Brand:

Finder 78.X1.1.230.2412 24 V DC 240 W PFC DIN Rail Power Supply

Description

Overview

Where a control cabinet needs more than a few amps of 24 V, the Finder 78.X1.1.230.2412 steps in with 10 A and 240 W from a single-phase input. It is the X1 member of the Finder 78 series industrial DIN rail supplies and, unlike the smaller J1 and W1 units, it uses a double-stage design with active power factor correction. That keeps the input current low and the power factor at or above 0.82, which matters when many supplies share one distribution board. Seven Star LLC is an independent supplier serving Oman and the GCC.

What the digits in 78.X1.1.230.2412 tell you

X stands for the 240 W output class. The two 1 digits mean single-phase supply and AC input with DC output, while 230 marks the universal input range of 100 to 240 V AC or 220 V DC. At the tail, 24 sets a 24 V output, the next 1 selects the double-stage version with PFC, and the final 2 adds an embedded fuse and an output voltage regulator. Compare this with the 2402 ending on the J1 and W1 supplies, whose 0 means a standard single-stage design without correction.

Output and input data for Finder 78.X1.1.230.2412

Item Datasheet value
Rated output 24 V DC, 10 A, 240 W (minus 20 to plus 50 degrees C, 230 V AC)
Output adjustment 24 to 28 V DC
Peak current capability 13 A for 5 ms
Voltage variation less than 2 percent, no load to full load
Ripple at full load 150 mV
Hold-up time at full load 12 ms at 115 V AC; 16 ms at 230 V AC
Nominal input 100 to 240 V AC; 140 to 338 V DC
Operating input range 90 to 264 V AC; 127 to 370 V DC
Maximum consumption 358.36 VA at the lowest AC input
Current at 230 V AC 1.3 A
Power factor 0.82 or better
Efficiency at 230 V AC 87 percent
Stand-by power 5.0 W
MTTF more than 200,000 hours
Start-up delay 1500 ms
Isolation 3000 V AC input to output; 2000 V AC input to earth
Protection and ambient IP 20; minus 20 to plus 70 degrees C with derating

How the Finder 78.X1.1.230.2412 differs from other 78 series variants

Step down to the 78.W1.1.230.2402 and you get 120 W, 5 A, 88 percent efficiency and 0.7 W stand-by, but no active PFC. Step up to the 78.Y1.1.230.2412 and the output doubles to 480 W and 20 A, with a 26 A boost for 3 s, efficiency of 92 percent and a power factor of 0.90 or better. Between these, the Finder 78.X1.1.230.2412 offers 10 A without a boost function, a stand-by draw of 5.0 W compared with 6.0 W for the Y1, and a power loss to the environment of 35.9 W. Its start-up delay is 1500 ms, a little longer than the 1200 ms of the smaller units.

Where 240 W of 24 V is needed in Oman and the GCC

A 10 A rail powers a typical PLC cabinet with a rack of I/O, a bank of interposing relays, several solenoid valve manifolds and a field switch. It is commonly found in water pumping and treatment skids, compressor control panels, tank farm cabinets and building plant rooms. In summer, cabinet temperature is the main concern: full current is guaranteed up to 50 degrees C and must be reduced at higher temperatures following the derating curves in the datasheet.

Sizing and installation

Add up the steady currents of all loads, include a margin of about 20 percent, and check the inrush of contactors and valve coils against the 13 A peak capability. Mount the unit on a 35 mm rail with clear space above and below, since hot surfaces are marked on the top. Use the terminals for wire up to the limits given in the datasheet and tighten them to the specified torque. For redundancy, two units can be paralleled through external diodes or a redundancy module.

Service and fault finding

The DC OK light shows that the output is present. If the unit enters hiccup mode, disconnect the load branches one at a time to find the short. Overheating shutdown resets automatically once the unit cools. Keep ventilation slots clear and check terminal tightness during shutdowns.

Ordering notes

Quote the full code Finder 78.X1.1.230.2412 when you order, since the neighbouring 240 W and 480 W codes share the same ending. Redundancy modules and DIN rail accessories can be quoted at the same time.

Why active PFC matters for the Finder 78.X1.1.230.2412

A plain rectifier supply draws current in short peaks, which distorts the line and raises the apparent power. Active correction shapes the input current so that it follows the voltage waveform, lifting the power factor and trimming the current drawn from the distribution board. In a panel with several 240 W supplies, or on a generator-backed site where voltage and frequency vary, this lowers the loading on cables and breakers and helps avoid nuisance tripping. The price is a slightly longer start-up delay and a higher stand-by consumption, which the datasheet states at 1500 ms and 5.0 W. Remember also the inrush peak of 35 A at 230 V AC when you select the upstream circuit breaker: choose a characteristic that tolerates the short peak when the supply is switched on.

When several supplies feed the same panel, stagger their start-up or use a breaker with a slow trip curve so that the combined inrush does not trip the incoming protection.

Related items you may also need: Finder 22.32.0.230.1340 25 A 2 NO Modular Contactor | Finder 46.61.9.024.0040 16 A Miniature Industrial Relay | Finder 38.51.7.024.0050 24 V DC 6 A Relay Interface Module | All Finder products.

