Legrand 420720 DPX3 250 Magnetic MCCB 3P 200 A 36 kA

Description

420720: Legrand DPX3 250 magnetic-only MCCB, 200 A, 36 kA, 3P

The Legrand 420720 is the 200 A version of the DPX3 250 magnetic-only moulded-case breaker: three poles, 36 kA at 400 V and an adjustable magnetic trip from 1000 to 2000 A. The catalogue describes it as a device for short-circuit protection, breaking, control and isolation of three-phase motors, with a voltage range of 220 to 690 V, IP30 protection and fixed mounting on plate or DIN rail. Seven Star LLC supplies 420720 in Oman and the GCC as an independent supplier in Muscat.

Compared with the 160 A device 420719, this version shifts the whole setting band up by a quarter: both the current rating and the trip thresholds are 25 % higher. The frame, the breaking capacity and the accessories remain the same, which makes it easy to scale a motor control centre between feeders.

How the 420720 rating and setting relate

Quantity Value Note
Rated current In 200 A Maximum continuous current
Magnetic setting 5 to 10 x In Gives 1000 to 2000 A
Icu at 380/415 V 36 kA 70 kA series exists with its own references
Thermal release None Add a separate overload relay
Reference 420720 Catalogue number to quote

Technical specifications for 420720

Parameter Specification
Manufacturer / part number Legrand / 420720 (DPX3 250 magnetic only, 3P, 200 A, 36 kA)
Type of protection Magnetic only; no thermal overload release
Poles / rated current Iu 3 / 200 A
Magnetic trip setting Adjustable 5 to 10 x In, that is 1000 to 2000 A
Rated voltage 220–690 V AC (Ue 690 V, Ui 800 V, Uimp 8 kV)
Breaking capacity Icu (IEC 60947-2) 36 kA at 380/415 V; 60 kA at 220/240 V; 30 kA at 440/460 V; 25 kA at 480/500 V; 20 kA at 600 V; 16 kA at 690 V; Ics 100 % of Icu
Making capacity Icm 75.6 kA at 415 V
Utilisation category / isolation A / suitable for isolation
Endurance Mechanical 20,000 cycles; electrical 8,000 at In and 10,000 at 0.5 In
Dimensions 3P / weight 105 x 165 x 100 mm / about 2.0 kg
Protection IP30, fixed built-in version, wing-knob control, front connection with screw terminals
Operating temperature -25 to 70 °C; tropical climate execution per data sheet
Mounting On plate or DIN rail; supplied with fixing screws, connection plates and phase barriers
Accessories Shunt and undervoltage releases, auxiliary and fault contacts, rotary handles, motor operators, plug-in base

Setting and coordinating the 420720

Choosing the setting is the central design step with a magnetic-only breaker. At 200 A the dial runs from 1000 to 2000 A. The setting must stay above the starting peak of the motor, including the first current wave, and below the smallest fault current expected at the end of the protected cable. If the fault current at the motor terminals is lower than the setting, the breaker will not clear the fault quickly, so cable length and loop impedance need a check.

Coordination with the contactor and thermal relay matters as well. The breaker should clear short circuits before they stress the contactor beyond its rated making and breaking limits, and the thermal relay should reach its own class-based trip before the breaker magnetic threshold. The data sheet also gives breaking capacity at lower voltages, 60 kA at 220/240 V for the 36 kA version, which may help with single-phase fault levels in TN systems.

Where 420720 fits and related parts

Neighbouring references are 420718 (100 A), 420719 (160 A), 420720 (200 A) and 420721 (250 A), all 36 kA. For a breaker with its own thermal element, the thermal-magnetic references such as 420207 should be considered. The data sheet lists a lock-out facility with key-type rotary handles, motor operators for remote control and a plug-in base for withdrawable versions.

Selection checklist for 420720

  • Load: 200 A feeder or a motor whose full-load current fits the starter.
  • Setting: dial between 1000 and 2000 A; check the minimum short-circuit current.
  • Overload: a separate relay is mandatory; confirm its class and setting.
  • Fault level: 36 kA at 400 V; confirm against the transformer and cable data.
  • Connection: front screw terminals, bars or lugs; larger cable needs the Cu/Al terminal kit.
  • Environment: IP30, so mount inside an enclosure.

Installation and maintenance of 420720

Fix the breaker with the supplied screws, fit the connection plates or the terminal kit, and fit the phase barriers before connecting. Torque the connections to the values in the instruction sheet and keep the first fixing point of the conductor within the distance given in the data sheet. Set the dial, seal if required, and log 420720 with the chosen value. A breaker should be exercised during outages, and a thermographic survey of the terminals after the first weeks of load can detect poor connections.

