- AC Drives
- Industrial Communications
- PLC & I/O Cards
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- Safety Switches & Guard Locking
- CCTV & Security
- Encoders
- Industrial Computers
- HMI Displays
- Motor Soft Starters
- Isolator & Barrier
- Pneumatic Cylinders
- Servo Drives
- Automation Software
- Robotics
- Machine Vision
Brand: GESTRA
GESTRA LRR 1-50 Conductivity Controller for Blowdown
Description
A conductivity controller for continuous boiler blowdown (TDS control)
The GESTRA LRR 1-50 is a conductivity controller and limit switch that works with LRG 12-2, LRG 16-4, LRG 16-9, LRG 17-1 and LRG 19-1 conductivity electrodes, and is used in steam boilers, pressurised hot-water installations and condensate or feedwater tanks. It reads the electrical conductivity of the boiler water, which reflects the total dissolved solids (TDS) concentration, and opens or closes a continuous blowdown valve to keep TDS within the boiler maker limit. When the MAX limit is reached, a MAX alarm contact switches. Its sibling LRR 1-51 takes a 4-20 mA signal from LRGT 1.-.. conductivity transmitters instead of an electrode.
Excess TDS causes foaming and priming and carries solids into steam lines and superheaters, so continuous top blowdown needs a controller that regulates the valve from the measured conductivity, together with fresh make-up water.
Technical specifications
| Parameter | Specification |
|---|---|
| Types | LRR 1-50 (electrode input, with MAX alarm); LRR 1-51 (4-20 mA transmitter input) |
| Function | Two-position controller: valve motored to OPEN at the setpoint, back to OPERATING below the setpoint minus hysteresis; valve closes when the boiler is shut down |
| Supply voltage; power | 24 V DC +/-20 %; 4 W; external 0.5 A semi-delay fuse |
| Measuring range | 1 to 10,000 uS/cm at 25 C, or 1 to 5,000 ppm at 25 C (1 uS/cm = 0.5 ppm) |
| Electrode input (LRR 1-50) | LRG 1.-.. with cell constant 1 cm-1 (3 poles with screen) or LRG 16-9 with cell constant 0.5 cm-1 and integral Pt 100 (5 poles with screen) |
| Measuring voltage | 0.8 Vss, pulse duty factor 0.5, frequency 20-10,000 Hz |
| Correction; compensation | Correction factor CF 0.05 to 5.000 in steps of 0.001; calibration function CAL; linear temperature compensation to 25 C with an adjustable coefficient (%/C) when LRG 16-9 is used |
| Transmitter input (LRR 1-51) | 4-20 mA for LRGT 16-1, 16-2, 16-3, 16-4, 17-1 and 17-3; measuring range start 0.0 to 100.0 uS/cm and end 20.0 to 12,000 uS/cm, adjustable |
| Outputs | 2 volt-free changeover contacts for valve OPEN / OPERATING / CLOSED and 1 for MAX alarm, 8 A at 250 V AC / 30 V DC, cos phi = 1; analogue 4-20 mA (actual value or manipulated variable Y), max. load 500 ohm |
| Reset hysteresis | MAX limit: -3 % of the adjusted limit, fixed |
| Display and operation | Four-digit green seven-segment LED; red MAX LED; 2 amber valve LEDs; rotary button with Test; 4-pole code switch; password protection |
| Protection; housing | Housing IP 40, terminal strip IP 20, IP 65 with panel adaptor (stock code 441553); polycarbonate; clip for TH 35 rail |
| Ambient; weight | 0 to 55 C at power-on, -10 to 55 C in operation; approx. 0.2 kg |
Automatic purging can rinse the blowdown valve at set intervals so that it does not stick. Faults in the electrode, transmitter, wiring or settings are shown as error codes, a MAX alarm is raised and the valve is driven to its OPERATING position. As a limit switch the controller does not interlock automatically; if the installation requires an interlock, it must be provided in the follow-up circuit and meet EN 50156. The equipment must not be used in potentially explosive areas.
Choosing electrode, transmitter and cable
For a simple installation use an LRG electrode with the LRR 1-50; use LRG 16-9 where temperature compensation to 25 C is wanted. Where the boiler already has an LRGT conductivity transmitter, select the LRR 1-51. Keep the cable between electrode and controller to 30 m, or 10 m for conductivities from 1 to 10 uS/cm, and protect non-UV-resistant control cable with a duct outdoors. The controller works with the continuous blowdown valve of the boiler, whose operating position sets the blowdown rate.
A related conductivity sensor already listed is the GESTRA LRGT 16-1 conductivity transmitter; more liquid analysis products are under liquid analysis sensors.
Installing the LRR 1-50 in the boiler control panel
Mount the controller on the TH 35 rail inside a closed control cabinet, away from contactors and frequency converters that switch heavy loads, and route the electrode cable separately from mains and motor wiring. The screened electrode cable should have its screen terminated as shown in the GESTRA wiring diagram and kept continuous along the run. Before the first power-up, check that the 24 V DC supply is within tolerance and that the external semi-delay fuse is fitted, then confirm that the volt-free contacts are wired to the correct coils or inputs of the blowdown valve actuator and the alarm circuit.
Commissioning and calibration on site
Commissioning is best done with the boiler at normal working pressure and with a reliable reference measurement of the boiler water. Take a cooled sample, measure its conductivity with a calibrated laboratory or handheld instrument, and use the CAL function or correction factor so that the displayed value matches the reference. Then enter the setpoint, hysteresis and MAX limit agreed with the boiler maker and the water treatment specialist, and set the purging interval for the blowdown valve. Run the valve through OPEN, OPERATING and CLOSED from the controller and confirm that the actuator follows each command and that the MAX alarm reaches the control room or the boiler alarm panel.
