Brand:

Legrand 420003 DPX3 160 MCCB 3P 63 A 16 kA Thermal-Magnetic

Description

420003: Legrand DPX3 160 thermal-magnetic MCCB, 3P 63 A, what the reference means

The Legrand 420003 is a three-pole moulded case circuit breaker from the DPX3 160 family, fitted with a thermal-magnetic release and rated for 63 A. Moulded case breakers sit between the modular DX3 miniature devices and the large air breakers: they carry feeders, motor starter groups and sub-distribution boards in the range from a few tens of amperes to several hundred.

The reference follows the logic of the family sheet. The 4 200 xx block covers the 16 kA versions of the 3P breaker, one reference for each of the eight current ratings from 16 A to 160 A, and 420003 is the 63 A position in that block. The 4P versions of the same ratings and the higher 25 kA, 36 kA and 50 kA families use their own blocks, so a single digit changes the breaking capacity or the pole count.

Seven Star LLC supplies the 420003 in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer. If you only have the old drawing number or the breaker nameplate, send the photo and we match it before quoting.

Technical specifications of 420003

Parameter Specification
Manufacturer / part number Legrand / 420003
Range DPX3 160, thermal-magnetic MCCB
Poles 3P
Rated current 63 A
Breaking capacity Icu 16 kA at 400 V, 50 Hz (catalogue page); the datasheet table lists 16 kA at 415 V~
Rated operational voltage Ue 220 – 690 V (690 V maximum)
Rated insulation voltage Ui 800 V
Rated impulse withstand Uimp 8 kV
Thermal release Adjustable 0.8 to 1.0 x In (50.4 – 63 A)
Magnetic release Fixed, 10 x In with 400 A minimum for In up to 40 A (630 A for this rating)
Utilisation category A, suitable for isolation
Electrical endurance 8,000 cycles at In; 10,000 cycles at 0.5 x In
Pole pitch 27 mm
Operating temperature -25 °C to +70 °C
Degree of protection IP30
Construction Fixed, front screw connection, wing knob
Terminals supplied Cage, 70 mm² flexible / 95 mm² rigid maximum
Auxiliary options Shunt and undervoltage releases, auxiliary contacts, rotary handle, motor operator

How the thermal-magnetic release of 420003 protects the circuit

The thermal element is a bimetal that bends as the conductor current heats it. Because the heating follows the square of the current, a modest overload is tolerated for a long time while a heavy overload trips quickly, which matches the heating curve of cables and motor windings. On the 420003 the thermal threshold is set by hand between 0.8 and 1.0 times the rated current, so a 63 A frame can be tuned down towards 50 A when the cable or the load does not need the full rating.

The magnetic element reacts to short-circuit current with no intentional delay. For this family the datasheet gives a fixed instantaneous setting of 10 times In, with a floor of 400 A on the smaller ratings. For the 63 A device that means a trip level of 630 A, which a feeder with a healthy prospective fault current will reach easily. There is no adjustable magnetic dial, so coordination with downstream breakers depends on the downstream device ratings and the let-through curves in the family sheet.

Where 420003 fits in a DPX3 160 board and related parts

Within the 63 A position the family offers the 3P and 4P versions at four breaking classes. The reference pattern from the sheet is shown below for orientation; always confirm the exact reference before ordering.

Version at 63 A Reference
3P, 16 kA 420003 (this device)
4P, 16 kA 420013
3P, 25 kA 420043
3P, 36 kA 420083
3P, 50 kA 420123

Upstream you will usually find a DPX3 250 or DPX3 630 incomer, and downstream DX3 miniature breakers or contactor-based motor feeders. Siblings in the same lane such as 420207 and 420239 (DPX3 250 thermal-magnetic) cover larger frames, while 420719 and 420720 are magnetic-only devices. The DPX3 160 sheet also lists trip-free switches of the DPX3-I type in the same housing where only isolation is required.

Selection and ordering checklist for 420003

  • Confirm the load current and cable size, then compare with the 63 A rating and the adjustable 50.4 – 63 A thermal range.
  • Check the prospective short-circuit current at the board against 16 kA at 400 V. If it is higher, a 25 kA, 36 kA or 50 kA version is needed.
  • Decide 3P or 4P. A neutral conductor with harmonic load may call for the 4P version, which protects the neutral at 100 percent of the phase rating.
  • Verify the ambient temperature. The datasheet derating table limits the long-time setting as the cabinet heats up toward 70 °C.
  • Choose the connection: cage terminals are supplied, spreaders, lugs or bar connections are accessories.
  • List the accessories before ordering: shunt trip, undervoltage release, auxiliary contacts, rotary handle or motor operator.

