Legrand 409799 DX3 4-Pole 50 A C-Curve MCB 25 kA

Description

409799: Legrand DX3 4-pole 50 A C-curve MCB, 25 kA, at a glance

The Legrand 409799 is a DX3 four-pole thermal-magnetic circuit breaker rated 50 A with a C curve and a 25 kA breaking capacity at 400 V AC. It is built on the DX3 platform that uses 1.5 modules (26.7 mm) per pole, which gives larger terminals and more thermal mass than the one-module range. All four poles are protected, the neutral is switched together with the phases and the device has a mechanical red and green position indicator. Seven Star LLC supplies 409799 in Oman and the GCC as an independent supplier in Muscat.

The data sheet for the 25 kA family describes the device as a current-limiting, trip-free breaker with positive contact indication for control, protection and isolation. It is suited to industrial and commercial boards where a high fault level is present at 400 V.

Decoding the description of 409799

Element Value Meaning
DX3 25 kA Product family Legrand DX3 modular breakers at 1.5 modules per pole with 25 kA Icu
4 pole Four protected poles Three phases and neutral protected; neutral switched concurrently
50 A Rated current Continuous rating of the breaker
Curve C Magnetic trip Instantaneous trip between 5 and 10 x In, so 250 to 500 A for 50 A
Ref. 409799 Catalogue number Quote this reference on your order

Technical specifications for 409799

Parameter Specification
Manufacturer / part number Legrand / 409799 (DX3 MCB 4 pole 50 A curve C)
Rated current 50 A, curve C (magnetic trip between 5 and 10 x In)
Poles 4 total, 4 protected, neutral switched concurrently
Rated voltage 400 V AC (360–440 V); 230/400 V and 240/415 V, 50/60 Hz per data sheet
Rated insulation voltage Ui / Uimp 500 V / 6 kV
Breaking capacity Icu (IEC 60947-2) 50 kA at 230 V, 25 kA at 400 V; Ics 75 % of Icu
Thermal thresholds Non-tripping 1.05 In, tripping 1.3 In
Width / height / depth 106.8 mm / 127.5 mm / 79.2 mm; built-in depth 47 mm
Conductors Multi-wire 1.5–35 mm²; solid-core 1.5–50 mm²
Terminal data (data sheet) Terminal depth 19 mm, strip length 17 mm, recommended torque 3 Nm
Protection IP20 terminals, IP40 enclosure front per data sheet, IK02
Temperature Operating -25 to 70 °C; storage -40 to 70 °C
Pollution degree 3
Mounting 35 mm DIN rail (EN/IEC 60715), any operating position, supply from top or bottom

How the 409799 limits fault energy

The breaker has a current-limiting contact system. On a short circuit the contacts open fast enough to cut the peak of the fault current, which reduces the stress on cables and busbars downstream. At 400 V the Icu is 25 kA and the service breaking capacity Ics is 75 % of that value, so the breaker remains usable after clearing a fault up to about 18.75 kA at 400 V. At 230 V the Icu rises to 50 kA, a figure that matters for single-pole faults to earth in TN systems.

For overload, the thermal release does not operate up to 1.05 times the rated current and operates within the conventional time at 1.3 times. The same family can also be used on direct current when the derating notes are followed; the data sheet lists a 25 kA Icu for four poles in series at 230 V DC, but direct-current duty needs the data-sheet derating table and should be confirmed before use.

Where 409799 fits and related parts

Typical use is as a feeder or motor-circuit protective device inside a main distribution board or motor control centre. The 4-pole 25 kA DX3 range runs through rated currents of 32, 40, 50 and 63 A in B and C curves, with D curve versions from 16 A. The 100 A sibling 409802 keeps the same body width but is covered by its own page data, and for smaller 4-pole breakers the one-module versions such as 407929 or 409071 save space. Auxiliaries, RCD add-on blocks and a terminal accessory for aluminium cable (4 063 10) are listed by the manufacturer for the DX3 range.

Selection checklist for 409799

  • Load: 50 A at the reference ambient; allow for the cabinet temperature.
  • Fault level: the board must stay below 25 kA at 400 V for this breaker, or use a higher rated device.
  • Curve: C for general feeders; B for long cable lengths with low fault current; D for high inrush loads.
  • Terminal capacity: 1.5 to 35 mm² flexible or 1.5 to 50 mm² rigid copper.
  • Coordination: check selectivity and back-up tables with the upstream breaker.
  • Space: six modules wide; check that the neighbours leave room for the 1.5-module poles.

