documents
- Datasheet MTL MTL5522 Loop-Powered Solenoid Driver, IIB Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
MTL is a British maker of intrinsic safety interfaces, surge protection and hazardous-area equipment, founded in 1971 in Luton as Measurement Technology Ltd, a spin-off from Kent Instrumentation. In 2008 Cooper Industries bought MTL Instruments for £144 million and placed it in its Crouse-Hinds division; Eaton acquired Cooper in 2012. MTL is now part of Eaton's Crouse-Hinds business, alongside the MEDC signalling range.
Seven Star LLC lists MTL isolators, a fieldbus barrier and the configuration tools for them, and supplies MTL (Eaton) barriers and spare modules to sites in Oman as an independent supplier.
MTL (Eaton) company profile
| Founded | 1971, Luton, England, as Measurement Technology Ltd |
|---|---|
| Origin | Spin-off from Kent Instrumentation |
| Headquarters | Luton, England |
| Ownership | Eaton (Crouse-Hinds), via Cooper Industries from 2008 |
| Product families | MTL5500 and MTL4500 isolators, MTL7700 zener barriers, 9300 fieldbus barriers, surge protection devices, process junction boxes, PCS45 configuration software; MEDC beacons, sounders and call points |
Milestones
- 1971: Measurement Technology Ltd is founded in Luton.
- 2007: MTL acquires ELPRO Technologies, RTK Instruments and Ocean Technical Systems.
- 2008: Cooper Industries acquires MTL Instruments for £144 million.
- 2012: Eaton acquires Cooper Industries.
MTL product families listed here
Most of the listed items are DIN-rail galvanic isolators. The MTL5541 repeater power supply and the MTL5576-THC temperature converter belong to the MTL5500 range, and the MTL 5043 repeater power supply comes from the earlier MTL5000 range that many plants still run. The MTL 9370-FB2 is a fieldbus barrier for intrinsically safe FOUNDATION fieldbus spurs. PCS45 software with the PCL45USB link is the configurator for MTL converter modules. For the listed part CPM08-BN, please send a label photo so the number can be matched to the manufacturer's records. Newer labels show Eaton MTL, older ones Measurement Technology Ltd, and the module numbers are the same. The MTL 9608 is a fieldbus junction box with eight spur outlets plus a trunk-in connection, listed under the Crouse-Hinds series part number FCS-9608.
Where MTL barriers and isolators are used
These interfaces sit in marshalling cabinets wherever instruments are located in Zone 0, 1 or 2 areas: gas plants, refineries, offshore platforms, tank farms and chemical units across the GCC. They power 2-wire transmitters, pass HART, convert thermocouple signals and drive solenoids or alarms while limiting energy to the field circuit.
MTL (Eaton) products we list
Ordering MTL modules: what we need
Send the full module number including every suffix, for example MTL5576-THC and not just MTL5576, and the quantity. Tell us if the module mounts on DIN rail or on a backplane, because MTL5500 and MTL4500 parts are not interchangeable. For a fieldbus barrier give the number of spurs and the enclosure reference. A photo of the side label, which shows the certificate numbers, helps when the certificate for your project file must match.
Facts checked against the Eaton MTL company history and Drives & Controls coverage of the 2008 Cooper offer, October 2026.
Browse MTL (Eaton) products by category: Isolator & Barrier, Automation Software.
FAQ
Questions about the MTL MTL5522 Loop-Powered Solenoid Driver, IIB
Answers from our engineering team on installation, compatibility and integration.
01What output can the MTL5522 deliver to a solenoid?
The datasheet gives a minimum output voltage of 10.7 V at 70 mA, a maximum of 24 V from a 158 ohm source, and a current limit of at least 70 mA.
02Which hazardous areas can the MTL5522 load sit in?
Zone 0, IIB, T4 to T6, and Division 1 Group C, provided the load device is suitably certified. For IIC loads the MTL5521 is the sibling listed.
03What SIL level does the MTL5522 reach?
It is SIL3 capable as a single device (HFT=0) when the function is to de-energise the output, and SIL1 capable for a single device when the function is to energise the output.
04Does the MTL5522 need a separate power supply?
It is loop-powered from a 20 to 35 V dc input and draws about 125 mA typical at 24 V, with 1.4 W dissipated inside the unit.
05Can the control switch be placed on either side of the supply?
Yes. The datasheet notes that input to output isolation allows the control switch to be connected into either side of the 24 V dc supply circuit.