- Automation & ControlView all 3,060 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Isolator & Barrier
- Controllers & Data Acquisition
- Safety Switches & Guard Locking
- Motor Soft Starters
- Encoders
- CCTV & Security
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Magnetrol
Magnetrol TK1 Side-Mounted Float Level Switch, 316 SS
Description
Overview
Magnetrol TK1 is a side-mounted float level switch for single-point high or low level alarms in tanks and process vessels. It is built entirely from stainless steel, uses a magnet and a hermetically sealed reed switch, and enters the vessel horizontally through a 1.5 or 2 inch threaded or flanged connection. The design targets OEM skids and small process vessels where a simple, rugged alarm is wanted without a stilling chamber. Seven Star LLC is an independent supplier serving Oman and the GCC.
Compared with a chamber-mounted float switch, this unit has no cage, no bridle piping and no separate valves, so the installed cost and the leak points are both lower. It is a point switch rather than a transmitter, which makes it the right choice when the control philosophy only needs a high alarm, a low alarm or an overflow trip, and when the operator wants every wetted part to be stainless steel for chemical compatibility.
Principle of operation
A magnet is fixed to the pivoting float assembly. A reed switch sits on the dry side of the barrier. As the liquid rises or falls, the float arm swings and carries the magnet toward or away from the reed switch, which makes or breaks the circuit. Because only magnetic force crosses the barrier, there is no dynamic seal to leak, and the unit works on rising or falling level depending on how it is wired and mounted.
Magnetrol TK1 at a glance
- Pressure rating up to 1500 psi (103 bar)
- Process temperature from -40 to +300 F (-40 to +149 C)
- Minimum specific gravity of 0.40
- All 316/316L stainless steel construction with an 18-8 stainless pivot pin
- 1.5 inch or 2 inch NPT or BSP threads, or 2 inch 150 or 300 pound ANSI flanges
- Narrow differential of 0.50 inch
- SPST, SPDT or DPDT contacts
- Enclosure Type 4X/7/9 for Class I Division 1 Groups C and D
Magnetrol TK1 technical data
| Float and trim | 316/316L stainless steel, 18-8 stainless pivot pin |
| Mounting connection material | 316/316L stainless steel |
| Physical range | Narrow differential, 0.50 inch |
| Minimum specific gravity | 0.40 |
| Maximum process pressure | 1500 psi (103 bar) |
| Process temperature | -40 to +300 F (-40 to +149 C) |
| Ambient temperature | -40 to +160 F (-40 to +71 C) |
| Contacts | SPST, SPDT or DPDT |
| SPST rating | 100 VA, 240 VAC/VDC maximum, 1.0 A maximum |
| SPDT rating | 30 VA, 240 VAC/DC maximum, 0.5 A maximum |
| DPDT relay | 42 VA, 5 A at 24 VDC or 120 VAC, hermetically sealed |
| Contact material | Silver cad-oxide |
| Electrical connection | 1/2 inch NPT or condulet box with 3/4 inch NPT |
| Enclosure | 316/316L stainless steel or cast iron/aluminum |
Decoding the Magnetrol TK1 model number
The code starts with TK1. Then comes a float stem code: 0 is the standard length for 1.5 inch nozzles up to 0.71 inch long and 2 inch nozzles up to 1.94 inch long, while 1 is an extended stem for 1.5 inch nozzles between 0.72 and 1.25 inch long. The connection size is 1 for 1.5 inch (NPT or BSP-T only) or 2 for 2 inch. The connection type is N for NPT, T for tapered BSP, A for a 150 pound ANSI raised-face flange or B for 300 pound, the flange options being 2 inch only. The material code B is 316/316L stainless steel.
The switch letter is R for SPST reed, S for SPDT reed, D for a four-wire DPDT powered relay in a junction box at 120 VAC, or E for the same at 24 VDC. The housing letter J is 316 SS with FM explosion-proof approval, A adds a cast iron or aluminum junction box, K is CSA explosion-proof, and C is CSA with junction box. Because the switch and housing letters set both electrical rating and approval, always confirm the full order code on the nameplate or from your project data sheet.
Typical applications in oil, water and industry
The TK1 shows up in storage tanks, seal pots, skid-mounted separators, day tanks, lube oil reservoirs and drain vessels. In an overflow protection or low-level shutdown role it gives a dependable discrete signal to the control system. Its all-stainless wetted parts suit chemical dosing tanks and water treatment vessels, and the explosion-proof housing options make it practical in classified areas of Gulf oil and gas facilities.
Selecting among connection and switch options
Pick threads when the nozzle is a standard half-coupling, and flanges when the vessel code requires them. The extended stem is for nozzles that are slightly thicker than normal, so the float swings clear of the nozzle wall. Confirm that the fluid has a specific gravity of at least 0.40 and that the pressure stays within 1500 psi. For motor starter coils or higher loads, choose the DPDT powered relay and remember that it needs a 120 VAC or 24 VDC supply.
Installation tips
Mount the switch horizontally with the float free to travel through the narrow 0.50 inch differential. The drawing shows roughly 6.50 inches from the process face to the electrical entry. Allow for the 0.75 inch of extra length with extended stems. Seal the conduit entry at the housing and wire the contacts according to the label for rising or falling level.
