Brand:

Rotork IQT500 Part-Turn Electric Valve Actuator

Description

Rotork IQT500 overview

The Rotork IQT500 is a size of the IQT range of intelligent part-turn electric actuators, designed to turn quarter-turn valves such as ball, plug and butterfly valves through a travel of about 90 degrees. In Rotork’s published electrical data the size appears in a table shared with the IQTM and IQTF versions, which means the Rotork IQT500 figures apply across those variants of the same size. Buyers in Oman and across the GCC usually come to us with the bare model name because it is the designation printed on the nameplate and quoted in valve data sheets, so this page is organised around that designation.

What sets the IQT500 apart from the multi-turn IQ family is its drive concept. Rotork describes the IQT motor as a low inertia 24 V permanent magnet DC motor with class F insulation. Alternating current supplies are handled by using two phases only, either phase to neutral or phase to phase, which are transformed and rectified inside the actuator to feed both the control package and the DC motor. A direct 24 VDC supply is also possible, within a tolerance of 17 to 36 VDC. That architecture is what allows one actuator size to cover such a wide list of voltages.

This page is intended to help engineers and purchasers identify the IQT500 quickly, compare it with neighbouring sizes and prepare a clear enquiry. All figures come from Rotork’s own published electrical and specification documents, and where a value is not published we do not quote one.

Key features of the IQT500 actuator

  • Part-turn output for 90 degree valves, with the IQT500 sized by Rotork for the quarter-turn market.
  • Low inertia 24 V permanent magnet DC motor with class F insulation, fed internally from AC or DC supplies.
  • Torque switch protection is the primary safeguard, backed by thermostats and control logic that prevents motor stall on a jammed valve.
  • AC supply tolerance of +10 percent and minus 15 percent on voltage, and plus or minus 5 percent on frequency, per the Rotork electrical data.
  • Published current and power figures valid for both 50 Hz and 60 Hz supplies at actuator rated torque.
  • Output speed adjustment, handwheel emergency operation and non-intrusive Bluetooth or infrared setting are described in the Rotork IQT specification that accompanies the IQT500 range.

IQT500 technical specifications

Parameter Value
Manufacturer Rotork
Model IQT500
Range IQT (variants IQTM and IQTF share the same electrical table)
Actuator type Part-turn electric valve actuator
Motor Low inertia 24 V permanent magnet DC motor, class F insulation
AC supply voltages 100, 110, 115, 120, 200, 208, 220, 230, 240, 270, 380, 400, 415, 440, 460, 480, 500, 550, 575, 590, 600, 660 and 690 V
DC supply 24 VDC nominal, tolerance 17 to 36 VDC
Tolerance (AC) Voltage +10 percent / -15 percent, frequency plus or minus 5 percent
Phases used on AC Two phases only (phase-neutral or phase-phase)
Current at 400 V, rated torque 1.2 A
Power at 400 V, rated torque 0.43 kW
Current at 24 VDC, rated torque 13.0 A
Source of electrical data PUB002-068

This page deliberately quotes electrical data only. The rated output torque of the IQT500 depends on the size and configuration and should be taken from the Rotork data sheet or confirmed in your RFQ.

IQT500 electrical and performance data

The table below reproduces the published figures for the IQT500 column at actuator rated torque. Rotork states that the data is valid for both 50 Hz and 60 Hz supplies and that manufacturing tolerances may mean individual units differ slightly.

Supply Current at rated torque (A) Power (kW)
24 VDC 13.0 0.32
100 V 4.5 0.43
110 V 4.1 0.43
115 V 4.1 0.43
120 V 3.7 0.43
200 V 2.2 0.43
208 V 2.2 0.43
220 V 2.2 0.43
230 V 1.9 0.43
240 V 1.9 0.43
270 V 1.9 0.43
380 V 1.2 0.43
400 V 1.2 0.43
415 V 1.2 0.43
440 V 1.2 0.43
460 V 1.2 0.43
480 V 0.9 0.43
500 V 0.9 0.43
550 V 0.9 0.43
575 V 0.9 0.43
590 V 0.9 0.43
600 V 0.9 0.43
660 V 0.9 0.43
690 V 0.9 0.43

Rotork also documents that the output speed of IQT actuators can be adjusted between 50 and 100 percent in 1 percent steps, which is useful where a slower stroke is needed to limit pressure surges in long pipelines.

