Brand:

Bürkert 238632 Type 6240 Stainless G1/2 Servo Solenoid Valve

Description

Overview

The Bürkert 238632 takes the Type 6240 servo valve to a 12 mm orifice. It is a stainless steel 2/2-way valve, circuit function A and normally closed, with a G½ internal thread, a water Kv value of 2.2 m3/h and a coil for 24 V DC. Where the smaller G¼ valves restrict flow, this article moves several times more water or air through the same style of body. Seven Star LLC is an independent supplier serving Oman and the GCC.

Facts at a glance

Parameter Value
Article Bürkert 238632 (Bürkert Type 6240)
Body Stainless steel 1.4404 / 316L
Port G 1/2 internal thread
Orifice and Kv 12 mm, 2.2 m3/h
Pressure range 0 to 16 bar
Function Servo-controlled, normally closed
Seals FKM / FKM, minus 10 to plus 140 degrees C
Coil Size 42 mm, 24 V DC
DC power 21 W cold, 16 W warm
Switching times, DN 12 Open 20 to 40 ms, close 80 to 100 ms
Nominal pressure 40 bar (standard variant)
Ambient up to 55 degrees C
Viscosity up to 21 mm2/s

What makes Bürkert 238632 the larger size

Everything that grows with the orifice grows here: the Kv value rises from 0.6 to 2.2 m3/h, the coil moves from size 32 to size 42, and switching times lengthen to 20 to 40 ms opening and 80 to 100 ms closing. The 42 mm coil needs more electrical power, roughly 21 W cold on DC compared with 12 W for the 32 mm coil of articles 177800 and 177806, which is relevant when many valves share one 24 V supply. The body is stainless only in this listed article, so there is no brass alternative at G½ in the same chart row.

Where it earns its place

  • Main isolation of instrument air branches and utility air headers.
  • Cooling water and process water lines where a 12 mm seat is needed.
  • Washdown, spray and cleaning circuits in coastal sites.
  • Hydraulic oil and lubrication supply lines on skids.
  • Filling and draining of tanks with neutral liquids.

Hydraulic sizing

Use the Kv value to estimate pressure loss: at 2.2 m3/h of water, the valve passes about 37 litres per minute with a drop of one bar. For compressed air, calculate with the gas flow formulas and remember that servo valves need a minimum differential to open fully. If your line runs at under one bar differential, consider a direct-acting valve instead.

Installation notes

Mount upright where possible, support the G½ pipe, and install a strainer before the valve. The coil accepts voltage deviations of plus or minus 10 percent. Select cable plug Type 2518 for IP65, or Type 2509 on stainless variants for NEMA 4X. Never lift the valve by the coil; handle it by the body.

Service life

Duty is 100 percent, so the valve can stay energised for long periods, but the coil will be warm, and the ambient limit of 55 degrees C needs to be respected. Inspect the seat and piston at planned shutdowns, and replace the seals on signs of swelling or seat leakage.

Calculating flow and power for Bürkert 238632

A quick sizing check for this valve starts from its Kv of 2.2 m3/h. Water at one bar differential flows at that rate, and the loss rises with the square of the flow, so at half the flow the loss falls to a quarter. For clean oils, scale the result with the square root of the density ratio and consider the viscosity limit of 21 mm2/s. If the line medium is compressed air, use the standard gas flow equation with upstream pressure and temperature and keep the differential above the minimum needed for the servo action.

On the electrical side, the 42 mm coil draws 21 W cold on DC. For a panel with a dozen valves that can open at once, that is over 250 W of inrush-level demand on the 24 V rail, so check the power supply capacity and the cable cross sections. A Kick and Drop coil would reduce holding power, but it is a different ordering option and not part of this article.

Installation, commissioning and checks for 238632

Flush the pipework before installing the valve, since weld spatter and scale are the most common causes of early failure. Fit a strainer upstream, preferably with a mesh of around 0.25 mm, and leave room above the coil for service. After wiring, apply the rated voltage and listen for a crisp click; a dull sound suggests low voltage. Raise the line pressure slowly, check the G½ thread for weeping, and cycle the valve ten or twenty times to settle the seals.

Position of 238632 within the Type 6240 range

The Type 6240 data sheet covers far more than this article. Besides the standard 40 bar valves there are high temperature versions with PTFE and PEEK seals reaching 180 degrees C at DN 6, high pressure versions up to 250 bar for hydraulic and car wash duties, a DN 13 steam valve, valves with approval to DIN EN 161 for gas burners, and ATEX or IECEx coil options for zone 1 and zone 2. Article Bürkert 238632 belongs to the plain standard group, which suits neutral media at moderate pressure and temperature. If your duty falls in one of the special groups, the article number will differ even when the thread looks the same, so describe the application when you request a quotation.

