E5CN-HR2M-500: advanced temperature controller with relay output

The Omron E5CN-HR2M-500 is a 48 x 48 mm advanced digital temperature controller with a relay control output, two auxiliary relay outputs and universal sensor input. It samples the input every 60 ms, displays with 0.01°C resolution and carries the advanced functions of the E5CN-H line, such as logic operations and a control output ON/OFF counter. Seven Star LLC supplies the E5CN-HR2M-500 in Oman and the GCC as an independent supplier in Muscat.

  • E5CN is the 48 x 48 mm controller size.
  • H means the advanced type.
  • R means control output 1 is a relay.
  • 2 means two auxiliary outputs.
  • M means an Option Unit can be mounted; no D means 100 to 240 VAC supply, and -500 means a terminal cover is supplied.

A relay output suits heaters and contactors directly, with the usual limits on switching frequency that apply to any electromechanical contact.

E5CN-HR2M-500 technical specifications

Parameter Specification
Manufacturer / part number Omron E5CN-HR2M-500
Control output 1 Relay: SPST-NO, 250 VAC, 3 A resistive; electrical life 100,000 operations; minimum load 5 V, 10 mA
Auxiliary outputs 2
Option unit Can be mounted (M)
Case / cover Black case with terminal cover (-500)
Supply voltage 100 to 240 VAC, 50/60 Hz; operating range 85% to 110%
Power consumption 8.5 VA max. (HR2 types at 100 VAC: 3.0 VA)
Sensor input Thermocouple K, J, T, E, L, U, N, R, S, B, W, PL II; Pt100, JPt100; 4 to 20 mA, 0 to 20 mA; 1 to 5 V, 0 to 5 V, 0 to 10 V (selectable)
Indication accuracy Thermocouple: ±0.1% of PV or ±1°C, whichever greater, ±1 digit; Pt: ±0.1% or ±0.5°C, ±1 digit; analog: ±0.1% FS ±1 digit
Input sampling period 60 ms
Control method ON/OFF or 2-PID with auto-tuning
Control period 0.5 s, or 1 to 99 s in 1 s steps
Auxiliary outputs Two relay outputs, SPST-NO, 250 VAC, 3 A resistive; ON/OFF delays 0 to 999 s
Display 5-digit, 2-level PV and SV; 0.01°C resolution
Memory protection Non-volatile memory, 1,000,000 writes
Degree of protection Front panel IP66; rear case IP20; terminals IP00
Weight Controller approx. 150 g; bracket approx. 10 g
Setup software CX-Thermo version 4.0 or higher

Values come from the Omron E5CN-H datasheet. The relay output life is 100,000 operations, so use the control period and the datasheet ON/OFF counter alarm to plan relay replacement.

How E5CN-HR2M-500 controls temperature

The E5CN-H reads the sensor signal, compares it with the set point and calculates an output using ON/OFF or 2-PID control with auto-tuning. With a relay output the controller switches the contact on a time-proportioned basis over the chosen control period, from 0.5 s to 99 s.

Two auxiliary relay outputs act as alarms, and ON and OFF delays of 0 to 999 s can be set. The advanced type adds logic operations (AND, OR and delays) set from CX-Thermo, a PV/SV status display that alternates controller status with the process value, a PV change rate alarm and a simple program function. The control output ON/OFF counter helps predict relay wear.

Where E5CN-HR2M-500 fits: option units and related models

The E5CN-HR2M-500 is the relay-output member of the 100 to 240 VAC black-case group. For SSR driving use E5CN-HQ2M-500, for 4 to 20 mA use E5CN-HC2M-500, and for 0 to 10 V use E5CN-HV2M-500. A 24 V supply version is E5CN-HR2MD-500 and silver cases carry a W in the code.

Option Unit Adds
E53-CNBN2 Two event inputs
E53-CNQBN2 Control output 2 plus event inputs
E53-CN03N2 RS-485 communications
E53-CNHBN2 / E53-CNH03N2 Heater burnout / SSR failure / overcurrent (CT1) with event inputs or RS-485
E53-CNQFN2 / CNBFN2 Transfer output (with control output 2 or event inputs)

Option Units are ordered separately and fitted into the controller; not every combination of function 1 and function 2 is available, so check the datasheet legend. The N2 version suffix applies to option units released after January 2008. The E5CN-H is configured with the CX-Thermo support software or from the front keys.

Selection and ordering checklist for E5CN-HR2M-500

Settle these points before asking for a quotation on E5CN-HR2M-500.

  • Confirm that a relay output is suitable; for frequent switching or heavy heaters use a voltage output with an SSR.
  • Define the sensor type and range; the universal input accepts thermocouples, Pt100/JPt100, current and voltage.
  • Check supply: 100 to 240 VAC (no D) or 24 VAC/VDC (D).
  • Check heater current against the 3 A relay rating.
  • Choose option units for communications, event inputs, heater burnout or transfer output.
  • Decide on black or silver case.

Installation, commissioning and maintenance of E5CN-HR2M-500

Mount the controller in a 48 x 48 mm panel cut-out with the bracket supplied, connect supply, sensor and outputs per the terminal diagram, and set input type and range before the set point.

  • Select the sensor type and units first.
  • Run auto-tuning with the load connected.
  • Set alarms on the auxiliary outputs and test them.
  • Use the ON/OFF counter alarm to plan relay replacement.
  • Back up parameters using CX-Thermo.