Typical applications in Oman and the GCC

In oil and gas facilities in Oman, the IQT500 is specified on isolation and control valves in gathering stations, pipelines and tank farms, where an actuator with integral controls and a lockable local/stop/remote selector simplifies operations. Utilities and power plants use similar IQT actuators on cooling water, feedwater and fuel lines. Water and desalination operators across the GCC rely on them for intake, transfer and distribution valves, where the sealed enclosure copes with humidity and dust. In manufacturing and petrochemical sites the IQT500 appears on process utilities and skid packages. Because the actuators are described by Rotork as suitable for indoor and outdoor use, with ambient limits of minus 30 to plus 70 degrees Celsius in the IQ specification, they suit the hot coastal climate of Muscat, Sohar and Duqm.

Typical valve types include gate and globe valves for multi-turn actuators and ball, plug and butterfly valves for part-turn actuators, so confirm the valve stem or shaft details when you request the IQT500.

Selection and compatibility notes for the IQT500

Because the IQT500 converts AC input internally, cable sizing should follow the voltage drop rule in the Rotork electrical data: choose a cable so that the volt drop does not exceed 10 percent of the nominal supply voltage at rated torque. Fuses and trip devices should protect the power cable rather than the motor, because torque monitoring and thermostats already protect the actuator. Where actuators share a three-phase feeder, spread them evenly across the phases to keep the load balanced.

A short guide to reading the Rotork electrical data helps when comparing builds. The IQT range is designed around the short duty of valve actuators: since continuous running is not needed for isolating, inching or regulating valves, motors only need a short duty rating, and valve load varies strongly across the stroke and from stroke to stroke. Applying traditional motor protection to such a motor is, in Rotork’s words, flawed because it leads to spurious tripping or no protection at all. Instead the primary protection is the torque switch, which measures actuator output torque and compares it with the open and close torque switch settings, protecting the motor and, more importantly, the valve. Thermostats provide over-temperature protection if the duty cycle exceeds the actuator rating, and the control logic prevents motor stall if the valve jams. For cable sizing Rotork requires that the volt drop does not exceed 10 percent of nominal supply voltage at rated torque, and for UPS supplies it asks for negligible harmonic distortion, with power conforming to standards such as EN 50160. On three-phase systems, connect multiple actuators equally across all three phases to achieve load diversity; three terminals are provided for the cable connection.

Match the IQT500 to the valve by the maximum valve torque including a safety margin, the stroke or number of turns, the mounting flange and the required operating time. Rotork’s sizing guidance says the actuator must guarantee valve closure at the specified differential pressure and temperature, with enough margin that the torque switch can still trip at maximum valve torque when the supply is 10 percent below nominal. Mention any hazardous-area, SIL or fieldbus requirement in your enquiry, because the certification of an actuator depends on the exact build.

Installation and commissioning

Before mounting the IQT500, check the valve flange and drive dimensions against the Rotork dimensional data sheet for the IQT range, which covers sizes 1000 to 3000 in a common drawing. The unit is delivered with a detachable drive coupling that is machined to suit the valve shaft, and gearing that is self-locking so the valve cannot back-drive the actuator. Rotork describes adjustable stop bolts giving about plus or minus 5 degrees at each end of travel. Wire the supply, then set the limits and torque levels through the non-intrusive Bluetooth or infrared interface without removing covers. Position can be set across 90 degrees plus or minus 10 degrees.

Rotork supplies a commissioning kit with its actuators comprising an installation manual, wiring diagram and cover seals. Keep the terminal compartment dry during cabling, and torque the cover fasteners evenly after wiring so the IQT500 retains its enclosure rating.

