Magnetrol B40-4C40 High Pressure External Cage Level Switch
Description
Overview
Magnetrol B40-4C40 is the 316 stainless steel, 1-1/2 inch socket weld chamber version of the B40 external cage liquid level switch. The B40 line is the manufacturer’s answer to high pressure, high temperature separators, flash drums and receivers, where an ordinary float chamber would be out of its depth. Inside the pressure-retaining cage a pivoted float carries a magnetic sleeve toward or away from a switch magnet, so the electrical switch sits outside the process boundary. Seven Star LLC is an independent supplier serving Oman and the GCC.
Pressure and temperature performance of Magnetrol B40-4C40
The chamber code 4C40 is rated at 3700 psi (255 bar) at 100 F (38 C). The rating then eases to 3543 psi (244 bar) at 500 F, 3169 psi (218 bar) at 750 F, 3129 psi (215 bar) at 800 F and still 3011 psi (207 bar) at 1000 F (538 C). That flat curve is what the 316 stainless chamber buys over carbon steel, and it is the headline reason to specify this code in hot hydrocarbon service.
Magnetrol B40-4C40 specification table
| Chamber code | 4C40 |
| Chamber material | 316 stainless steel |
| Tank connection | 1-1/2 inch socket weld |
| Minimum specific gravity | 0.65 |
| Rating at 100 F | 3700 psi (255 bar) |
| Rating at 500 F | 3543 psi (244 bar) |
| Rating at 750 F | 3169 psi (218 bar) |
| Rating at 1000 F | 3011 psi (207 bar) |
| Float | 300 series stainless steel |
| Process temperature | Up to +1000 F (+538 C) |
| Switch enclosure | Type 4X polymer-coated steel, or polymer-coated aluminum with various approvals |
| Hydrostatic test | 1.5 times the design pressure |
| Weld standard | ASME Section IX welders and procedures, full penetration |
| Options | Flanged connections, ASME B31.1, temperature extensions, ATEX housing, low specific gravity calibration, additional QC testing |
How the B40 switch mechanism works
Permanent magnetic force is the only link between float and switch. As liquid level moves the pivoted float, a magnetic sleeve enters or leaves the field of a switch actuating magnet. A non-magnetic barrier tube isolates the mechanism from the liquid, and a tension spring returns the assembly on a falling level. Switch choices include dry contact styles and hermetically sealed styles; the datasheet gives, for example, Series C ratings of 15 A at 120 or 240 VAC and 6 A at 24 VDC, and shows hermetic Series F and HS capsules that stand up to salt and corrosive atmospheres.
How B40-4C40 differs from other B40 variants
Among B40 chambers the code decides rating and metallurgy. The carbon steel 3C30 (1-1/2 inch socket weld) falls from 1925 psi at 100 F to just 215 psi at 1000 F, and 5C20 with a 1 inch socket weld shows 2085 psi at 100 F and 165 psi at 1000 F. The chrome-moly 1F30, 1B60 and 1C50 types hold 2067 psi, 2067 psi and 2533 psi respectively at 100 F with much better high temperature retention. The 4C40 gives the highest cold rating in the table, 3700 psi, together with strong retention at 1000 F, but its 1-1/2 inch connection and 316 stainless chamber should be matched to the process nozzle.
Where this chamber is specified in Oman and the GCC
Accumulators, flash tanks, knock-out drums, flare pots, scrubbers, separators, receivers and storage tanks are listed by the manufacturer. In refineries, gas plants and power stations of the region these are the vessels with high alarm and shutdown duties, and an external cage makes the switch removable for proof tests without opening the vessel.
Construction quality behind the rating
Pressure vessels in this series are designed within code-specified stress limits, with design calculations, prints and qualifications available for audit. Chamber branch and circumferential weld joints are designed for full penetration. All welding is performed by qualified welders to procedures required by the ASME Boiler and Pressure Vessel Code Section IX, welds are visually inspected for full penetration, and any other non-destructive examination follows ANSI B31.1. Every chamber is hydrostatically tested at 1.5 times its design pressure, and all pressure-retaining materials are procured with certificates of conformance to confirm that components meet the required standards.
That documentation trail matters in Gulf projects where inspection bodies ask for material traceability on every pressure-containing item, and it is a good reason to quote the exact chamber code rather than just the model name.
Selection checks before ordering
- Match the nozzle to a 1-1/2 inch socket weld
- Check that fluid specific gravity is above 0.65 or request low gravity calibration
- Select switch style by temperature and contact rating
- Choose enclosure and area approval, including ATEX if needed
- Ask for ASME B31.1 documentation if the project requires it
Installation and commissioning
Weld the cage connections to the vessel nozzles to the project code, then hydrotest the vessel with the switch fitted if specified. Keep the ambient temperature at the switch head at or below +140 F (+60 C), allow about 8 inches of overhead for cover removal and confirm the actuation level from the dimension drawing. Run a wet test by raising and lowering level before putting the alarm into service.
