Legrand 422155 DPX3 630 Sg Electronic MCCB 4P 630 A 50 kA

Description

422155: Legrand DPX3 630 Sg electronic MCCB, 4P 630 A 50 kA, what the reference means

The Legrand 422155 is a four-pole moulded case circuit breaker from the DPX3 630 line, rated 630 A, with a 50 kA breaking capacity at 400 V and an electronic protection unit of the Sg type. Sg is the most complete of the basic electronic units: it adds an adjustable earth fault function and an LCD with buttons and a USB port to the long-delay and short-delay functions of the S2 unit.

The family sheet organises the DPX3 630 electronics in five unit types (S1, S2, S2 with measure, Sg, Sg with measure), four breaking classes (36, 50, 70 and 100 kA) and five ratings from 250 A to 630 A. In the 50 kA class and at 630 A the references are 422512 (S1 3P), 422517 (S1 4P), 422150 and Legrand 422155 (Sg 3P and 4P) and 422190 and 422195 (Sg with measure). The 422155 is the 4P Sg version without the measurement option.

Seven Star LLC supplies the Legrand 422155 in Oman and the GCC as an independent supplier in Muscat and is not affiliated with the manufacturer. For a replacement, send the nameplate photo so that we can compare the frame, unit type and class.

Technical specifications of Legrand 422155

Parameter Specification
Manufacturer / part number Legrand / 422155
Range DPX3 630, electronic trip unit Sg
Poles 4P
Rated current In 630 A
Breaking capacity Icu 50 kA at 400 V, 50 Hz; Ics 100 percent of Icu
Rated operational voltage Ue 220 – 690 V
Rated insulation voltage Ui 800 V
Rated impulse withstand Uimp 8 kV
Long-delay Ir 0.4 – 1 x In in 1 A steps (252 – 630 A); Tr 3 – 30 s
Short-delay Isd 1.5 – 10 x Ir (378 – 6,300 A at 630 A); Tsd 0 – 500 ms
Earth fault Ig 0.2 – 1 x In or OFF; Tg 0.1 – 1 s
Neutral protection (4P) 0 / 50 / 100 / 150 / 200 percent
Utilisation category A (In 500 A and above), suitable for isolation
Electrical endurance 4,000 cycles at In; 8,000 at 0.5 x In
Dimensions (4P) 183 x 260 x 105 mm (W x H x D)
Weight, fixed 4P (500 A and above) 7.80 kg maximum
Pole pitch 42 mm
Operating temperature -25 °C to +70 °C
Degree of protection IP30
Construction Fixed, front screw connection, wing knob
Auxiliary contacts 2 changeover contacts
Unit battery 2 x CR1616 lithium cells

How the Sg electronic unit of 422155 works

Current transformers inside the breaker feed an electronic unit that calculates the true RMS value of each phase current and compares it with the stored thresholds. The long-delay function provides an inverse-time overload characteristic, set by Ir and by the time delay Tr. The short-delay function trips on a short circuit after a set time, so that downstream breakers have the chance to clear a fault first; the choice between a fixed-time and an I squared t characteristic is listed in the sheet. A fixed instantaneous level backs this up for the heaviest faults.

The Sg version adds the earth fault protection, with a pick-up between 0.2 and 1 times In and a time delay up to one second. For 4P devices the neutral protection can be set to zero, 50, 100, 150 or 200 percent of the phase setting, which helps on networks with heavy third-harmonic loads. The unit also protects itself: it trips if its internal temperature goes above 95 °C and runs a watchdog self-test. Logic and dynamic selectivity, described on the catalogue page, support coordination with other DPX3 devices.

Where 422155 fits in a DPX3 630 installation and related parts

The 630 A electronic breaker typically serves as a main incomer or a large feeder breaker behind a transformer or generator. Within the 50 kA class at 630 A, the family sheet lists these companions:

Unit type 3P 4P
S1 422512 422517
S2 422070 422075
S2 with measure 422110 422115
Sg 422150 422155 (this device)
Sg with measure 422190 422195

Lower ratings in the same class use neighbouring references, and the magnetic-only DPX3 630 such as the 422600 serves motor feeders where the overload function is external. Accessories shown for this family include shunt and undervoltage releases, earth leakage modules, motor operators, rotary handles, plug-in and draw-out bases, and a Modbus communication interface with software for configuration.

Selection and ordering checklist for 422155

  • Confirm that a 630 A, 4P, 50 kA Sg unit matches the drawing; the same frame exists as 3P and in 36, 70 and 100 kA classes.
  • Check the prospective fault level at 400 V and 690 V, using the voltage table of the sheet.
  • Decide whether energy measurement is needed. If so, the Sg with measure version is a different reference.
  • Define the neutral setting needed for the load, and whether earth fault protection should trip or only signal.
  • Plan the power supply for the unit at low load: auxiliary supply, Modbus interface or USB.
  • List accessories: shunt or undervoltage release, contacts, motor operator, plug-in or draw-out base, phase barriers.