Installation, locking and maintenance of 409799

Fit the breaker on the rail and tighten the terminal screws to 3 Nm using a Pozidriv no. 2 or 5.5 mm flat screwdriver. Strip conductors to 17 mm, and remember that the terminals are 19 mm deep. The handle can be sealed in either position and locked off with a 5 mm padlock using the Legrand lock-out accessory, which is useful for permit-to-work procedures. After energising, check terminal temperature during the first load cycle and record 409799 in the circuit list.

Typical applications in Oman and the GCC

A 50 A four-pole breaker with 25 kA capacity is a good match for pump-house boards, workshop supplies, desalination skid distribution and building services boards where the transformer is close to the board and fault levels are high. In dusty and hot sites, keep the enclosure closed, use filtered ventilation and avoid mounting the breaker directly above heat-producing equipment.

Information to send with an RFQ for 409799

  • Reference 409799 and the quantity, including spares for panel maintenance.
  • Curve (B, C or D), rated current and number of poles.
  • Prospective short-circuit current and supply system (TN, TT or IT).
  • Accessories needed, such as auxiliary contacts, RCD blocks or lock-out devices.
  • Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
  • Any documents you need with the quotation, such as a technical data sheet or a compliance statement.

Documents and quotation

The Legrand technical data sheet that covers 409799 is attached on this page. It gives the range table, dimensions, curves and accessories, so check its notes against your design before you order.

To request a quotation, send reference 409799, the quantity and your delivery location. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer; we will confirm availability and lead time for your order.

Other Models in the Legrand Dx3 Mcb 4p Range

Seven Star LLC supplies models from the Legrand Dx3 Mcb 4p range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Legrand 409802 DX3 4-Pole 100 A C-Curve MCBCircuit BreakersView details
Legrand 409799 DX3 4-Pole 50 A C-Curve MCB 25 kACircuit BreakersYou are viewing this model
Legrand 407929 DX3 6000 A 4-Pole 20 A C-Curve MCBCircuit BreakersView details
Legrand 409071 DX3 10000 A 4-Pole 63 A B-Curve MCBCircuit BreakersView details
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Legrand is a French maker of electrical and digital building infrastructure, headquartered in Limoges. Its roots lie in a nineteenth-century porcelain workshop in Limoges, and it grew into one of the largest makers of wiring devices, circuit protection, cable management and data centre products. Legrand is listed on Euronext Paris and sells under brands including Legrand, Bticino and Cablofil.

Seven Star LLC, an independent supplier in Muscat, lists Legrand circuit breakers for electrical contractors and panel builders in Oman and the GCC, at present a DX3 4-pole miniature circuit breaker rated C32.

Legrand company profile

Headquarters Limoges, France
Listing Euronext Paris
Brands Legrand, Bticino, Cablofil, Zucchini
Product families DX3 miniature circuit breakers and RCDs, wiring devices, cable trays, busbar trunking, UPS

Legrand DX3 circuit breakers

DX3 is the Legrand family of modular protection devices for DIN rail mounting. The item on our site is a 4-pole MCB with a C tripping curve and a 32 A rated current. Three things besides the pole count define a breaker of this kind: the curve, the rated current and the breaking capacity printed on the front. Legrand catalogs DX3 breakers in 6000 A and 10000 A versions under separate references.

Ordering Legrand breakers: what we need

Send the Legrand catalog number printed on the device, a six-digit reference, where it is legible. Otherwise give the number of poles, the curve, the rated current, the breaking capacity and the voltage. Mention any auxiliary contact or residual current add-on module fitted beside the breaker, and the board type.

Facts checked against Legrand's published corporate information, October 2026.

FAQ

Questions about the Legrand 409799 DX3 4-Pole 50 A C-Curve MCB 25 kA

Answers from our engineering team on installation, compatibility and integration.

01What is 409799?
It is a Legrand DX3 four-pole thermal-magnetic miniature circuit breaker rated 50 A, curve C, with 25 kA breaking capacity at 400 V and a 1.5-module-per-pole body.
02What is the instantaneous trip range of 409799?
A C curve trips magnetically between 5 and 10 times the rated current, so for 50 A the band is 250 to 500 A. The data sheet gives the exact tolerance for the family.
03What breaking capacity does 409799 have at 400 V?
The Icu is 25 kA at 400 V and 50 kA at 230 V under IEC 60947-2, with a service breaking capacity Ics of 75 % of Icu according to the data sheet.
04Which cable sizes fit the 409799 terminals?
The terminals take 1.5 to 35 mm² flexible and 1.5 to 50 mm² rigid copper cable, with a 17 mm strip length and a 3 Nm tightening torque.
05Can 409799 be locked or sealed?
Yes. The data sheet describes sealing in the open or closed position and a 5 mm padlock lock-out with the matching accessory for the open position.