- Automation & ControlView all 3,176 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Encoders
- Motor Soft Starters
- CCTV & Security
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Magnetrol
Magnetrol Modulevel P51 Flanged Top Level Controller
Description
Overview
Not every vessel has side nozzles to spare, and not every process allows a cage. The Magnetrol Modulevel P51 solves this by hanging the displacer inside the tank from a flanged top connection. It is a pneumatic level controller from the Modulevel range, converting the rise and fall of a buoyant displacer into a modulated air signal through a magnetic coupling and a range spring.
The catalogue groups it with the P61 and P62 as a flanged top displacer model. Because the controller head sits on top of the vessel and the sensing element is suspended below it, the instrument is useful for large tanks, for open sumps and for interface duties that call for non-standard displacer sizes.
Seven Star LLC is an independent supplier serving Oman and the GCC. Please send your nozzle size, displacer length and control mode for a quotation.
Why choose a top-mounted design
A top-mounted unit has no external piping and no cage valves, so there are fewer leak points. The catalogue calls the top models directly interchangeable with the external cage models, which makes them attractive for retrofit when an existing cage has to be replaced. They are described as used extensively in interface control, where displacers of unusual diameter are needed to match the density difference.
An adjustable stainless steel suspension cable, 8 feet (2.4 m) long as standard, can be ordered under part number 32-3110-001 to hang the displacer at the right depth. Heavy duty versions are available for pressures up to 4047 psig at 100 degrees Fahrenheit. When you order, state the nozzle flange size and class, the vessel pressure and temperature, the process liquid with its specific gravity, and the cable length needed from the nozzle face down to the displacer.
Magnetrol Modulevel P51 specification sheet
| Parameter | Value |
|---|---|
| Process pressure (standard models) | Up to 4047 psig at 100 degrees Fahrenheit (279 bar at 38 degrees Celsius) |
| Temperature, stainless steel cage | Minus 150 to plus 700 degrees Fahrenheit (minus 101 to plus 371 degrees Celsius) |
| Temperature, carbon steel cage | Minus 20 to plus 700 degrees Fahrenheit (minus 29 to plus 371 degrees Celsius) |
| Specific gravity range | 0.11 minimum to 2.20 maximum |
| Interface detection | Minimum 0.10 specific gravity difference between liquids |
| Output signal | 3 to 15 or 6 to 30 psig (proportional and transmitter); 0 to 20 or 0 to 35 psig (differential gap) |
| Supply pressure | Up to 250 psig to the regulator, instrument quality air, regulator set 5 psig above maximum output |
| Air consumption | 3 SCFH at 9 psig output; 6 SCFH at 15 psig output |
| Response | 100 cubic inches of output volume in 3.2 seconds for a 3 to 15 psig rise |
| Level range | Fractional inches up to 10 feet (3 m), limited by displacer length |
| Wetted parts | 316 SS displacer, 304 or 316 SS trim, 316 SS or Inconel spring, carbon steel or 316 SS chamber |
| Housing | IP53 (IP55 on request), NEMA 1, 2, 3 and 3R |
| Control action | Direct or reverse |
| Mounting | Flanged top, displacer suspended in the tank |
| Optional hangar | Adjustable stainless steel cable, 8 ft standard, part number 32-3110-001 |
How Magnetrol Modulevel P51 differs from other Modulevel models
Compared with the P65, which uses an external cage with side connections, the P51 has no chamber and sees the real vessel conditions directly, so the vessel must tolerate the displacer travel and any internal turbulence. The APM-131 variant is threaded and top-mounted for inside-tank use, while the P68 is a side-mounted float design for narrow level ranges. The P51 is the choice for a flanged nozzle on the roof of the vessel with level spans up to 10 feet.
Calibration and set-up
Weights can replace the displacer for bench calibration, or the head can be calibrated in place with the displacer in position. Set the zero and proportional band, choose direct or reverse action, and confirm the output across the range. The visual indicator on the head reads percent span regardless of air supply.
Connect filtered air at the regulated pressure, keeping the regulator 5 psig above the maximum output, and use the filter regulator 06-9501-002 and gauge 06-9501-003 if required.
Typical duties
- Condensate and drip pot control in steam systems.
- Feedwater heater and boiler level regulation.
