Brand:

Rotork CVL-1500 Electric Linear Actuator 6,672 N

Description

Rotork CVL-1500 in one paragraph

The Rotork CVL-1500 gives a control valve 1,500 lbf (6,672 N) of electric thrust. It is the highest-force version of the 24 kg, 2 in stroke CVA linear body, and it is what you specify when a 1 to 6 in globe or cage valve has high packing friction, high pressure drop or a large unbalanced plug and a 1,000 lbf actuator would run near its limit.

Performance numbers for CVL-1500

Rated thrust 1,500 lbf / 6,672 N
Minimum settable thrust (40 percent) 600 lbf / 2,669 N
Maximum stroke 2 in / 50.8 mm
Stroke speed 0.1 in/s / 2.54 mm/s
Full-stroke time 20 s
Unit weight Approximately 24 kg (53 lb)
Valve flange reference MSS SP-102 FA07 / ISO 5210 F07
Thrust measurement accuracy Plus or minus 5 percent of rated force
Reserve powerpack charge 100 s
Design life 12 million 1 percent strokes at 75 percent load / 6 million 10 percent strokes at full load
Supply options 100 to 240 VAC 50/60 Hz or 24 VDC
Control interface 4 to 20 mA command and feedback; HART, Pakscan, Profibus, Foundation Fieldbus, Modbus options

Rotork also quotes ability to resist back-drive of 125 percent of rated thrust, which for the Rotork CVL-1500 equals 8,340 N, without moving; the optional lock mechanism protects up to 300 percent.

Energy and heat: CVL-1500 power figures

At 240 VAC the CVL-1500 pulls 4.9 W (0.07 A) when idle, 15.0 W (0.13 A) at full speed with no load, 28.2 W (0.22 A) at half load, and 36.0 W (0.27 A) at full load. Peak charging power for the capacitor pack is 43 W (0.30 A). Its 0.5 Hz, 2 percent cycling test at full load averages 38 W (0.27 A), which is the highest of the CVL family below the CVL-5000, as expected from more force per stroke. Because motor heat is so low, the actuator can modulate continuously without a derated duty cycle.

Is CVL-1500 right for the job? A short comparison

How CVL-1500 differs from other CVA variants. Compared with CVL-1000 you gain 2,224 N more thrust at identical size and speed. Compared with CVL-500 you gain 4,448 N and 12.7 mm of stroke but give up speed (20 s instead of 6 s). Compared with CVL-5000 you lose 15,569 N of force and 63.5 mm of stroke but save about 27 to 29 kg of mass. The two quarter-turn units, CVQ-1200 and CVQ-2400, are not substitutes because they deliver torque.

Installing CVL-1500: the sequence that works

  • Check the nameplate weight, around 24 kg, and use proper lifting; the unit is top-heavy once on the valve.
  • Machine the coupling to the stem so the actuator output shaft and stem are concentric; misalignment increases wear.
  • Fit the four M8 screws (M8 on a 70 mm PCD) and tighten to 14 Nm (9.5 lbf.ft).
  • Wire power and 4 to 20 mA through the four M25 entries; the terminal compartment stays sealed even with the cover off thanks to the double seal.
  • Pair a phone or PC over Bluetooth and run quick setup; then set action on loss of signal, deadband and input characterisation for non-linear trims.

Fieldbus and certification choices for CVL-1500

The standard card handles 4 to 20 mA. A network option can be fitted when the project requires HART, Foundation Fieldbus, Profibus, Modbus or Rotork Pakscan; the extra current drawn is small, between 10 mA (HART, Foundation Fieldbus) and 30 mA (Pakscan, Profibus) at 24 VDC. Japanese TIIS certificates exist for CVL-1500 with 24 VDC or 100 to 240 VAC supplies, and hazardous-area ATEX, IECEx, UKEx, FM, CSA and EAC builds are listed. Ask for the certificate that matches the country and gas group of your installation.