Documents and quotation

The series datasheet covering the Finder 78.X1.1.230.2412 is attached to this page and includes ordering information, derating curves, outlines and wiring diagrams. Please send your RFQ with Finder 78.X1.1.230.2412, the quantity and your delivery location in Oman or the GCC.

Other Models in the 78 Range

Seven Star LLC supplies models from the 78 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Finder 78.J1.1.230.2402 24 V DC 75 W DIN Rail Power SupplyPower ModulesView details
Finder 78.X1.1.230.2412 24 V DC 240 W PFC DIN Rail Power SupplyPower ModulesYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Finder 78.X1.1.230.2412 24 V DC 240 W PFC DIN Rail Power Supply Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Finder is an Italian manufacturer of relays, timers and other electromechanical and electronic devices for industry and buildings. It was founded in 1954 by Piero Giordanino, who had patented a step relay in 1949, and it is headquartered in Almese, Piedmont, where most of its manufacturing still takes place. Finder is owned and run by the Giordanino family.

Seven Star LLC is an independent supplier in Muscat. We list Finder relays, power supplies and protection devices for control panels, building services and machine automation in Oman and the GCC.

Finder company profile

Founded 1954, Italy, by Piero Giordanino
Headquarters Almese, Piedmont, Italy; more than 70 % of manufacturing is done there
Ownership Giordanino family
Range More than 14,000 product types, according to the company
Product families Industrial relays (series 40, 46, 55, 60), interface relay modules (34, 38, 39), timers (80, 85), monitoring relays (70, 71), surge protection (7P), switch-mode power supplies (78), thermostats and panel fans

Milestones

  • 1949: Piero Giordanino patents his first step relay.
  • 1954: Finder is founded.
  • 1965: The plant in Almese opens.
  • 1966: The Series 60 industrial relay is launched.

Finder product series

Relays include the 46.61 miniature industrial relay, the 62.32 power relay with magnetic blow-out for DC loads, the 38.51 relay interface module and the 7S forcibly guided safety relay. Control relays include the 72.01 liquid level control relay and the 80.01 multi-function modular timer, and the 22.32 modular contactor switches loads up to 25 A.

Power supplies include the 78.12, 78.36, 78.W1, 78.Y1 and three-phase 78.Y3 DIN rail units from 12 W to 480 W, and surge protection includes the 7P.04 Type 1+2 and 7P.45 Type 2 three-phase devices.

Where Finder devices are used

Control panels for machines, pumps and HVAC, distribution boards in commercial and residential buildings, water tank and well level control, lighting control and the protection of electrical installations against surges.

Finder products we list

Family Examples
Automation Accessories 38.51.7.024.0050 24 V DC 6 A Relay Inter…, 46.61.9.024.0040 16 A Miniature Industri…, 62.32.9.024.4800 16 A Magnetic Blow DC P…, 72.01.9.024.0000 Liquid Level Control Re…, 7P.04.8.260.1025 Type 1+2 Three-Phase Su…, 7P.45.8.275.1020 Type 2 Three-Phase Surg…, 7S.23.9.024.0210 Forcibly Guided Safety…, 80.01.0.240.0000 Multi-Function Modular…
Power Modules 78.12.1.230.2400 24 V 12 W DIN Rail Powe…, 78.36.1.230.2402 24 V 36 W Modular Power…, 78.W1.1.230.2402 24 V 120 W DIN Rail Pow…, 78.Y1.1.230.2412 24 V 480 W Single-Phase…, 78.Y3.1.440.2414 24 V 480 W Three-Phase…
Contactors & Overload Relays 22.32.0.230.1340 25 A 2 NO Modular Conta…

Ordering Finder products: what we need

Quote the complete ordering code, for example 62.32.9.024.4800, which includes coil voltage and contact variant, together with the quantity, the supply voltage and frequency and any approvals the project requires. With that information the matching Finder version can be confirmed against the datasheet before a quotation is issued.

Facts checked against Finder's own company pages (findernet.com), October 2026.

FAQ

Questions about the Finder 78.X1.1.230.2412 24 V DC 240 W PFC DIN Rail

Answers from our engineering team on installation, compatibility and integration.

01What output does the Finder 78.X1.1.230.2412 deliver?
It delivers 24 V DC at 10 A, which is 240 W, adjustable from 24 to 28 V DC, from an input of 100 to 240 V AC or 140 to 338 V DC.
02Does the Finder 78.X1.1.230.2412 have power factor correction?
Yes. It is a double-stage design with active PFC, and the datasheet lists a power factor of 0.82 or higher.
03What is the difference between 78.X1 and 78.Y1?
The X1 is rated 10 A and 240 W with 87 percent efficiency and 5.0 W stand-by, while the Y1 is 20 A and 480 W with 92 percent efficiency and a 26 A boost.
04Can two 78.X1.1.230.2412 supplies be paralleled?
Yes. The series allows parallel working for more current or redundancy when an external diode is used on each output.
05What is the hold-up time of the 78.X1.1.230.2412?
At full load the hold-up time is 12 ms with 115 V AC input and 16 ms with 230 V AC input.