Brand:

FIAMM SGL 15 2 V 183 Ah Planté GroE Flooded Cell

Description

SGL 15, referenced in the folder as 7 GroE 175, is a 2 V vented Planté cell from the FIAMM SGL-SGH series built to the German DIN 40738 GroE standard. It is rated 183 Ah at the 10-hour rate to 1.80 volts per cell at 20 °C, in a 182 x 153 x 415 mm case with 4.8 litres of electrolyte and a typical weight of 26.3 kg.

A pure lead Planté cell with a stated 25-year design life

FIAMM positions SGL-SGH as the longest-life lead-acid battery in its flooded portfolio, designed to operate 25 years without loss of performance. The positive plate is Planté pure lead with a laminate design, which also gives very low water consumption: a single topping-up in three years under float conditions.

The SGL branch starts at SGL 7 (3 GroE 75, 79 Ah) and reaches 314 Ah at SGL 25 (12 GroE 300), continuing up to SGL 37. SGL 15 is the largest of the five narrow 153 mm wide cells before the case grows to 228 mm wide from SGL 17.

Features listed in the folder and manual

  • Planté pure-lead positive plate with narrow plate distance, built to DIN 40738 (GroE).
  • Design life 25 years; deep-discharge and high-rate performance.
  • Special inspection hole in SGL-SGH cells to check electrolyte density and temperature without removing the recombination plugs.
  • Electrolyte specific gravity 1.22 kg per litre at 20 °C; transparent SAN container.
  • Optional nut and bolt terminals to UK National Grid; the manual also lists BS 6290 part 2 for the Planté range.

Technical specification

Data printed for SGL 15 in the SGL-SGH folder

Parameter Specification
Cell type SGL 15 (7 GroE 175)
Nominal voltage 2 V per cell
Nominal capacity, 10 h to 1.80 V per cell, 20 °C 183 Ah
Length x width x height 182 x 153 x 415 mm
Electrolyte quantity 4.8 litres
Typical weight with electrolyte 26.3 kg
Positive plate Planté pure lead
Design life 25 years
Standards listed DIN 40738 GroE; UK National Grid (optional nut and bolt terminals)

Values from the flooded engineering manual (range data)

Parameter Specification
Float voltage at 20 °C 2.23 V per cell; float current about 0.3 mA per Ah
Terminal torque, M10 female 20 to 25 Nm
Maximum storage before refresh 9 months at 10 °C, 5 months at 20 °C, 3 months at 30 °C
Temperature compensation plus 2.5 mV per cell per °C at 10 °C or below; minus 2.5 mV at 30 °C or above
Equalizing charge 2.70 V per cell, under FIAMM supervision, below 45 °C

Derived values (calculated here, not printed)

Parameter Specification
Energy at the C10 rating about 0.37 kWh per cell (2 V x 183 Ah)
60-cell string float voltage 60 x 2.23 = 133.8 V at 20 °C

Reading the GroE name and the SGL step sizes

In the DIN naming convention (general knowledge, not a FIAMM statement) the number after GroE is the nominal capacity and the first number the plate count: 7 GroE 175 means seven plates and 175 Ah, and the folder shows FIAMM delivering 183 Ah. That margin is typical of the range, where actual capacity exceeds the DIN nominal value.

Adjacent types change capacity in steps of about 25 Ah: SGL 13 gives 155 Ah and SGL 17 gives 209 Ah in the wider 228 mm case. For larger plants the SGH branch extends to 2860 Ah according to the manual.

Commissioning and maintenance notes from the manual

Use straps or mechanical lifting, never the terminals. Fit connectors with insulated wrenches at 20 to 25 Nm, apply No-Oxide grease, and label cells from number 1 at the positive end. Dry-charged cells are filled to the MAX line and charged at 0.10 C10 for 16 to 17 hours.

Boost charge after a discharge at 2.40 V per cell, limited to 0.15 C10, ending at 0.001 C10 or after 24 hours. Equalizing is not a routine method and should be supervised by a FIAMM technician.

Long-life DC supplies for utilities and process plants

SGL-SGH is aimed at industry and utility installations, including power stations and substations where replacement outages are costly. General engineering note: when a plant life of 20 years or more is planned, a Planté cell cuts the number of battery replacements, but it requires a ventilated room and periodic electrolyte checks.

Related FIAMM items

SD-SDH offers a 15-year flat-plate alternative, LM is the tubular OPzS cell to DIN 40736, and accessories on the FIAMM site include racks, plugs and the battery sizing software.