Typical applications in Oman and the GCC

Large pumps, chillers, crushers, compressors and fan systems in oil and gas, water and industrial sites in Oman and the GCC use 200 A class feeders. High ambient temperatures, dust and humidity demand an enclosure with good ventilation and a regular inspection routine, and the 690 V rating also suits some plant supplies that use higher voltage levels.

Information to send with an RFQ for 420720

  • Reference 420720 and the quantity, including spares for panel maintenance.
  • Rated current (200 A), trip type (magnetic only) and breaking capacity.
  • Motor data, starting method and overload relay.
  • Accessories such as rotary handle, shunt trip or motor operator.
  • Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
  • Any documents you need with the quotation, such as a technical data sheet or a compliance statement.

Storage, handling and spares for the Legrand 420720

Keep Legrand 420720 units in their original packaging until they are mounted. Store them indoors in a dry, dust-free room, away from direct sun and condensation. Panel shops in Oman and the GCC often hold stock in warehouses that get very hot in summer, so check that storage temperature stays within the limits given in the manufacturer datasheet.

  • Check the label and order code on every unit against the drawing before it goes into the panel.
  • Use the correct tool and tightening torque for the terminals, as given in the instructions supplied with the product.
  • Keep a small number of spare units for each rating used on site, so that a failed or damaged part can be replaced without waiting for a new shipment.
  • Record the order code in the panel documentation and the as-built drawings, so that maintenance teams can reorder the same part later.

When you plan spares for a project, group the Legrand 420720 with the other parts of the same panel in one RFQ. This keeps delivery dates aligned and makes it easier to confirm stock for the whole bill of materials at once.

Documents and quotation

The Legrand technical data sheet that covers 420720 is attached on this page. It gives the range table, dimensions, curves and accessories, so check its notes against your design before you order.

To request a quotation, send reference 420720, the quantity and your delivery location. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer; we will confirm availability and lead time for your order.

Other Models in the Legrand Dpx3 250 Mo Range

Seven Star LLC supplies models from the Legrand Dpx3 250 Mo range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Legrand 420719 DPX3 250 Magnetic MCCB 3P 160 A 36 kACircuit BreakersView details
Legrand 420720 DPX3 250 Magnetic MCCB 3P 200 A 36 kACircuit BreakersYou are viewing this model
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Legrand is a French maker of electrical and digital building infrastructure, headquartered in Limoges. Its roots lie in a nineteenth-century porcelain workshop in Limoges, and it grew into one of the largest makers of wiring devices, circuit protection, cable management and data centre products. Legrand is listed on Euronext Paris and sells under brands including Legrand, Bticino and Cablofil.

Seven Star LLC, an independent supplier in Muscat, lists Legrand circuit breakers for electrical contractors and panel builders in Oman and the GCC, at present a DX3 4-pole miniature circuit breaker rated C32.

Legrand company profile

Headquarters Limoges, France
Listing Euronext Paris
Brands Legrand, Bticino, Cablofil, Zucchini
Product families DX3 miniature circuit breakers and RCDs, wiring devices, cable trays, busbar trunking, UPS

Legrand DX3 circuit breakers

DX3 is the Legrand family of modular protection devices for DIN rail mounting. The item on our site is a 4-pole MCB with a C tripping curve and a 32 A rated current. Three things besides the pole count define a breaker of this kind: the curve, the rated current and the breaking capacity printed on the front. Legrand catalogs DX3 breakers in 6000 A and 10000 A versions under separate references.

Ordering Legrand breakers: what we need

Send the Legrand catalog number printed on the device, a six-digit reference, where it is legible. Otherwise give the number of poles, the curve, the rated current, the breaking capacity and the voltage. Mention any auxiliary contact or residual current add-on module fitted beside the breaker, and the board type.

Facts checked against Legrand's published corporate information, October 2026.

FAQ

Questions about the Legrand 420720 DPX3 250 Magnetic MCCB 3P 200 A 36 kA

Answers from our engineering team on installation, compatibility and integration.

01What is 420720?
It is a Legrand DPX3 250 magnetic-only moulded-case breaker, three poles, 200 A, 36 kA at 400 V, with an adjustable magnetic trip of 1000 to 2000 A.
02How does 420720 differ from 420719?
420720 is rated 200 A with a setting of 1000 to 2000 A, while 420719 is rated 160 A with 800 to 1600 A. The frame and breaking capacity are the same.
03Is overload protection included in 420720?
No. The breaker has no thermal release, so a thermal overload relay or motor protection device must be added to protect the motor and cable from overload.
04What voltage range does 420720 cover?
The catalogue gives 220 to 690 V AC, with Ui 800 V and Uimp 8 kV in the data sheet, and breaking capacity decreasing at higher voltage.
05What accessories fit 420720?
The data sheet lists shunt and undervoltage releases, auxiliary and fault contacts, rotary handles, motor operators and plug-in bases for the DPX3 250 frame.