Maintenance outlook for Rotork CVL-1500

Service work focuses on the valve, not the actuator. Compare the stored reference stroke with a fresh one; a rise in thrust at the same position suggests packing or guide wear. Keep enclosures closed, since IP68 protection is only assured when covers have not been disturbed. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Typical selection logic for the CVL-1500: first calculate the maximum stem load of the valve, adding packing friction, seat load and the pressure unbalance force; then add at least a margin so the working thrust falls between 40 and 100 percent of the 6,672 N rating, which is where thrust sensing is most meaningful. The Rotork CVL-1500 then offers the full CVA feature set: dual 12-bit encoders, selector with Run, Stop and Test positions, tri-colour LED, configurable availability relay, characterisable input for non-linear trims, and bumpless transfer.

On a typical Gulf site the CVL-1500 is often chosen for boiler and heat-recovery steam generator feed valves, produced-water injection chokes, caustic and acid transfer control, and cooling-water bypass valves, where electrical power is more dependable than a compressor. The 20 s stroke is quick enough for temperature and level, and the brushless motor tolerates hundreds of tiny corrections each hour without wear, even in the summer heat of an unshaded Omani plant yard.

Environmental limits are the same as the family: -30 to +60 C as standard, -40 to +60 C with the low-temperature option, IP66/IP68 to 7 m for 72 hours, vibration up to 1 g RMS from 10 to 1,000 Hz, shock to 5 g and under 61 dB(A) of noise at 1 m.

Documents and quotation

The datasheet attached is the Rotork CVA brochure containing the full table for CVL-1500. Please quote CVL-1500, the quantity and your supply voltage and stem dimension in the RFQ.

Delivery to Sites in Oman and the GCC

Delivery of the Rotork CVL-1500 is arranged to suit the site, whether that is a plant in Sohar or Duqm, an oilfield location in the interior, or a project elsewhere in the GCC. Tell us the delivery point, any site access or gate-pass requirements, and the person who will receive the goods. Goods are packed to protect sensitive electric actuators equipment during road or air transport, and shipping details are shared once the order is dispatched so that your stores team can plan receipt and inspection.

Other Models in the Rotork Cva Range

Seven Star LLC supplies models from the Rotork Cva range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Rotork CVQ-1200 Quarter-Turn Electric Control ActuatorElectric ActuatorsView details
Rotork CVL-1500 Electric Linear Actuator 6,672 NElectric ActuatorsYou are viewing this model
Rotork CVL-5000 Heavy-Duty Electric Linear ActuatorElectric ActuatorsView details
Rotork CVQ-2400 Quarter-Turn Electric Actuator 271 NmElectric ActuatorsView details
Rotork CVL-1000 Linear Electric Actuator 4,448 NElectric ActuatorsView details
Rotork CVL-500 Linear Electric Control Valve ActuatorElectric ActuatorsView details
Datasheets & Documents
  • PDF Datasheet Rotork CVL-1500 Electric Linear Actuator 6,672 N Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Rotork is a British flow control company best known for electric valve actuators. Jeremy Fry founded Rotork Engineering Company in Bath in 1957, the year its first actuator, the 100A, went on sale, and the group is still headquartered in Bath and listed on the London Stock Exchange. Today Rotork makes electric, pneumatic, hydraulic and electro-hydraulic actuators, gearboxes, precision regulators and valve positioners.

Seven Star LLC is an independent supplier listing Rotork actuators, Rotork Fairchild regulators, YTC positioners and spare parts for buyers in Oman and the GCC. Replacement units are matched from the actuator nameplate and wiring diagram number.

Rotork company profile

Origin Founded by Jeremy Fry in 1957 in Bath, England; first product the 100A valve actuator
Headquarters Brassmill Lane, Bath, United Kingdom
Ownership Rotork plc, a public company listed on the London Stock Exchange
Acquired brands Fairchild precision pneumatic controls (2011, Winston-Salem, USA), YTC valve positioners (Young Tech Co., Seoul, 2014), Mastergear gearboxes (2016)
Product families Intelligent electric actuators, control valve actuators, electro-hydraulic and fluid power actuators, gearboxes, precision regulators, positioners and network control systems

Milestones

  • 1957: Jeremy Fry founds Rotork in Bath, England; the first product is the 100A valve actuator.
  • 2011: Fairchild precision pneumatic controls (Winston-Salem, USA) is acquired.
  • 2014: YTC valve positioners (Young Tech Co., Seoul) is acquired.
  • 2016: Mastergear gearboxes is acquired.