Maintenance and spare parts for the IQT500

Rotork designs the gear case as an oil-filled enclosure suitable for operation at any angle, and the motor and internal electrical elements are sealed from the environment, so routine maintenance on the IQT500 is mainly visual and functional. Check the cable glands, cover seals and fasteners during shutdowns, exercise infrequently used valves, and review the datalogger or event records for torque trends that point to valve wear. Replace seals if covers were opened. For hard-to-find parts and replacement units please send the full nameplate details together with the model IQT500.

Rotork IQT500 vs Other Rotork Part-Turn Electric Valve Actuator Variants

Within this product family the variants are built on the same platform and differ mainly in one key parameter. For the Rotork IQT500 that parameter is IQT500; check it against the process data, the supply available at the panel and any spare-parts commonality you want to keep across the plant.

Variant Distinguishing detail
Rotork IQT125 Part-Turn Electric Valve Actuator IQT125
Rotork IQT250 Part-Turn Electric Valve Actuator IQT250
Rotork IQT500 Part-Turn Electric Valve Actuator (this page) IQT500
Rotork IQT1000 Part-Turn Electric Valve Actuator IQT1000
Rotork IQT2000 Part-Turn Electric Valve Actuator IQT2000

FAQ summary

The most common questions we receive about the IQT500 concern its torque rating, available output speeds, supply voltage options, and how to specify a replacement. In short, the IQT500 is a Rotork part-turn electric valve actuator; the data on this page is taken from the Rotork documents listed below; and the exact build always depends on the voltage, speed and options that you confirm in your RFQ. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Documents and quotation

The datasheet for the IQT500 is the Rotork electrical data document PUB002-068, which you can download from this page when available. To obtain pricing and lead time, send the RFQ with the part number IQT500, the quantity, supply voltage and frequency, valve type and any special requirements, and our team will respond promptly. Please note that the product is described by its model designation and that final configuration is confirmed against the manufacturer’s data.

Other Models in the IQT Range

Seven Star LLC supplies models from the IQT range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Rotork IQT125 Part-Turn Electric Valve ActuatorElectric ActuatorsView details
Rotork IQT250 Part-Turn Electric Valve ActuatorElectric ActuatorsView details
Rotork IQT500 Part-Turn Electric Valve ActuatorElectric ActuatorsYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Rotork IQT500 Part-Turn Electric Valve Actuator Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Rotork is a British flow control company best known for electric valve actuators. Jeremy Fry founded Rotork Engineering Company in Bath in 1957, the year its first actuator, the 100A, went on sale, and the group is still headquartered in Bath and listed on the London Stock Exchange. Today Rotork makes electric, pneumatic, hydraulic and electro-hydraulic actuators, gearboxes, precision regulators and valve positioners.

Seven Star LLC is an independent supplier listing Rotork actuators, Rotork Fairchild regulators, YTC positioners and spare parts for buyers in Oman and the GCC. Replacement units are matched from the actuator nameplate and wiring diagram number.

Rotork company profile

Origin Founded by Jeremy Fry in 1957 in Bath, England; first product the 100A valve actuator
Headquarters Brassmill Lane, Bath, United Kingdom
Ownership Rotork plc, a public company listed on the London Stock Exchange
Acquired brands Fairchild precision pneumatic controls (2011, Winston-Salem, USA), YTC valve positioners (Young Tech Co., Seoul, 2014), Mastergear gearboxes (2016)
Product families Intelligent electric actuators, control valve actuators, electro-hydraulic and fluid power actuators, gearboxes, precision regulators, positioners and network control systems

Milestones

  • 1957: Jeremy Fry founds Rotork in Bath, England; the first product is the 100A valve actuator.
  • 2011: Fairchild precision pneumatic controls (Winston-Salem, USA) is acquired.
  • 2014: YTC valve positioners (Young Tech Co., Seoul) is acquired.
  • 2016: Mastergear gearboxes is acquired.