Routine checks during operation
Compare the displayed conductivity with a manual sample at regular intervals set by the site water treatment programme; a drift between the two usually points to fouling or scale on the electrode, which should be inspected and cleaned during a planned boiler stop. Review any error codes, look at how often the MAX alarm has been raised, and check that the blowdown valve still moves freely after periods of low demand. Record setpoint changes so that operators and the water treatment contractor work from the same values.
Operating conditions in Oman and GCC boiler houses
Boiler houses in Oman and across the GCC can become very hot in summer, especially where the panel sits close to the boiler front or in a roof plant room without good ventilation. Because the controller is rated for an ambient of up to 55 °C in operation, place the cabinet where it is shaded and ventilated, and consider cabinet cooling where the room temperature approaches that limit. Fine dust and humid coastal air can enter enclosures that are left open, so keep cabinet doors closed and cable entries sealed. Make-up water from desalination or brackish sources varies in quality, so the setpoint and blowdown rate should be reviewed whenever the feedwater source or treatment chemistry changes.
Documents and quotation
The attached GESTRA data sheet 819211 covers LRR 1-50 and LRR 1-51 with a glossary on blowdown, temperature compensation and wiring. Send the electrode or transmitter model, the boiler TDS limit and the valve actuator type for a quotation, and confirm the variant before ordering.
Datasheets & Documents
- Datasheet GESTRA LRR 1-50, LRR 1-51 conductivity controller data sheet 819211-06 Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
GESTRA is the German steam and condensate specialist behind the UNA ball float steam traps, the MPA blowdown valves and a long line of boiler level and conductivity controls. It was founded in Bremen in 1902 by Gustav F. Gerdts, and has been part of Spirax Sarco since 2017.
Seven Star LLC is an independent supplier in Muscat. We list GESTRA steam traps, blowdown valves and boiler control equipment, and supply GESTRA parts and spares to boiler houses and process plants in Oman and the GCC.
GESTRA company profile
| Established | 29 October 1902, Bremen, Germany, by Gustav Friedrich Gerdts; renamed Gustav F. Gerdts KG in 1907 |
|---|---|
| Ownership history | Became a stock corporation (GESTRA AG) in 1987, was taken over by Flowserve in 2002, and has been part of the Spirax Sarco group since 2017 |
| Product families | Steam traps, non-return and check valves, boiler blowdown valves, control valves, and boiler control electronics for level, conductivity and temperature |
| Applications | Steam boilers, steam distribution and condensate return in process plants, power stations, hospitals, food and textile plants |
Milestones
- 1902: Gustav Friedrich Gerdts founds the company in Bremen on 29 October.
- 1907: The company is renamed Gustav F. Gerdts KG.
- 1987: It becomes a stock corporation, GESTRA AG.
- 2002: Flowserve takes over GESTRA.
- 2017: GESTRA becomes part of the Spirax Sarco group.
GESTRA products we list
| Series | Type | What it does |
|---|---|---|
| UNA 45, UNA 16, UNA 38 | Ball float steam traps | Continuous condensate discharge from heat exchangers and process equipment; the UNA 38 is the high-pressure version (PN 100) |
| BK 45 | Bimetallic steam trap | Robust trap for steam main drainage and tracing, resistant to water hammer |
| MK 45, TK 23, SMK 22-81 | Thermostatic steam traps | Air venting and condensate discharge; the SMK 22-81 is the sanitary version for clean steam |
| MPA 46 | Rapid-action blowdown valve | Short, intermittent bottom blowdown that removes sludge from the boiler |
| NRS 1-54, NRR 2-50, NRR 2-60, NRGT 26-2 | Boiler level controls | Water level limiting, feedwater control and continuous level measurement |
| LRGT 16-1, LRR 1-50 | Conductivity measurement and control | Keeps boiler water conductivity in range through continuous blowdown |
| TRS 5-50 | Safety temperature limiter | SIL 3 temperature limiting for boilers and hot water systems |
The type of steam trap follows the duty. Ball float traps discharge condensate as soon as it forms, which suits heat exchangers with changing loads. Thermostatic and bimetallic traps hold condensate back slightly and suit steam mains, tracing and air venting. On the boiler itself, GESTRA level and conductivity electronics work as a system: electrodes or transmitters in the boiler, controllers in the panel, and the feedwater and blowdown valves they drive.
Where GESTRA products are used
In Oman and the GCC, GESTRA equipment is used in boiler houses of refineries, petrochemical and fertiliser plants, power and desalination stations, food and beverage plants, laundries, hotels and hospitals.
Ordering GESTRA parts: what we need
Send the type designation, pressure rating (PN) and connection size (DN), the end connection (flanged, screwed or socket weld), the operating pressure and condensate load for steam traps, and the supply voltage and bus type (CAN bus, 4-20 mA) for control equipment. For electrodes, add the insertion length.
Facts checked against GESTRA company history and Bremen city records, October 2026.
Browse GESTRA products by category: Liquid Analysis Sensors.
Related products
Frequently Asked Questions
Conductivity (TDS) in boiler water, by opening or closing a continuous blowdown valve and raising a MAX alarm at the limit.
LRR 1-50 connects a conductivity electrode; LRR 1-51 connects a 4-20 mA LRGT conductivity transmitter.
1 to 10,000 uS/cm at 25 C, or 1 to 5,000 ppm at 25 C.
Yes, with the LRG 16-9 electrode (integral Pt 100) the reading is referenced to 25 C using an adjustable linear temperature coefficient.
24 V DC +/-20 % at 4 W with an external 0.5 A semi-delay fuse.

Reviews
There are no reviews yet.