Maintenance and checks
Inspect the float for fouling and check the pivot for free movement at each turnaround. Test the alarm by raising and lowering the level or by tilting the float where the process allows. Look for moisture inside the housing and replace gaskets as needed. The reed capsule is hermetically sealed, so electrical wear is minimal.
Related items you may also need: Magnetrol 089-7260-002 Input Wiring Board, Full Feature, Thermatel TA2 | Magnetrol Z30-2043-002 Echotel 910 Phono Jack PC Board 24 VDC | Magnetrol 089-7905-001 TG1 DIN Rail Housing and Electronics | All Magnetrol products.
Documents and quotation
The datasheet for Magnetrol TK1 is provided on this page. Send an RFQ to Seven Star LLC with the TK1 code you need, including connection size and type, switch letter, housing letter and quantity. Matching an existing nameplate removes any ambiguity.
Datasheets & Documents
- Datasheet Magnetrol TK1 Side-Mounted Float Level Switch, 316 SS Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Magnetrol is the American level and flow measurement specialist known for the Eclipse guided wave radar, Pulsar radar transmitters and the float and displacer switches that guard boilers and vessels. It was founded in 1932, is based in Aurora, Illinois, and has been part of AMETEK since 2021.
Seven Star LLC is an independent supplier in Muscat. We list Magnetrol level transmitters and level and flow switches, and supply them to refineries, gas plants and utilities in Oman and the GCC by complete model number.
Magnetrol company profile
| Established | 1932, USA; headquarters in Aurora, Illinois |
|---|---|
| Ownership | Acquired by AMETEK in March 2021 and now part of its Electronic Instruments Group |
| Product families | Guided wave radar, non-contact radar, displacer and buoyancy transmitters, ultrasonic and thermal dispersion switches, float switches and magnetic level indicators (through its Orion Instruments brand) |
| Applications | Separators, storage tanks, boilers and feedwater heaters, interface measurement, pump protection and flow detection |
Milestones
- 1932: The first mechanical buoyancy level switch; the company grows into Magnetrol, based in Aurora, Illinois.
- 1998: Eclipse Model 705, a loop-powered guided wave radar transmitter for industrial liquid level, according to Magnetrol.
- 2021: AMETEK acquires Magnetrol on 29 March.
Magnetrol products we list
| Model | Principle | Typical use |
|---|---|---|
| Eclipse 706 | Guided wave radar | Level and interface in separators, chambers and boiler drums, unaffected by changing density |
| Pulsar R80 | 80 GHz FMCW radar | Narrow-beam non-contact level in tanks with internals and in solids |
| Pulsar R86 | 26 GHz radar | Non-contact level in process and storage vessels |
| Pulsar R96 | 6 GHz radar | Non-contact level where vapour, foam or condensation are present |
| E4 Modulevel | Displacer | Level and interface in high-pressure, high-temperature vessels, often replacing older torque tube units |
| Echotel 961/962 | Ultrasonic gap switch | High and low level alarms and pump protection |
| Thermatel TD1/TD2 | Thermal dispersion switch | Flow and no-flow detection and level switching for liquids and gases |
Guided wave radar sends pulses down a probe and times the reflection from the surface, so dust, vapour and changes in density don't affect the reading. That is why it often replaces displacers on separators and chambers. Non-contact radar suits tanks where nothing should touch the product, and a higher frequency gives a narrower beam that avoids tank internals.
Where Magnetrol instruments are used
In Oman and the GCC, Magnetrol transmitters and switches measure level in production separators, slug catchers, storage tanks, boiler drums and feedwater heaters, and protect pumps in oil and gas, refining, petrochemical, power and water plants.
Ordering Magnetrol instruments: what we need
Send the complete model number from the nameplate. On Magnetrol instruments every digit sets the electronics, the probe or antenna, the process connection and the approvals. For a new application, send the medium, the dielectric constant if known, the measuring range, the pressure and temperature, the process connection and the hazardous area classification.
Facts checked against Magnetrol and AMETEK company information, October 2026.
Browse Magnetrol products by category: Level Transmitter.
FAQ
Questions about the Magnetrol TK1 Side-Mounted Float Level Switch, 316
Answers from our engineering team on installation, compatibility and integration.
01What is the maximum pressure and temperature of the TK1?
The datasheet gives 1500 psi (103 bar) maximum process pressure and a process temperature range of -40 to +300 F (-40 to +149 C).
02How does the TK1 float switch actuate?
A float magnet moves toward or away from a hermetically sealed reed switch across a non-magnetic barrier, making or breaking the circuit.
03What connection sizes does the TK1 offer?
It is offered in 1.5 or 2 inch NPT or BSP threads and in 2 inch 150 or 300 pound ANSI raised-face flanges.
04What contact types are available on TK1?
SPST reed, SPDT reed, or a four-wire DPDT powered relay for 120 VAC or 24 VDC are available.
05What specific gravity can the TK1 handle?
Its minimum specific gravity is 0.40, so it works with many light hydrocarbons as well as water.


















Reviews
There are no reviews yet.