Installation, commissioning and maintenance of 422155

The breaker is delivered with fixing screws, connection screws, bar connection plates and insulating phase barriers. Mount it on a plate in a vertical or horizontal position, with the first conductor support within the distance recommended in the sheet for the fault level (300 mm at 50 kA). Torque the connections correctly and check the thermal condition of the bars with a thermal camera after the first loaded period.

During commissioning set Ir, Tr, Isd, Tsd and the earth fault values from the protection study, then run the test function from the unit and record the settings. The sheet gives long-time derating with temperature: 630 A is held to 50 °C and drops to 567 A at 60 °C and 536 A at 70 °C. Replace the battery cells according to the manual, keep the sealing cover for settings protected, and download event data through the USB port when diagnosing a trip.

Typical applications in Oman and the GCC

A 630 A electronic breaker with earth fault protection is used on the main low-voltage boards of desalination plants, water pumping stations, industrial workshops, hospitals and commercial buildings in Oman and the GCC. It usually sits behind a distribution transformer or a standby generator, where the adjustable time delays allow selectivity with the feeders behind it and the earth fault function limits damage from insulation faults.

The harsh outdoor climate drives cabinet design more than the breaker itself. High ambient temperature means checking the derating table, dust asks for filtered ventilation, and humid coastal air favours regular tightening and inspection of busbar joints. Specify the settings in the protection study and keep a copy with the maintenance records.

Information to send with an RFQ for 422155

  • Part number 422155 and the quantity.
  • Source and system data: transformer or generator rating, voltage, earthing system.
  • Prospective short-circuit current and selectivity requirements.
  • Accessories needed: communication interface, releases, contacts, motor operator, base.
  • Nameplate photo of the existing breaker for replacements.
  • Delivery location in Oman or the GCC and the required date.

Documents and quotation

A technical sheet for the DPX3 630 electronic circuit breakers is attached on this page. It covers the range, dimensions, characteristics, protection unit functions, accessories and curves relevant to the 422155.

Send the part number and quantity to Seven Star LLC and we will confirm availability, lead time and accessories for your RFQ.

Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Legrand is a French maker of electrical and digital building infrastructure, headquartered in Limoges. Its roots lie in a nineteenth-century porcelain workshop in Limoges, and it grew into one of the largest makers of wiring devices, circuit protection, cable management and data centre products. Legrand is listed on Euronext Paris and sells under brands including Legrand, Bticino and Cablofil.

Seven Star LLC, an independent supplier in Muscat, lists Legrand circuit breakers for electrical contractors and panel builders in Oman and the GCC, at present a DX3 4-pole miniature circuit breaker rated C32.

Legrand company profile

Headquarters Limoges, France
Listing Euronext Paris
Brands Legrand, Bticino, Cablofil, Zucchini
Product families DX3 miniature circuit breakers and RCDs, wiring devices, cable trays, busbar trunking, UPS

Legrand DX3 circuit breakers

DX3 is the Legrand family of modular protection devices for DIN rail mounting. The item on our site is a 4-pole MCB with a C tripping curve and a 32 A rated current. Three things besides the pole count define a breaker of this kind: the curve, the rated current and the breaking capacity printed on the front. Legrand catalogs DX3 breakers in 6000 A and 10000 A versions under separate references.

Ordering Legrand breakers: what we need

Send the Legrand catalog number printed on the device, a six-digit reference, where it is legible. Otherwise give the number of poles, the curve, the rated current, the breaking capacity and the voltage. Mention any auxiliary contact or residual current add-on module fitted beside the breaker, and the board type.

Facts checked against Legrand's published corporate information, October 2026.

FAQ

Questions about the Legrand 422155 DPX3 630 Sg Electronic MCCB 4P 630 A

Answers from our engineering team on installation, compatibility and integration.

01What does the Sg unit on 422155 protect against?
The Sg electronic unit gives long-delay overload protection, short-delay short-circuit protection and an adjustable earth fault function. The instantaneous short-circuit threshold is fixed, and the unit also protects itself against over-temperature.
02What are the setting ranges on 422155?
Per the datasheet, Ir is 0.4 to 1 x In in 1 A steps (252 – 630 A here), Tr 3 to 30 s, Isd 1.5 to 10 x Ir in 11 steps, Tsd 0 to 500 ms, earth fault Ig 0.2 to 1 x In with Tg 0.1 to 1 s.
03What breaking capacity does 422155 offer?
The catalogue lists 50 kA at 400 V, 50 Hz. The datasheet table for the 50 kA class adds 100 kA at 220/240 V and 18 kA at 690 V, with Ics equal to 100 percent of Icu.
04How is the trip unit of 422155 powered?
The unit is normally supplied by the internal current transformers once the load exceeds a modest fraction of the rated power. An external auxiliary supply, a USB power bank or the Modbus interface keeps display and measurement alive at low load.
05What is the difference between 422155 and 422195?
Both are 4P 630 A 50 kA Sg units. The 422195 adds the energy-measurement function listed in the sheet for Sg plus measure versions, while 422155 is the Sg unit without that measuring option.