- Automation & ControlView all 1,652 products
- AC Drives
- Industrial Communications
- PLC & I/O Cards
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- Industrial Computers
- Servo Drives
- Isolator & Barrier
- Motor Soft Starters
- HMI Displays
- Pneumatic Cylinders
- Automation Software
- Machine Vision
- Robotics
Brand: Bender
Bender isoUG425-D4-4 Earth Fault Monitor for 12-120 V DC
Description
Earth fault detection for low-voltage DC control and battery supplies
The Bender isoUG425-D4-4 is an ISOMETER for earth fault detection in unearthed DC systems (IT systems) with system voltages of 12 to 120 V. It monitors the asymmetrical insulation resistance RF between the system and earth, measures the system voltage Un (true RMS and DC) with under- and overvoltage detection, and measures the DC residual voltages between L+ and earth and between L- and earth. The maximum permissible system leakage capacitance is 50 uF. The article number of the push-wire terminal version is B71036320.
An important detail from the datasheet: the isoUG425 is not an insulation monitoring device in the sense of IEC 61557-8. It uses a passive measuring method that evaluates the offset voltage produced by a fault on one conductor. Faults that are equally large on both the positive and the negative conductor to earth (symmetrical faults) are not detected. This is why it suits battery-backed DC supplies where a single-conductor fault is the expected case.
Technical specification
| Parameter | Specification |
|---|---|
| Type / article number | isoUG425-D4-4, B71036320 (push-wire terminals) |
| Monitored system | Unearthed DC, Un 12 to 120 V (tolerance +20 %); permissible Ce max. 50 uF; internal resistance min. 115 kOhm |
| Supply voltage Us | AC 100 to 240 V, 47 to 63 Hz; DC 24 to 240 V; tolerance -30 % / +15 %; power consumption max. 3 W / 9 VA; can be taken from the DC system if at least 24 V |
| Response values | Ran1 1 to 100 kOhm (50 kOhm default); Ran2 1 to 95 kOhm (25 kOhm default); uncertainty plus/minus 15 %, at least plus/minus 2 kOhm; hysteresis 25 %, at least 1 kOhm |
| Voltage monitoring | Undervoltage 8 to 143 V and overvoltage 8.1 to 144 V (both off by default); uncertainty plus/minus 5 %, at least plus/minus 0.5 V; hysteresis 5 % |
| Time response | Response time max. 1 s at RF = 0.5 x Ran and Ce = 1 uF; start-up delay 0 to 10 s; response delay 0 to 99 s; delay on release 0 to 99 s |
| Display | Multi-functional LC display (not illuminated); insulation range 1 kOhm to 1 MOhm; system voltage 0 to 150 V; password off or 0 to 999; fault memory on/off |
| Outputs | 2 x 1 N/O contacts (common terminal 11), N/C or N/O selectable; 10 000 cycles; AC-12 230 V 5 A, AC-14 230 V 2 A, DC-12 24 V 1 A, 110 V 0.2 A, 220 V 0.1 A |
| Interface | RS-485 galvanically isolated: BMS, Modbus RTU and isoData (115.2 kBd); up to 1200 m at 9.6 kBd; 120 Ohm terminating resistor; address 3 to 90 (factory 3) |
| Insulation coordination | Rated voltage 400 V; overvoltage category III; rated impulse voltage 6 kV (measuring circuit) and 4 kV (other circuits); pollution degree 3 |
| Environment | Operating temperature -40 C to +70 C; transport -40 C to +85 C; climatic class 3K22; mechanical class 3M11; EMC per IEC 61326-2-4 |
| Connection | Push-wire terminals AWG 24 to 14, rigid 0.2 to 2.5 mm2, stripping 10 mm, opening force 50 N |
| Enclosure | Polycarbonate, 36 mm wide; IP30 internal, IP20 terminals; DIN rail IEC 60715 or 2 x M4 screws; mount vertically with cooling slots ventilated |
| Weight | max. 150 g |
| Standard noted | Developed in compliance with DIN EN 50155:2018-05; EU declaration of conformity available from Bender |
Passive measurement and what it means for the application
The isoUG425 measures from a minimum system voltage onwards. Detected faults can be assigned to the alarm relays through the menu, so that K1 may indicate a fault on L+ and K2 on L-, or both relays can be used as pre-warning and alarm. Voltage limits can alarm when the DC system voltage leaves its window. Because it only sees asymmetry, a system with equal leakage on both poles will look healthy; where such symmetrical faults must be detected, an ISOMETER per IEC 61557-8 such as the IR425-D4-2 or iso685-D-P on this site is the right choice. The device can be parameterised from the front or through BMS or Modbus RTU, for example with a COM465IP gateway.