Rotork actuators, regulators and positioners

Series Type Typical use
IQ3 Intelligent multi-turn electric actuator Gate and globe valves, penstocks and sluice gates; non-intrusive setup with a Bluetooth setting tool, double-sealed enclosure, data logging
IQT3 Intelligent part-turn electric actuator Ball, butterfly and plug valves and dampers, with the same setup and diagnostics as IQ3
CVA Precision control valve electric actuator Continuous modulating control of linear and part-turn control valves where instrument air is not available
CMA Compact modulating electric actuator Small control valves, chemical injection and metering pumps
Skilmatic SI3 Self-contained electro-hydraulic actuator Spring-return fail-safe and ESD duty with partial stroke testing, needing only an electrical supply
GP / GH Scotch yoke pneumatic (GP) and hydraulic (GH) actuators Large quarter-turn valves on pipelines and ESD service; spring-return or double-acting
CP Compact pneumatic quarter-turn actuator Smaller on-off ball and butterfly valves on plant air
Fairchild 10, 30, 55, 66, M11, 81 Precision pressure regulators Instrument air to positioners and actuators, test benches; Model 66 in stainless steel for corrosive and offshore sites
Fairchild 1000 No-bleed precision regulator Saves instrument air or gas where continuous bleed is not acceptable
Fairchild 10BP, 4000ABP Back pressure regulators Holding upstream pressure in process and test systems
YTC YT-1000, YT-3300 Valve positioners Electro-pneumatic (YT-1000) and smart HART (YT-3300) positioning of linear and rotary pneumatic actuators

Where Rotork equipment is used

Rotork actuators are common on oil and gas pipelines and terminals, refineries and gas plants, water and wastewater networks, desalination plants and power stations. Electric IQ actuators handle isolation valves on long pipelines and water mains, often networked over Rotork Pakscan, Modbus or another fieldbus. Skilmatic and scotch yoke actuators cover emergency shutdown valves, and Fairchild regulators and YTC positioners sit on pneumatic control valves throughout process plants.

Ordering Rotork actuators and spare parts: what we need

Send photos of the actuator nameplate with the model, serial number and wiring diagram number; the wiring diagram is usually inside the terminal cover. Rotork can identify the original build, including options and control interface, from the serial number. For a new application add the valve type and size, required torque or thrust, operating time, mounting flange (ISO 5210 or ISO 5211), power supply, control signal or network protocol, fail-safe requirement and hazardous-area marking. For regulators and positioners send the full model code and the pressure or signal ranges.

Facts checked against Rotork plc company information and product data, October 2026.

FAQ

Questions about the Rotork IQT500 Part-Turn Electric Valve Actuator

Answers from our engineering team on installation, compatibility and integration.

01What type of actuator is the Rotork IQT500?
The IQT500 is a part-turn (quarter-turn) electric valve actuator from the Rotork IQT range, intended for ball, butterfly and plug valves that travel through roughly 90 degrees. It is a compact integral unit with its own starter and local controls.
02What power supplies can the IQT500 run from?
Rotork electrical data for the IQT range covers 24 VDC supplies and a series of AC voltages from 100 V to 690 V at 50 Hz and 60 Hz. For AC the unit uses two phases only, which are transformed and rectified internally, and the DC supply tolerance is 17 to 36 VDC.
03How much current does the IQT500 draw?
At rated torque and 400 V the published figure for the IQT500 column is 1.2 A and 0.43 kW, and at 230 V it is 1.9 A. The table on this page lists every supply voltage so you can size cables and protection.
04Does the IQT500 share data with other variants?
Yes. Rotork groups the IQT, IQTM and IQTF versions of the same size in one electrical table, so the figures shown for the IQT500 also apply to the modulating (IQTM) and IQTF versions of that size.
05How do I request a quotation for the IQT500?
Send us the part number IQT500 with the quantity, supply voltage, valve type and any hazardous-area or network requirements, and we will reply to your RFQ with availability and lead time. Seven Star LLC is an independent supplier and is not affiliated with Rotork.