Installation, commissioning and maintenance of 420003

Fix the breaker on its DIN rail or plate according to the instruction sheet and keep the insulating phase shields in place; they are part of the delivery. The datasheet recommends keeping the first conductor fixing point close to the breaker, with a maximum distance of 400 mm for 16 kA, so that short-circuit forces do not stress the terminals. Tighten the terminals with a calibrated tool and recheck them after the first load cycle, since copper creeps under heat.

During commissioning set the thermal dial for the actual cable and load, operate the handle a few times to confirm free movement, and record the setting on the board schedule. For maintenance use a thermal camera under load to look for a hot terminal, and exercise the handle at the intervals set by your asset plan. Power loss at 63 A with cage terminals is about 5.5 W per pole according to the sheet, which is useful when sizing cabinet ventilation.

Typical applications in Oman and the GCC

A 63 A moulded case breaker is common in the sub-distribution boards of process buildings, pump stations, workshop blocks, camp facilities and utility rooms across Oman and the Gulf. In desalination and water treatment plants it feeds pump starter groups and dosing skids; in oil and gas facilities it often protects lighting and small-power boards, air-conditioning units and instrument cabinets. Where the cabinet sits in a hot, dusty room the temperature derating table and a regular terminal check matter more than the nameplate rating alone.

Because the 420003 is an IP30 device meant for installation inside an enclosure, plan for the enclosure rating that the site needs. Coastal humidity and fine dust call for sealed or ventilated cabinets with filters, and for conformal protection of the busbar joints where the project requires it.

Information to send with an RFQ for 420003

  • Part number 420003 and the quantity.
  • Voltage, frequency and earthing system of the board.
  • Prospective short-circuit current at the installation point.
  • Required accessories: releases, contacts, handle, motor operator.
  • Any spare or replacement context, such as the nameplate photo of the breaker being replaced.
  • Delivery location in Oman or the GCC and the required date.

Documents and quotation

A datasheet for this DPX3 160 family is attached on this page, covering the range, characteristics, installation rules and curves. Check the Legrand reference printed on the breaker against the 420003 reference before ordering.

Send the part number and the quantity to Seven Star LLC and we will confirm availability, lead time and any accessories for your RFQ.

Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Legrand is a French maker of electrical and digital building infrastructure, headquartered in Limoges. Its roots lie in a nineteenth-century porcelain workshop in Limoges, and it grew into one of the largest makers of wiring devices, circuit protection, cable management and data centre products. Legrand is listed on Euronext Paris and sells under brands including Legrand, Bticino and Cablofil.

Seven Star LLC, an independent supplier in Muscat, lists Legrand circuit breakers for electrical contractors and panel builders in Oman and the GCC, at present a DX3 4-pole miniature circuit breaker rated C32.

Legrand company profile

Headquarters Limoges, France
Listing Euronext Paris
Brands Legrand, Bticino, Cablofil, Zucchini
Product families DX3 miniature circuit breakers and RCDs, wiring devices, cable trays, busbar trunking, UPS

Legrand DX3 circuit breakers

DX3 is the Legrand family of modular protection devices for DIN rail mounting. The item on our site is a 4-pole MCB with a C tripping curve and a 32 A rated current. Three things besides the pole count define a breaker of this kind: the curve, the rated current and the breaking capacity printed on the front. Legrand catalogs DX3 breakers in 6000 A and 10000 A versions under separate references.

Ordering Legrand breakers: what we need

Send the Legrand catalog number printed on the device, a six-digit reference, where it is legible. Otherwise give the number of poles, the curve, the rated current, the breaking capacity and the voltage. Mention any auxiliary contact or residual current add-on module fitted beside the breaker, and the board type.

Facts checked against Legrand's published corporate information, October 2026.

FAQ

Questions about the Legrand 420003 DPX3 160 MCCB 3P 63 A 16 kA

Answers from our engineering team on installation, compatibility and integration.

01What is Legrand 420003?
It is a DPX3 160 thermal-magnetic moulded case circuit breaker with three poles, a 63 A rating and a breaking capacity of 16 kA at 400 V. It is a fixed, front-connected device with a wing knob and IP30 protection.
02Can the overload setting of 420003 be adjusted?
Yes. The thermal release is manually adjustable from 0.8 to 1.0 of the rated current, which for this 63 A frame means about 50.4 A to 63 A. The magnetic release is fixed at 10 times In, with a 400 A minimum for ratings up to 40 A.
03What conductors fit the standard terminals of 420003?
The breaker ships with cage terminals for flexible cable up to 70 mm² or rigid cable up to 95 mm². Spreaders, lugs and rear terminals are listed as accessory connection options in the range documentation.
04Is 420003 suitable for isolation?
The DPX3 160 datasheet lists the thermal-magnetic breakers as suitable for isolation, utilisation category A. Confirm the isolation function against your project specification and the wiring rules for the board.
05Where is 420003 normally mounted?
It mounts on a DIN rail or on plates inside XL3 type cabinets and enclosures. Check the available depth, the phase barriers and the busbar spacing before you order the board.