Rotork actuators, regulators and positioners

Series Type Typical use
IQ3 Intelligent multi-turn electric actuator Gate and globe valves, penstocks and sluice gates; non-intrusive setup with a Bluetooth setting tool, double-sealed enclosure, data logging
IQT3 Intelligent part-turn electric actuator Ball, butterfly and plug valves and dampers, with the same setup and diagnostics as IQ3
CVA Precision control valve electric actuator Continuous modulating control of linear and part-turn control valves where instrument air is not available
CMA Compact modulating electric actuator Small control valves, chemical injection and metering pumps
Skilmatic SI3 Self-contained electro-hydraulic actuator Spring-return fail-safe and ESD duty with partial stroke testing, needing only an electrical supply
GP / GH Scotch yoke pneumatic (GP) and hydraulic (GH) actuators Large quarter-turn valves on pipelines and ESD service; spring-return or double-acting
CP Compact pneumatic quarter-turn actuator Smaller on-off ball and butterfly valves on plant air
Fairchild 10, 30, 55, 66, M11, 81 Precision pressure regulators Instrument air to positioners and actuators, test benches; Model 66 in stainless steel for corrosive and offshore sites
Fairchild 1000 No-bleed precision regulator Saves instrument air or gas where continuous bleed is not acceptable
Fairchild 10BP, 4000ABP Back pressure regulators Holding upstream pressure in process and test systems
YTC YT-1000, YT-3300 Valve positioners Electro-pneumatic (YT-1000) and smart HART (YT-3300) positioning of linear and rotary pneumatic actuators

Where Rotork equipment is used

Rotork actuators are common on oil and gas pipelines and terminals, refineries and gas plants, water and wastewater networks, desalination plants and power stations. Electric IQ actuators handle isolation valves on long pipelines and water mains, often networked over Rotork Pakscan, Modbus or another fieldbus. Skilmatic and scotch yoke actuators cover emergency shutdown valves, and Fairchild regulators and YTC positioners sit on pneumatic control valves throughout process plants.

Ordering Rotork actuators and spare parts: what we need

Send photos of the actuator nameplate with the model, serial number and wiring diagram number; the wiring diagram is usually inside the terminal cover. Rotork can identify the original build, including options and control interface, from the serial number. For a new application add the valve type and size, required torque or thrust, operating time, mounting flange (ISO 5210 or ISO 5211), power supply, control signal or network protocol, fail-safe requirement and hazardous-area marking. For regulators and positioners send the full model code and the pressure or signal ranges.

Facts checked against Rotork plc company information and product data, October 2026.

FAQ

Questions about the Rotork CVL-1500 Electric Linear Actuator 6,672 N

Answers from our engineering team on installation, compatibility and integration.

01What is the maximum thrust of the Rotork CVL-1500?
Rated thrust is 1,500 lbf (6,672 N), adjustable down to 40 percent (600 lbf, 2,669 N), and the actuator resists back-drive up to 125 percent of rated force.
02What is the CVL-1500 stroke and speed?
Maximum stroke is 2 in (50.8 mm) at 0.1 in/s (2.54 mm/s), which gives a full-stroke time of about 20 seconds at 100 percent speed.
03How heavy is the CVL-1500?
The datasheet gives approximately 24 kg (53 lb), the same as the CVL-1000, so the extra force comes without extra mass or a different mounting pattern.
04Does the CVL-1500 have a 24 VDC version?
Yes. The 24 VDC option is available on all CVA models except CVL-5000, with a 7 A maximum, and a reserve powerpack can be added for fail-to-position.
05How long does the CVL-1500 reserve powerpack take to charge?
The datasheet lists 100 seconds for the CVL-1500, during which operation is inhibited and the LED flashes while the super capacitors charge.