Installation notes
- Connect E and KE separately to PE with the same cross section as the supply terminals A1 and A2.
- Protect the supply with 6 A fuses (5 A for UL and CSA applications); use 60/75 C copper conductors for UL.
- If supplied from the DC system itself, both lines must be fused; below 24 V DC use a separate supply.
- Mount vertically so that the cooling slots are ventilated; an external test/reset button can be connected at T/R.
- The alarm must be audible or visible when the device is inside a control cabinet.
GCC use cases
Typical applications are 24 V, 48 V and 110 V DC control and battery supplies in substations, gas compressor stations and telecom shelters, where a first earth fault must be signalled without tripping. See the relays category for other Bender devices.
Selection and installation notes
Insulation and residual current monitoring devices are selected from the system type (IT, TN or TT), the system voltage, the leakage capacitance and the alarm levels needed. Connect the device to the system and to earth as the manual shows, set the response values from the system design, check the coupling or measuring current transformer and its wiring, and test the alarm and relay outputs after commissioning. Do not do an insulation test of the plant with the monitor connected unless the manual allows it.
Information needed for a quotation
Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.
Documents and supply information
The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.
Datasheets & Documents
- Datasheet Bender isoUG425 datasheet (08.2024) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Bender is a German family company specialising in electrical safety monitoring, based in Grünberg, Hesse. Walther Bender patented the insulation monitoring device he called the ISOMETER in 1942 and registered the company in Grünberg in 1946. Bender employs about 1,100 people across subsidiaries on four continents.
Seven Star LLC is an independent supplier in Muscat. We list Bender monitoring devices for power, oil and gas, marine, hospital and industrial installations in Oman and the GCC.
Bender company profile
| Founded | 1946, Grünberg, Germany |
|---|---|
| Founder | Walther Bender |
| Ownership | Bender family |
| Key invention | ISOMETER insulation monitor, patented 1942 |
| Product families | ISOMETER insulation monitors such as iso685 and IR425, EDS insulation fault locators, RCMS residual current monitors, NGRM neutral grounding resistor monitors |
Milestones
- 1942: The ISOMETER is patented.
- 1946: The company is registered in Grünberg.
- 2021: Bender marks 75 years.
Bender product series
Insulation monitors include the IR425-D4-2 for systems up to 300 V, the iso685-D-P for 690 V AC systems, the isoUG425-D4-4 earth fault monitor for 12-120 V DC and the IRDH275BM-7 for medium voltage networks. The EDS440-L-4 ISOSCAN locates the faulty feeder once an insulation fault is detected.
Residual current monitors include the RCMS460-D-2 twelve-channel monitor and the RCMA420-D-2 AC/DC monitor for 10 to 500 mA. The NGRM700 supervises neutral grounding resistors, the VMD460-NA-D-2 is a network and system protection relay, and the MK2430-11 COMTRAXX is a remote alarm indicator with twelve inputs.
Where Bender devices are used
IT power systems in plants, ships, hospitals and data centres, DC supplies and battery systems, generator and solar connections to the grid, and earthing systems with neutral grounding resistors.
Bender products we list
Ordering Bender devices: what we need
Send the Bender type and article number, system type (IT, TN or TT), nominal voltage and frequency, the supply voltage of the device and the alarm and communication outputs needed.
Facts checked against Bender's own history and 75th anniversary release, October 2026.
Browse Bender products by category: Switchgear, Enclosures & Distribution.
FAQ
Questions about the Bender isoUG425-D4-4 Earth Fault Monitor for 12-120
Answers from our engineering team on installation, compatibility and integration.
01What does the isoUG425 detect?
Asymmetrical insulation faults in unearthed DC systems of 12 to 120 V; symmetrical faults on both conductors are not detected.
02Is it an IEC 61557-8 insulation monitor?
No. The datasheet states that the isoUG425 is not an insulation monitoring device in the sense of IEC 61557-8.
03What supply does it need?
AC 100 to 240 V (47 to 63 Hz) or DC 24 to 240 V; it can be fed from the DC system if that is at least 24 V.
04What is the article number?
B71036320 for isoUG425-D4-4 with push-wire terminals.
05Does Seven Star LLC manufacture it?
No, Seven Star LLC is an independent supplier in Muscat; send us your DC system voltage for a quotation.


















Reviews
There are no reviews yet.