Brand:

ABB ACH580-04-585A-4 HVAC Drive Module 315 kW 585 A

Description

A 315 kW HVAC drive module for cabinet builders

ACH580-04-585A-4 is the 315 kW, 585 A step of ABB’s ACH580-04 drive-module range. Unlike the wall-mounted ACH580-01, which stops at 250 kW, the -04 modules cover 250 to 500 kW and are meant for system integrators, cabinet builders and OEMs who want to design their own enclosure around the drive. This type sits on frame R10 and carries the same HVAC control program as the smaller sizes, so BACnet MS/TP, Modbus RTU and N2 are available without an adapter.

ABB names fans, pumps, compressors, air handling units and chillers as the target applications for its HVAC drives, and notes that the ACH580-04 comes with a choke for harmonic mitigation. If a project needs a ready-built panel instead, the catalogue lists the same 585 A rating as a cabinet-built ACH580-07 drive. Smaller wall-mounted sizes are in the AC drives category and the sister platform is on the ABB ACS580 overview.

Technical specifications

Parameter Specification
Type designation ACH580-04-585A-4
Series / construction ACH580 / 04 = drive module for cabinet installation
Supply voltage 3-phase, 380 to 480 V (code 4)
Frame size R10
Nominal rating, 380-415 V 315 kW, 585 A
Light-duty use, 380-415 V 575 A, 315 kW
Light-duty use, 440-480 V 573 A, 450 hp
Power range of the ACH580-04 line 250 to 500 kW
Degree of protection IP00 (UL Type Open) or IP20 (UL Type 1); +B051 adds IP20 finger shrouds
Dimensions (H x W x D) 1462 x 350 x 529 mm
Weight 162 kg
Operation temperature -15 to +55 degrees C
EMC Category C3 with the standard pre-configured built-in filter
Harmonic mitigation Built-in choke
Neighbouring types ACH580-04-505A-4 (250 kW) below; ACH580-04-650A-4 (355 kW) above

Ratings and what they mean in practice

On a 380 to 415 V network the catalogue gives 585 A for 315 kW in nominal use and 575 A for 315 kW in light-duty use, where ABB allows 110% for one minute in ten (about 633 A, a derived figure). On a 440 to 480 V network the light-duty entry is 573 A for 450 hp. ABB states that frames R10 and R11 comply with EMC category C3 with the pre-configured internal filter, so check the first-environment rules if the drive is installed in a residential or commercial building without further filtering.

The ratings table covers the neighbouring modules too: 505 A / 250 kW below and 650 A / 355 kW above, followed by R11 modules at 725, 820 and 880 A. Frame R10 is therefore the entry to the large-module range, and the 585 A type is its middle step.

Mounting and enclosure notes

The module measures 1462 mm in height, 350 mm in width and 529 mm in depth and weighs 162 kg, so lifting gear and a rigid cabinet base are needed. The module is supplied as IP00 / UL Type Open and, with the +B051 option, receives IP20 finger shrouds; the catalogue lists IP00 or IP20 as the degree of protection of the whole ACH580-04 line. The operating temperature range for -04 modules is -15 to +55 degrees C, five degrees higher than the wall-mounted drives.

Cabinet design drives the rest of the project: heat removal, input protection, an output filter where the motor cable is long, and a control panel mounting solution. The catalogue offers the DPMP-05 outdoor mounting kit for ACH580-04 and ACH580-34 panels, and a control panel is part of the delivery.

Ordering code and communication

Read ACH580-04-585A-4 as series ACH580, construction 04 (module), rating 585A and voltage code 4 for 380 to 480 V. Options are added with plus codes: +B051 for finger shrouds, +L501 for CMOD-01, +L523 for CMOD-02 and +L512 for CHDI-01 extension modules, and +K codes for fieldbus adapters such as +K465 for BACnet/IP with FBIP-21, +K491 for Modbus TCP with FMBT-21 or +K492 for PROFINET IO with FPNO-21.

Documents and quotation

All values come from ABB’s ACH580 HVAC catalogue (3AUA0000186691, revision F, dated 9.14.2019), linked on this page. Seven Star LLC supplies the ACH580-04-585A-4 on request from Muscat; send the motor nameplate, supply voltage, cabinet concept and network protocol with your RFQ, and the quotation states availability and lead time.

Confirm before ordering: that this catalogue revision still matches ABB’s current data for the type, the plus options, the cooling and fuse concept for your cabinet, the EMC category needed on site and the motor current at your voltage.

Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

Frequently Asked Questions

What is the nominal rating of the ACH580-04-585A-4?
ABB lists 315 kW and 585 A in nominal use on a 380 to 415 V supply, with 575 A light duty for 315 kW and 573 A for 450 hp at 440 to 480 V.
Which frame size and weight does the ACH580-04-585A-4 have?
It is frame R10, 1462 mm high, 350 mm wide and 529 mm deep, with a weight of 162 kg.
What degree of protection does the ACH580-04 module have?
The catalogue lists IP00 (UL Type Open) or IP20 (UL Type 1) for the ACH580-04 line; the +B051 option adds IP20 finger shrouds for modules.
What is the permitted ambient temperature of the ACH580-04 line?
ABB specifies operation from -15 to +55 degrees C for ACH580-04, with ratings stated at +40 degrees C.
Which EMC category do frames R10 and R11 meet?
ABB states that R10 and R11 comply with category C3 with the standard pre-configured built-in filter.