Brand: EVAPCO
EVAPCO PHW Parallel Hybrid Closed Circuit Cooler
Description
Large closed circuit cooler cells for industrial plants and data centers
The EVAPCO PHW is a Parallel Hybrid closed circuit cooler: a mechanical induced draft, crossflow unit in which the process fluid is kept inside a sealed coil while spray water and air carry the heat away. It combines a spray-wetted coil with a crossflow PVC fill below it. Hot fluid enters the coil at the bottom connections, basin water is pumped over the coil, and air is drawn in parallel flow with the water through the coil; the water then falls through the fill, where more air removes additional heat by evaporation, before returning to the basin.
EVAPCO builds the series around its largest single cells, a 12 ft by 24 ft and a 14 ft by 26 ft unit, for projects that need the fewest units, connections and fans. The EVAPCO product page names industrial plants, data centers and large HVAC applications as the target uses, and states that the PHW offers CTI certified performance and is supplied with a written thermal performance guarantee.
Technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer | EVAPCO, Inc. |
| Type | Induced draft, parallel flow hybrid, crossflow closed circuit cooler |
| Cell sizes (printed) | PHW 12 (12 x 24 ft) and PHW 14 (14 x 26 ft), double air inlet models |
| Printed model range | PHW 12-5M24 to 12-10Q24 and PHW 14-5M26 to 14-10R26 |
| Coil | Elliptical Sensi-Coil with internal tube enhancement, steel tubing, hot-dip galvanized after assembly |
| Coil design pressure | 300 psi, ANSI/ASME B31.5, strength tested and air-under-water leak tested |
| Coil options | TITAN coil in Type 304L or 316L stainless steel with 5-year coil warranty (EVAPCO) |
| Coil connections | Two 4 in beveled for weld; 6 in when flow exceeds 450 gpm (high flow configuration) |
| Fill | XPak bonded block PVC crossflow fill, up to 120 F (48.9 C), flame spread under 25 per ASTM E84 |
| Casing and basin | G-235 mill hot-dip galvanized steel; Type 304 or 316 stainless optional with welded basin seams |
| Spray nozzles | ZM II ABS, 1-1/4 in orifice, PVC headers with threaded end caps |
| Fan motors | TEAO, inverter duty standard |
| Fan drive | Power-Band belt sized for 150% of motor power, aluminum alloy sheaves, L10 bearing life of 100,000 h |
| Drive warranty (EVAPCO) | 5 years on all drive components |
| Sound options | Low sound fan (4 to 7 dB(A) reduction) and super low sound fan (9 to 15 dB(A) reduction), per EVAPCO |
| Strainer | Type 304 stainless steel |
Model range and engineering data
The printed tables list each model by fan motor letter, from M to Q on the 12 ft cell and M to R on the 14 ft cell, with a number from 5 to 10 before the letter. The data below includes fan hp as printed, air flow, weights, coil volume, spray pump and remote sump data. Selected rows:
| Model | Fan hp | Air flow cfm | Shipping lb | Operating lb | Coil volume gal | Remote sump gal |
|---|---|---|---|---|---|---|
| PHW 12-5M24 | 30 | 177,600 | 37,220 | 57,360 | 687.8 | 1,600 |
| PHW 12-8P24 | 60 | 217,000 | 46,070 | 68,970 | 1,077.5 | 1,600 |
| PHW 12-10Q24 | 75 | 230,000 | 51,450 | 76,990 | 1,337.3 | 1,600 |
| PHW 14-5M26 | 30 | 209,100 | 43,070 | 68,570 | 808.8 | 2,110 |
| PHW 14-8R26 | 100 | 296,700 | 53,810 | 83,150 | 1,267.5 | 2,110 |
| PHW 14-10R26 | 100 | 292,000 | 60,010 | 91,910 | 1,573.3 | 2,110 |
Every printed model lists a (2) 7.5 hp spray pump delivering 1,800 gpm and a 14 in remote sump connection. Notes state that series flow piping is marked with a Z suffix, stainless coils with a C suffix and low sound fans with an R suffix, that heaviest section is the upper section, and that unit dimensions may vary slightly from catalog drawings.
Use, access and winter protection
EVAPCO notes that closed circuit coolers should only be used on sealed, pressurized systems, because continual aeration of the water in an open system can cause corrosion inside the coil tubes. The internal walkway is standard on the double air inlet units, a large access door and pump house access are standard, and optional features include an elevated internal service platform, an internal motor davit, an external service platform with ladder and a Sun-Blocker system against algae.