Battery room and maintenance notes

Planté cells are chosen for long-life DC supplies in substations, power plants, desalination plants and process plants, where the battery must be reliable for many years. Flooded cells produce hydrogen during charging, so the battery room must be ventilated as required by the manual and the applicable standard, with no ignition sources near the cells. The room should be cooled in the region’s climate, because high temperatures shorten battery life, and the charger’s float voltage and temperature compensation should be set as given in the manual.

Check electrolyte levels, specific gravity and cell voltages at the intervals in the manual, top up only with the specified water, and keep the cell tops clean and dry. Recheck the connection torque during routine maintenance.

Information to send with an enquiry

  • System DC voltage and load profile
  • Required autonomy and number of cells
  • Racks, connectors and accessories
  • Quantity

Frequently asked questions

What does 7 GroE 175 mean?

It is the DIN 40738 designation; by convention it means seven plates and 175 Ah nominal; the SGL 15 folder capacity is 183 Ah.

What design life does FIAMM state?

25 years for the SGL-SGH series.

How often is topping-up needed?

The folder states a single topping-up in 3 years under float conditions.

What float voltage is recommended?

2.23 volts per cell at 20 °C according to the flooded manual.

How heavy is SGL 15?

26.3 kg with electrolyte, in a 182 x 153 x 415 mm case.

Documents and quotation

Download the official FIAMM datasheet and manual for SGL 15 from this page. As an independent supplier based in Muscat, Seven Star LLC supplies FIAMM items on request: use the quote form with the quantity you need. Check every value in the documents against your own specification before you order. Browse similar items in the category.

Datasheets & Documents
  • PDF Datasheet FIAMM SGL-SGH range folder, rev. 11.2025 (EN, PDF) Download
  • PDF Manual FIAMM Engineering Manual flooded technology, ed. 07/2026 rev. 15 (EN, PDF) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

FIAMM is an Italian battery brand founded in 1942 in Montecchio Maggiore, near Vicenza, as Fabbrica Italiana Accumulatori Motocarri Montecchio, to make batteries for electric three-wheelers. It went on to make traction, starter and industrial standby batteries. In 2017 the battery business became FIAMM Energy Technology, a joint venture in which Hitachi Chemical took a 51% stake.

FIAMM company profile

Founded 1942, Montecchio Maggiore, Italy
Name Fabbrica Italiana Accumulatori Motocarri Montecchio
Headquarters Montecchio Maggiore, Vicenza
Joint venture FIAMM Energy Technology with Hitachi Chemical, 2017
Product families FLB and FGL AGM VRLA batteries, FIT and FHT front-terminal telecom batteries, FHB high-rate UPS batteries, SD flooded high-rate cells, automotive starter batteries

Milestones

  • 1942: FIAMM is founded in Montecchio Maggiore.
  • 2017: FIAMM Energy Technology is formed with Hitachi Chemical.

Reserve power batteries for standby and storage

The FIAMM Reserve Power Solutions business supplies industrial batteries under ranges such as FG and FGL general-purpose AGM blocks, FIT, FHT2, FHB and FLB front and top terminal AGM batteries, SD, SDH, SGL, SGH and LM flooded cells, and SMG gel OPzV cells. Applications named on the site include data centres and UPS, telecom, industry and utilities, security and emergency, and renewable energy storage.

Supply through Seven Star LLC

Seven Star LLC is an independent supplier in Muscat that quotes FIAMM batteries for projects in Oman and the GCC, with the official range folder and engineering manual attached to each product page.

FIAMM products we list

Family Examples
UPS and Batteries 12FGL42 12 V 42 Ah AGM VRLA Battery, 12FHB400 12 V 101 Ah High-Rate AGM Battery, 12FHT182 12 V 180 Ah Front Terminal AGM…, 12FIT201 12 V 195 Ah Front Terminal Tele…, 12FLB250P 12 V 75 Ah AGM UPS Battery, SD 15 2 V 280 Ah High-Rate Flooded Cell

Facts checked against FIAMM's own history page and published reports on the 2017 joint venture, October 2026.

Frequently Asked Questions

What does 7 GroE 175 mean?
It is the DIN 40738 designation; by convention it means seven plates and 175 Ah nominal; the SGL 15 folder capacity is 183 Ah.
What design life does FIAMM state?
25 years for the SGL-SGH series.
How often is topping-up needed?
The folder states a single topping-up in 3 years under float conditions.
What float voltage is recommended?
2.23 volts per cell at 20 °C according to the flooded manual.
How heavy is SGL 15?
26.3 kg with electrolyte, in a 182 x 153 x 415 mm case.