Brand:

Legrand 422600 DPX3 630 Magnetic-Only MCCB 3P 630 A 36 kA

Description

422600: Legrand DPX3 630 magnetic-only MCCB, 3P 630 A 36 kA, what the reference means

The Legrand 422600 is a fixed, front-connected moulded case circuit breaker from the DPX3 630 family: three poles, 630 A, a breaking capacity of 36 kA at 400 V and a magnetic-only release. It is meant for circuits where the overload function is handled elsewhere, typically motor feeders with their own overload relay, generator and transformer short-circuit back-up, or large controlled loads.

The datasheet lists the magnetic-only family in two breaking classes, 36 kA and 70 kA, with 400 A, 500 A and 630 A ratings and 3P and 4P versions. The Legrand 422600 is the 630 A, 3P position in the 36 kA class. Reading the numbers across the range is easy: 422598 and 422599 are the 400 A and 500 A three-pole companions, while 422601 to 422603 belong to the 70 kA class.

Seven Star LLC supplies the Legrand 422600 as an independent supplier in Muscat serving Oman and the GCC. We are not affiliated with the manufacturer, and we confirm the exact reference against your drawing before a quotation.

Technical specifications of Legrand 422600

Parameter Specification
Manufacturer / part number Legrand / 422600
Range DPX3 630, magnetic-only MCCB
Poles 3P
Rated current Iu 630 A
Breaking capacity Icu 36 kA at 400 V, 50 Hz
Rated operational voltage Ue 220 – 690 V
Rated insulation voltage Ui 800 V
Rated impulse withstand Uimp 8 kV
Magnetic release Adjustable 5 – 10 x In (3,150 – 6,300 A at 630 A)
Thermal release None (magnetic-only)
Utilisation category A, suitable for isolation
Electrical endurance 4,000 cycles at In; 8,000 cycles at 0.5 x In
Mechanical endurance 20,000 cycles (10,000 with motor control)
Dimensions (3P) 140 x 266 x 108 mm (W x H x D)
Operating temperature -25 °C to +70 °C
Degree of protection IP30
Construction Fixed, front screw connection, wing knob
Mounting On plate; not DIN rail
Auxiliary contacts 2 changeover contacts

How a magnetic-only breaker works and what it leaves to other devices

A magnetic release uses a coil in series with the main current. When a short circuit pushes the current beyond the set level, the coil force overcomes a spring and the mechanism opens within a few milliseconds. The 422600 lets you turn the dial between 5 and 10 times the rated current, so you can place the trip point above the inrush of a motor or transformer but below the minimum fault current at the far end of the cable.

Because there is no thermal element, the breaker will not protect against a slow overload. Pair it with a motor protection relay, an overload relay on the contactor, or an electronic relay that monitors current and trips the contactor. This is a common arrangement in motor control centres, where the breaker provides short-circuit protection and isolation while the starter provides overload protection and control.

Where 422600 fits in the system and related parts

The 630 A frame sits in the middle of the DPX3 line: below it are the DPX3 160 and DPX3 250 devices, such as 420003, 420207 and 420239, and above it the DPX3 1600. Within the magnetic-only 630 family the sheet lists these references:

Rating 3P 36 kA 3P 70 kA
400 A 422598 422601
500 A 422599 422602
630 A 422600 (this device) 422603

The 4P versions use separate references listed in the datasheet. Accessories listed there include shunt releases for 24 to 400 V, undervoltage releases, time-lag undervoltage modules, earth leakage modules, rotary handles and motor operators. They fit the same housing, so a spare or a retrofit can reuse the accessory set when the reference matches.

Selection and ordering checklist for 422600

  • Confirm that overload protection is provided elsewhere. If not, a thermal-magnetic or electronic DPX3 630 version is required.
  • Check the prospective fault level against 36 kA at 400 V. Use the 70 kA class where the value is higher, and check the voltage-dependent values for 480 V to 690 V supplies.
  • Set the magnetic level using the inrush of the motor or transformer and the minimum fault current, within the 3,150 – 6,300 A range.
  • Decide 3P or 4P and the neutral treatment.
  • Check the plate size: the 3P body is 140 mm wide and 266 mm high, and DIN rail mounting is not possible.
  • List accessories: releases, contacts, handle or motor operator, earth leakage module.

Installation, commissioning and maintenance of 422600

The breaker is supplied with connection plates for bars up to 32 mm wide and with seals for the adjustment dials. Mount it on a plate in the vertical or horizontal position, as the sheet allows, torque the connections to the instruction sheet values and fit the phase barriers. After connection, set the magnetic dial, fit the sealing cover if the project requires it and write the setting on the panel record.

