Bürkert 560204 Type 8619 multiCELL pH/Conductivity Unit

Description

Overview

When pH and conductivity must be controlled together, Bürkert 560204 puts both in one panel instrument. The Type 8619 multiCELL in this article combines the main module with a pH and ORP module, a conductivity module and an extra output module. The result is two flow inputs, two raw sensor inputs, two Pt100 or Pt1000 inputs, four transistor outputs and four 4 to 20 mA outputs. Seven Star LLC is an independent supplier serving Oman and the GCC.

Configuration of Bürkert 560204

Parameter Value
Article 560204, main + pH/ORP + conductivity + output module
Digital inputs 2
Raw sensor inputs 1 pH/ORP and 1 conductivity
Pt100/Pt1000 inputs 2
Transistor outputs 4
Analogue outputs 4 x 4 to 20 mA
pH range minus 2.0 to plus 16 pH
Conductivity range 0 microS/cm to 2 S/cm, cell dependent
UL approval No (UL version is 560212)
Housing Panel-mounted multiCELL, 1/4 DIN, 92 x 92 mm cutout, PPO housing
Supply 12 to 36 V DC plus or minus 10 percent, max. 2 A, via external SELV and LPS supply
Power consumption max. 1.5 VA for the main module alone
Display LC graphic display, 128 x 168 pixels, light blue backlight, English, German, French
Keys 4 soft keys and 1 central navigation key
Module slots 6
Data logger up to 16 values, SD or SDHC card up to 8 GB
Ambient temperature minus 10 to plus 70 degrees C with main module only; up to plus 60 degrees C with an additional module
Protection IP65 or NEMA 250 4X in front of a closed cabinet; IP20 behind the panel
Altitude and humidity max. 2000 m, below 85 percent without condensation

Why combine modules in Bürkert 560204

A single device that handles both parameters saves a cut-out, a power supply and a network drop. Cooling and boiler water often need pH correction by acid or caustic dosing and conductivity control by blowdown at the same time, and both loops can run from the same controller using separate outputs. Four transistor outputs allow acid, caustic, blowdown and alarm functions, while four 4 to 20 mA outputs re-transmit pH, conductivity and temperatures to the PLC.

How Bürkert 560204 differs from Bürkert 560200 and Bürkert 560201

Against 560200 and 560201, which carry one analytical module each and two outputs of each type, 560204 doubles the output count by adding an output module and measures two parameters. It occupies more module slots of the six available. The UL Recognized equivalent is 560212, and a Modbus TCP, PROFINET or EtherNet/IP version of a two-sensor layout requires a different row of the chart.

Troubleshooting guide

If the display shows no flow although the process is running, check the sensor supply, the digital input threshold of 5 volts or higher and the frequency range of 0.5 to 2500 Hz. If a loop output stays at 4 mA, check the loop impedance against the limits quoted for the supply voltage and confirm that the output is configured as source or sink to match the receiving device. If values freeze when a memory card is inserted, try the tested Bürkert card, because untested cards may not work reliably.

Power supply, wiring and EMC practice

The multiCELL expects a filtered and regulated 12 to 36 V DC supply from an external limited power source. Use cable rated for more than 90 degrees C, with cross sections of 0.2 to 1.5 mm2 on the terminal strip and 0.75 to 1.5 mm2 for the earth conductor. Strip insulation to 7 mm, use ferrules where possible, and keep shielded signal cable away from motor and drive cables. Where the unit is installed outdoors or in a humid place, the maximum voltage allowed drops by one volt according to the data sheet notes for the wall variant, so confirm the supply setting before energising.

Power distribution terminals marked PWR OUT can feed external loads up to 1.8 A at the supply voltage with polarity protection, which saves a separate supply for small sensors.

Dual-parameter alarm logic in Bürkert 560204

With pH and conductivity on one device, alarms can be combined. A rise in conductivity together with a fall in pH can indicate carry-over of acid or a breakthrough on an ion exchanger, while a rise in both may point to over-dosing. Use the four transistor outputs as separate relays for acid dosing, caustic dosing, blowdown and a common alarm, and let the PLC read the same values on the analogue outputs for trending and logging. Because both measurements share a single clock and data logger, events can be correlated afterwards from the SD card record.