Electric basin heater packages with thermostat and low water cutoff are listed for the two cell sizes, for example two 12 kW heaters at 0 F for the 12 x 24 ft cell and two 15 kW heaters for the 14 x 26 ft cell, and external pumps should be heat traced and insulated. Support is on structural I-beams under the outer flanges, levelled within 1/8 in in 6 ft, without shimming between the unit and the beams. An electric water level control can replace the mechanical make-up valve.
Using the PHW in Oman and the GCC
Large closed circuit coolers are used in the region in data centres, power generation, industrial process cooling, compressor stations and water-cooled heat pump systems, where the process fluid must stay clean and free of dust and sand. Keeping the fluid inside the coil avoids fouling of heat exchangers and process equipment, which is a common problem with open towers in dusty locations. The cooler must be selected at the project’s design wet-bulb temperature, which can be high in coastal summer conditions, and multi-cell installations should consider recirculation of warm exhaust air.
The spray water outside the coil needs a water treatment programme, blowdown control and a Legionella control plan, because scale on the coil and fill reduces capacity. Make-up water in the region may be desalinated water, groundwater or treated effluent, and the treatment programme should be designed for the actual source. Plan regular cleaning of the basin, strainers, nozzles and fill, and leave access space around the unit for maintenance. Check the structural support for the operating weight, including the coil fluid and spray water.
Information to send with an enquiry
- Process fluid, flow rate and temperatures
- Design wet-bulb temperature and site layout
- Make-up water source and quality
- Number of cells, sound limits and quantity
Documents and quotation
The attached brochure includes the full PHW engineering tables and the optional equipment pages. Seven Star LLC is an independent supplier in Muscat; to quote a closed circuit cooler send the fluid, flow rate, entering and leaving temperature, allowable pressure drop and design wet bulb. See also cooling equipment.
Datasheets & Documents
- Brochure EVAPCO PHW parallel hybrid closed circuit cooler brochure with engineering data (EN) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
EVAPCO is an American manufacturer of evaporative cooling and heat transfer equipment, founded on 14 June 1976 in Baltimore, Maryland, by Bill Kahlert and Wilson Bradley. It started with five employees and one product line, evaporative condensers for industrial refrigeration, before adding cooling towers and closed circuit coolers. EVAPCO is employee-owned, headquartered in Taneytown, Maryland, and marked 50 years in June 2026.
EVAPCO company profile
| Founded | 14 June 1976, Baltimore, Maryland |
|---|---|
| Founders | Bill Kahlert and Wilson Bradley |
| Headquarters | Taneytown, Maryland |
| Ownership | Employee-owned |
| Product families | ATC-E and PHC-E evaporative condensers, ATWB closed circuit coolers, AXS crossflow and AT counterflow cooling towers, LPT and LSTE forced draft centrifugal fan cooling towers, eco-Air dry coolers, water treatment systems |
Milestones
- 1976: EVAPCO is founded in Baltimore with one product line.
- 2026: EVAPCO marks 50 years.
EVAPCO product families
The range runs from factory-assembled cooling towers to larger field-erected equipment. Open cooling towers reject heat by evaporation, closed circuit coolers keep the process fluid inside a sealed coil, and evaporative condensers cool refrigerant directly for ammonia and other refrigeration plants. The eco-Air series adds dry and adiabatic coolers that use little or no water, and EVAPCO publishes engineering data bulletins for its model families.
EVAPCO equipment from Seven Star LLC
Seven Star LLC is an independent supplier in Muscat and supplies EVAPCO cooling equipment against project duties. Send the heat load, fluid, temperatures and site conditions with your request for quotation, and use the product pages for the datasheets of each EVAPCO series.
EVAPCO products we list
Facts checked against EVAPCO's own history page and 50th anniversary coverage, October 2026.
Related products
Frequently Asked Questions
It lists a 12 ft by 24 ft cell (PHW 12) and a 14 ft by 26 ft cell (PHW 14), both double air inlet models.
The coil has a design pressure of 300 psi and complies with ANSI/ASME B31.5, with strength and leak testing.
The coil connections increase from 4 in to 6 in BFW when the flow rate exceeds 450 gpm, called the high flow coil configuration.
No. The brochure states closed circuit coolers should only be used on sealed, pressurized systems because aeration can corrode the coil tubes.
Low sound fans reduce sound by 4 to 7 dB(A) and super low sound fans by 9 to 15 dB(A), depending on selection and measurement location.

Reviews
There are no reviews yet.