Typical E5CN-HR2M-500 applications in Oman and the GCC

This controller serves ovens, furnaces, heaters, extruders, sterilisers, test chambers and process heating loops. In Oman and the GCC it is used in industrial ovens, laboratory equipment, heat-treatment lines and packaging machines.

Heat and dust in plant environments call for good panel ventilation. The front panel is IP66, protecting against washdown or dust at the face.

E5CN-H family compared with E5CN-HR2M-500

The datasheet lists a set of E5CN-H controllers built from the same universal-input core. The table shows the models in the ordering section.

Model Supply Control output 1 Auxiliary outputs Case
E5CN-HR2M-500 100 to 240 VAC Relay 2 Black
E5CN-HQ2M-500 100 to 240 VAC Voltage (for driving SSR) 2 Black
E5CN-HC2M-500 100 to 240 VAC Current 2 Black
E5CN-HV2M-500 100 to 240 VAC Linear voltage 2 Black
E5CN-HR2MD-500 / HQ2MD-500 24 VAC/VDC Relay / voltage (SSR) 2 Black
E5CN-HR2M-W-500 / HQ2M-W-500 100 to 240 VAC Relay / voltage (SSR) 2 Silver
E5CN-HR2MD-W-500 / HQ2MD-W-500 24 VAC/VDC Relay / voltage (SSR) 2 Silver

Information to send with an RFQ for E5CN-HR2M-500

  • Part number E5CN-HR2M-500 and quantity.
  • Sensor type and range.
  • Supply voltage.
  • Heater load.
  • Option units needed.
  • Delivery location.

Documents and quotation

A datasheet for the E5CN-H series is attached on this page, with the model legend, ordering information, specifications, input ranges, alarm types and precautions for E5CN-HR2M-500.

Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer. Send the part number E5CN-HR2M-500 with the sensor type, supply voltage and any option units, and we will confirm availability and lead time for Oman and the GCC.

Other Models in the Omron E5cn H Controllers Range

Seven Star LLC supplies models from the Omron E5cn H Controllers range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Omron E5CN-HR2M-500 Advanced PID Temperature Controller, RelayControllers & Data AcquisitionYou are viewing this model
Omron E5CN-HQ2M-500 Advanced PID Temperature Controller, SSRControllers & Data AcquisitionView details
Datasheets & Documents
  • PDF Datasheet Omron E5CN-HR2M-500 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Omron is a Japanese electronics and automation company, founded in 1933 in Osaka by Kazuma Tateisi and now headquartered in Kyoto. Its industrial automation business makes PLCs, I/O, sensors, relays, safety components, motion control and robots. Omron's CJ and NX series controllers and I/O units are widely used in machine building.

Seven Star LLC lists Omron PLC input and output units from the CJ and NX series and supplies them to panel builders and maintenance teams in Oman.

Omron company profile

Founded 1933, Osaka, Japan
Founder Kazuma Tateisi
Headquarters Kyoto, Japan
Business Industrial automation, healthcare, electronic components
Product families CJ1/CJ2 PLCs and I/O units, NX and NJ controllers, NX I/O, E2E proximity sensors, G2R and MY relays

Omron CJ-series and NX-series units listed here

Three I/O units are on this page. The CJ1W-ID211 is a CJ-series 16-point 24 VDC input unit and the CJ1W-OC211 is a CJ-series 16-point relay output unit. The NX-ID5442 is an NX-series 16-point 24 VDC digital input unit for PNP wiring, 12 mm wide with push-in terminals. CJ and NX units belong to different hardware platforms and do not plug into each other's racks.

Omron products we list

Family Examples
PLC & I/O Cards CJ1W-ID211 CJ-Series 16-Point 24 VDC Inp…, CJ1W-OC211 CJ-Series 16-Point Relay Outp…, NX-ID5442 NX-Series 16-Point Digital Inp…

Ordering Omron PLC modules: what we need

Send the complete model number from the front or side label of the unit, including every suffix. If you are replacing a failed card, add the CPU or coupler model it is mounted with, and tell us if the terminal block or connector is needed as well. For obsolete Omron PLC parts we check which successor the manufacturer documents. Requests from other GCC countries are handled the same way.

Facts checked against Omron's published company history, October 2026.

FAQ

Questions about the Omron E5CN-HR2M-500 Advanced PID Temperature

Answers from our engineering team on installation, compatibility and integration.

01What input types does E5CN-HR2M-500 accept?
Thermocouples K, J, T, E, L, U, N, R, S, B, W and PL II, Pt100 and JPt100, 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V and 0 to 10 V.
02What is the sampling period?
60 ms, with indication accuracy of 0.1% of PV for thermocouple and Pt inputs, subject to the minimum degree figure in the datasheet.
03What can the relay output switch?
SPST-NO, 250 VAC, 3 A resistive load with 100,000 operations electrical life and a minimum load of 5 V, 10 mA.
04How many alarm outputs does E5CN-HR2M-500 have?
Two auxiliary relay outputs, each SPST-NO 250 VAC 3 A, with ON and OFF delays of 0 to 999 s.
05What protection does the front panel have?
IP66 on the front panel, IP20 on the rear case and IP00 on terminals.