Maintenance
The cage should be drained and flushed according to site procedure, and the float and sleeve inspected at major turnarounds. Test the alarm contacts regularly and keep the housing gasket in good condition, since moisture inside an electrical enclosure can cause nuisance trips in humid coastal sites. Confirm the full order code on the nameplate when ordering spares for an installed unit.
Related items you may also need: Magnetrol 089-9126-016 Echotel 355 Transducer Kit Lexan FM M20 Kynar | Magnetrol 036-1006-001 Pneumatic Controller Case for Modulevel | Magnetrol 089-7256-001 AC Electronics Module for Echotel 961 Hygienic | All Magnetrol products.
For the Magnetrol B40-4C40, keep the downloaded document together with your purchase order and commissioning records. Having the manufacturer reference available at installation time simplifies acceptance checks, supports later spare-part planning and gives maintenance staff a single place to confirm wiring, mounting and setup information.
Documents and quotation
The datasheet for Magnetrol B40-4C40 is attached to this page. Send your RFQ to Seven Star LLC with the chamber code, switch and enclosure code, any ASME or ATEX requirement and the quantity.
Datasheets & Documents
- Datasheet Magnetrol B40-4C40 High Pressure External Cage Level Switch Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Magnetrol is the American level and flow measurement specialist known for the Eclipse guided wave radar, Pulsar radar transmitters and the float and displacer switches that guard boilers and vessels. It was founded in 1932, is based in Aurora, Illinois, and has been part of AMETEK since 2021.
Seven Star LLC is an independent supplier in Muscat. We list Magnetrol level transmitters and level and flow switches, and supply them to refineries, gas plants and utilities in Oman and the GCC by complete model number.
Magnetrol company profile
| Established | 1932, USA; headquarters in Aurora, Illinois |
|---|---|
| Ownership | Acquired by AMETEK in March 2021 and now part of its Electronic Instruments Group |
| Product families | Guided wave radar, non-contact radar, displacer and buoyancy transmitters, ultrasonic and thermal dispersion switches, float switches and magnetic level indicators (through its Orion Instruments brand) |
| Applications | Separators, storage tanks, boilers and feedwater heaters, interface measurement, pump protection and flow detection |
Milestones
- 1932: The first mechanical buoyancy level switch; the company grows into Magnetrol, based in Aurora, Illinois.
- 1998: Eclipse Model 705, a loop-powered guided wave radar transmitter for industrial liquid level, according to Magnetrol.
- 2021: AMETEK acquires Magnetrol on 29 March.
Magnetrol products we list
| Model | Principle | Typical use |
|---|---|---|
| Eclipse 706 | Guided wave radar | Level and interface in separators, chambers and boiler drums, unaffected by changing density |
| Pulsar R80 | 80 GHz FMCW radar | Narrow-beam non-contact level in tanks with internals and in solids |
| Pulsar R86 | 26 GHz radar | Non-contact level in process and storage vessels |
| Pulsar R96 | 6 GHz radar | Non-contact level where vapour, foam or condensation are present |
| E4 Modulevel | Displacer | Level and interface in high-pressure, high-temperature vessels, often replacing older torque tube units |
| Echotel 961/962 | Ultrasonic gap switch | High and low level alarms and pump protection |
| Thermatel TD1/TD2 | Thermal dispersion switch | Flow and no-flow detection and level switching for liquids and gases |
Guided wave radar sends pulses down a probe and times the reflection from the surface, so dust, vapour and changes in density don't affect the reading. That is why it often replaces displacers on separators and chambers. Non-contact radar suits tanks where nothing should touch the product, and a higher frequency gives a narrower beam that avoids tank internals.
Where Magnetrol instruments are used
In Oman and the GCC, Magnetrol transmitters and switches measure level in production separators, slug catchers, storage tanks, boiler drums and feedwater heaters, and protect pumps in oil and gas, refining, petrochemical, power and water plants.
Ordering Magnetrol instruments: what we need
Send the complete model number from the nameplate. On Magnetrol instruments every digit sets the electronics, the probe or antenna, the process connection and the approvals. For a new application, send the medium, the dielectric constant if known, the measuring range, the pressure and temperature, the process connection and the hazardous area classification.
Facts checked against Magnetrol and AMETEK company information, October 2026.
Browse Magnetrol products by category: Level Transmitter.
FAQ
Questions about the Magnetrol B40-4C40 High Pressure External Cage
Answers from our engineering team on installation, compatibility and integration.
01What pressure is the B40-4C40 chamber rated for?
The datasheet rates code 4C40 at 3700 psi (255 bar) at 100 F, falling to 3011 psi (207 bar) at 1000 F.
02What is the tank connection on B40-4C40?
It uses a 1-1/2 inch socket weld connection with a 316 stainless steel chamber.
03What minimum specific gravity applies to the B40?
The B40 series is listed with a minimum specific gravity of 0.65, with low gravity calibration offered as an option.
04What maximum process temperature can the B40 reach?
The series can reach process temperatures up to +1000 F (+538 C), depending on the switch mechanism chosen.
05What switch types fit the B40?
Dry contact and hermetically sealed mechanisms are offered, in a Type 4X steel housing or an approved polymer-coated aluminum housing.


















Reviews