Purchasing details for Bürkert 560204

Please state the article number, the quantity and whether UL approval is mandatory, since the UL Recognized equivalent is a separate article. Tell us which pH electrode and conductivity cell will be connected, the cable lengths, and whether the supply is a 24 V DC rail in the cabinet. Delivery to Oman and the GCC will then be planned. The device is configured at the factory, so there is no field change of modules. Record the module list from the nameplate in your asset register, because a replacement must match it exactly, and keep a backed-up parameter file on the SD card so that commissioning of a spare takes minutes instead of hours at site.

Loop design hints

Keep acid and caustic dosing on separate outputs with interlocks so that both cannot run together. Use the sensor monitor during commissioning to validate probe readings before closing the loop. Set alarm limits for both parameters and route one transistor output to a horn or lamp. Review the data log after the first weeks of operation to tune hysteresis and dosing time.

Related items you may also need: Bürkert Type 8681 Control Head for Hygienic Process Valves | Bürkert Type 6026 Direct-Acting 2/2-Way Plunger Solenoid Valve | Phoenix Contact FL MGUARD RS4004 TX/DTX Security Router | All Bürkert products.

Documents and quotation

The Type 8619 data sheet covering Bürkert 560204 is attached with ordering chart, module data and dimensions. Send an RFQ with part number 560204, quantity and delivery location in Oman or the GCC.

Other Models in the 8619 Range

Seven Star LLC supplies models from the 8619 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Bürkert 560205 Type 8619 multiCELL Flow Transmitter ControllerControllers & Data AcquisitionView details
Bürkert 560200 Type 8619 multiCELL pH/ORP ControllerControllers & Data AcquisitionView details
Bürkert 560201 Type 8619 multiCELL Conductivity ControllerControllers & Data AcquisitionView details
Bürkert 569259 Type 8619 multiCELL Modbus TCP ControllerControllers & Data AcquisitionView details
Bürkert 560204 Type 8619 multiCELL pH/Conductivity UnitControllers & Data AcquisitionYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Bürkert 560204 Type 8619 multiCELL pH/Conductivity Unit Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Bürkert is a German family-owned maker of fluid control systems, headquartered in Ingelfingen, Baden-Württemberg. Christian Bürkert founded the company in 1946, and it is known for solenoid valves, process and control valves, flow and analytical sensors, and mass flow controllers. Its products serve water treatment, hygienic processing, gas handling and laboratory applications.

Seven Star LLC lists Bürkert valves and valve automation devices and supplies Bürkert solenoid valves and spare parts to plants in Oman as an independent supplier.

Bürkert company profile

Founded 1946, by Christian Bürkert
Headquarters Ingelfingen, Germany
Ownership Family-owned
Product families Solenoid valves, angle seat process valves, positioners, flow meters, mass flow controllers

Bürkert types listed on this page

Two types are listed. Type 6026 is a direct-acting 2/2-way plunger solenoid valve, with a stainless steel bellows that separates the medium from the coil, and as a direct-acting valve it switches without needing a pressure difference. Type 8681 is the Bürkert control head that mounts on top of hygienic process valves to pilot the actuator and report valve position to the control system. Control heads of this kind are common in food, beverage and pharmaceutical plants in the GCC.

Ordering Bürkert valves: what we need

The type number alone is not enough. Send the identification number from the label, or else the type with orifice, port connection, body and seal material, coil voltage and frequency, circuit function and pressure range. For a Type 8681 control head add the communication variant and the make and model of the process valve it sits on.

Facts checked against Bürkert's published company history, October 2026.

FAQ

Questions about the Bürkert 560204 Type 8619 multiCELL pH/Conductivity

Answers from our engineering team on installation, compatibility and integration.

01What does Bürkert 560204 combine?
It combines the main module with a pH and ORP module, a conductivity module and one output module in one panel multiCELL.
02How many outputs has 560204?
It provides four transistor outputs and four 4 to 20 mA analogue outputs, with two Pt100 or Pt1000 temperature inputs.
03Is Bürkert 560204 UL approved?
No, this article has no UL approval; the UL version of the same configuration is listed as article 560212.
04What pH range does 560204 measure?
The pH input covers minus 2.0 to plus 16 pH, with ORP from minus 2000 to plus 2000 mV.
05How is 560204 mounted?
It is a panel-mounted quarter DIN unit for a 92 x 92 mm cut-out, held by four fastening elements, with IP65 on the front.