Temperature affects the usable current. The sheet shows that a 630 A rating is held up to 50 °C ambient and reduced to 580 A at 60 °C and 530 A at 70 °C; altitude above 2,000 m reduces the rated current and voltage. For maintenance, check terminal temperature under load, exercise the handle, and record any trip with its cause before you reset.

Typical applications in Oman and the GCC

Large magnetic-only breakers appear in motor control centres for desalination high-pressure pumps, seawater intake pumps, compressors and fans, as well as in transformer secondary protection in power and water utilities. They are used where the thermal characteristic of a standard breaker would cause nuisance trips on long starting times or where a dedicated overload relay offers better protection of the motor.

In oil and gas facilities, in substations and in industrial estates across Oman, the cabinets that house such breakers see high ambient temperatures, dust and humidity. Use the derating table, specify ventilated or air-conditioned rooms, and schedule thermography so that a loose joint is found before it fails.

Information to send with an RFQ for 422600

  • Part number 422600 and the quantity.
  • System voltage, frequency and earthing arrangement.
  • Prospective short-circuit current and the load type (motor, transformer, feeder).
  • Accessories needed: shunt or undervoltage release voltage, contacts, handle, motor operator.
  • Nameplate photo or existing reference if this is a replacement.
  • Delivery location and required date.

Documents and quotation

A technical sheet for the DPX3 630 magnetic-only family is attached on this page. It lists the range, dimensions, characteristics, accessories and curves for the 422600 and its siblings.

Send the part number and the quantity to Seven Star LLC and we will confirm availability, lead time and compatible accessories for your RFQ.

Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Legrand is a French maker of electrical and digital building infrastructure, headquartered in Limoges. Its roots lie in a nineteenth-century porcelain workshop in Limoges, and it grew into one of the largest makers of wiring devices, circuit protection, cable management and data centre products. Legrand is listed on Euronext Paris and sells under brands including Legrand, Bticino and Cablofil.

Seven Star LLC, an independent supplier in Muscat, lists Legrand circuit breakers for electrical contractors and panel builders in Oman and the GCC, at present a DX3 4-pole miniature circuit breaker rated C32.

Legrand company profile

Headquarters Limoges, France
Listing Euronext Paris
Brands Legrand, Bticino, Cablofil, Zucchini
Product families DX3 miniature circuit breakers and RCDs, wiring devices, cable trays, busbar trunking, UPS

Legrand DX3 circuit breakers

DX3 is the Legrand family of modular protection devices for DIN rail mounting. The item on our site is a 4-pole MCB with a C tripping curve and a 32 A rated current. Three things besides the pole count define a breaker of this kind: the curve, the rated current and the breaking capacity printed on the front. Legrand catalogs DX3 breakers in 6000 A and 10000 A versions under separate references.

Ordering Legrand breakers: what we need

Send the Legrand catalog number printed on the device, a six-digit reference, where it is legible. Otherwise give the number of poles, the curve, the rated current, the breaking capacity and the voltage. Mention any auxiliary contact or residual current add-on module fitted beside the breaker, and the board type.

Facts checked against Legrand's published corporate information, October 2026.

FAQ

Questions about the Legrand 422600 DPX3 630 Magnetic-Only MCCB 3P 630 A

Answers from our engineering team on installation, compatibility and integration.

01What does magnetic-only mean for 422600?
The 422600 has no thermal overload element. It trips on short circuit through an adjustable magnetic release, so overload protection must come from a separate device such as a motor protection relay or a thermal relay on the contactor.
02What is the magnetic setting range of 422600?
The datasheet gives an adjustable magnetic release of 5 to 10 times In, which on this 630 A rating is 3,150 A to 6,300 A. The catalogue page lists the same 3,150 – 6,300 A range.
03What breaking capacity does 422600 have?
The catalogue lists 36 kA at 400 V, 50 Hz for this three-pole 630 A breaker. The sheet table adds values at other voltages, for example 25 kA at 480/550 V class and 14 kA at 690 V for the 36 kA version.
04Can 422600 be mounted on a DIN rail?
No. The catalogue page states that DIN rail mounting is not suitable and not optional for this device. It mounts on a plate, vertical or horizontal, including a supply-inverter arrangement.
05Which accessories can be added to 422600?
The family sheet lists shunt releases, undervoltage releases, time-lag undervoltage modules, auxiliary and fault-signal contacts, earth leakage modules, rotary handles and motor operators. Confirm references for your board before ordering.