For a hazardous area, the coil must also carry the right explosion protection marking; the standard 24 V DC coil of this article is not an ATEX coil, and an explosion-protected variant needs its own code from the ATEX chart of the data sheet.

Compatibility of Bürkert 238632 with the rest of the system

Because the article is a DC version, it works naturally with PLC output cards at 24 V DC, provided each channel can deliver the coil current and the card has flyback protection. Use a relay interface where the output card is limited to small currents. The plug contacts follow DIN EN 175301-803 form A, so any compatible cable plug with the right pin spacing can be fitted; Bürkert Type 2518 is the one mentioned in the data sheet for IP65.

Related items you may also need: Bürkert Type 8681 Control Head for Hygienic Process Valves | Bürkert Type 6026 Direct-Acting 2/2-Way Plunger Solenoid Valve | SMC VK3120-5G-M5 Direct Operated 5-Port Solenoid Valve | All Bürkert products.

Points to confirm for the Bürkert 238632

  • If the Bürkert 238632 is a like-for-like replacement, read the full code from the installed nameplate and compare it with this page.
  • For each Bürkert 238632 request we confirm the exact code and lead time in writing.
  • Dimensions, ratings and connection data for the Bürkert 238632 are in the datasheet attached to this page.

Documents and quotation

The Type 6240 data sheet holding Bürkert 238632 is attached, together with ordering chart rows, materials and dimension drawings. Send your RFQ listing Bürkert 238632, the quantity and the delivery location in Oman or the GCC.

Other Models in the 6240 Range

Seven Star LLC supplies models from the 6240 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Bürkert 177800 Type 6240 Brass G1/4 Servo Solenoid ValveSolenoid ValvesView details
Bürkert 177806 Type 6240 Stainless G1/4 Servo Solenoid ValveSolenoid ValvesView details
Bürkert 238632 Type 6240 Stainless G1/2 Servo Solenoid ValveSolenoid ValvesYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Bürkert 238632 Type 6240 Stainless G1/2 Servo Solenoid Valve Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Bürkert is a German family-owned maker of fluid control systems, headquartered in Ingelfingen, Baden-Württemberg. Christian Bürkert founded the company in 1946, and it is known for solenoid valves, process and control valves, flow and analytical sensors, and mass flow controllers. Its products serve water treatment, hygienic processing, gas handling and laboratory applications.

Seven Star LLC lists Bürkert valves and valve automation devices and supplies Bürkert solenoid valves and spare parts to plants in Oman as an independent supplier.

Bürkert company profile

Founded 1946, by Christian Bürkert
Headquarters Ingelfingen, Germany
Ownership Family-owned
Product families Solenoid valves, angle seat process valves, positioners, flow meters, mass flow controllers

Bürkert types listed on this page

Two types are listed. Type 6026 is a direct-acting 2/2-way plunger solenoid valve, with a stainless steel bellows that separates the medium from the coil, and as a direct-acting valve it switches without needing a pressure difference. Type 8681 is the Bürkert control head that mounts on top of hygienic process valves to pilot the actuator and report valve position to the control system. Control heads of this kind are common in food, beverage and pharmaceutical plants in the GCC.

Ordering Bürkert valves: what we need

The type number alone is not enough. Send the identification number from the label, or else the type with orifice, port connection, body and seal material, coil voltage and frequency, circuit function and pressure range. For a Type 8681 control head add the communication variant and the make and model of the process valve it sits on.

Facts checked against Bürkert's published company history, October 2026.

FAQ

Questions about the Bürkert 238632 Type 6240 Stainless G1/2 Servo

Answers from our engineering team on installation, compatibility and integration.

01What is the orifice size of Bürkert 238632?
The orifice is 12 mm, with a water Kv value of 2.2 m3/h and a G 1/2 internal thread on a stainless steel body.
02Which coil does 238632 use?
It uses the size 42 mm coil in the 24 V DC version, which the data sheet gives as 21 W cold and 16 W warm.
03How fast does Bürkert 238632 switch?
For the DN 12 standard variant the data sheet lists 20 to 40 ms for opening and 80 to 100 ms for closing.
04Is 238632 normally closed?
Yes, it is circuit function A: a servo-controlled 2/2-way valve that is closed when the coil is not powered.
05What pressure range is quoted for 238632?
The ordering chart gives 0 to 16 bar, with FKM seals suitable for medium temperatures from minus 10 to plus 140 degrees C.