- Large storage vessel interface monitoring.
- Process vessel level transmission where cages are not practical.
- Scrubber and flash tank level control.
Selecting the displacer and cable
The sensing element hangs on a cable, so the length of the cable and the size of the displacer decide where the measuring range sits in the tank. For a simple level duty a standard displacer is enough, but when two liquids are involved a non-standard diameter may be needed to give adequate buoyancy change across the interface, which is why the catalogue singles out top models for interface control. The specific gravity of both liquids must be given when the order is placed, and the interface must stay inside the displacer length with the displacer submerged at all times.
Think also about what is inside the tank. Agitators, inlet streams and ladders can disturb a hanging displacer or tangle the cable, so the nozzle position should keep the displacer clear. If the vessel is turbulent, discuss the arrangement with the factory before ordering. Surface turbulence is damped by the range spring, but strong currents can still push the displacer sideways.
Maintenance notes
Plan the inspection around outages: lift the head, examine the suspension cable for wear and corrosion, check the displacer for deposits or damage, and record the as-found zero. Inspect the suspension cable at scheduled shutdowns, confirm that the displacer hangs freely, and verify the output and the visual indicator. The controller head can be removed without disturbing the pressure boundary, which lets technicians work without emptying the tank.
Related items you may also need: Magnetrol Z30-2086-003 Echotel 910 Relay PC Board 120 VAC 8A DPDT | Magnetrol 089-6125-001 14-inch Displacer for Pneumatic Modulevel | Magnetrol 089-7905-001 TG1 DIN Rail Housing and Electronics | All Magnetrol products.
Points to confirm for the Magnetrol Modulevel P51
- If the Magnetrol Modulevel P51 is a like-for-like replacement, read the full code from the installed nameplate and compare it with this page.
- For each Magnetrol Modulevel P51 request we confirm the exact code, new or surplus condition and lead time in writing.
- Dimensions, ratings and connection data for the Magnetrol Modulevel P51 are in the datasheet attached to this page.
- The Magnetrol Modulevel P51 belongs to our level switches range and can be delivered to Muscat, Sohar, Duqm and other GCC locations.
- Plants that run the Magnetrol Modulevel P51 on critical service often hold a spare unit in the store.
Documents and quotation
The Magnetrol catalogue 48-110 is attached as the datasheet for the Magnetrol Modulevel P51. Send your RFQ with the part number Magnetrol Modulevel P51, flange size, displacer length and quantity, and we will respond with availability and lead time for Oman and the GCC.
Other Models in the Modulevel Range
Seven Star LLC supplies models from the Modulevel range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Magnetrol Modulevel P65 Pneumatic Level Controller | Level Switches | View details |
| Magnetrol Modulevel P51 Flanged Top Level Controller | Level Switches | You are viewing this model |
Datasheets & Documents
- Datasheet Magnetrol Modulevel P51 Flanged Top Level Controller Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Magnetrol is the American level and flow measurement specialist known for the Eclipse guided wave radar, Pulsar radar transmitters and the float and displacer switches that guard boilers and vessels. It was founded in 1932, is based in Aurora, Illinois, and has been part of AMETEK since 2021.
Seven Star LLC is an independent supplier in Muscat. We list Magnetrol level transmitters and level and flow switches, and supply them to refineries, gas plants and utilities in Oman and the GCC by complete model number.
Magnetrol company profile
| Established | 1932, USA; headquarters in Aurora, Illinois |
|---|---|
| Ownership | Acquired by AMETEK in March 2021 and now part of its Electronic Instruments Group |
| Product families | Guided wave radar, non-contact radar, displacer and buoyancy transmitters, ultrasonic and thermal dispersion switches, float switches and magnetic level indicators (through its Orion Instruments brand) |
| Applications | Separators, storage tanks, boilers and feedwater heaters, interface measurement, pump protection and flow detection |
Milestones
- 1932: The first mechanical buoyancy level switch; the company grows into Magnetrol, based in Aurora, Illinois.
- 1998: Eclipse Model 705, a loop-powered guided wave radar transmitter for industrial liquid level, according to Magnetrol.
- 2021: AMETEK acquires Magnetrol on 29 March.
Magnetrol products we list
| Model | Principle | Typical use |
|---|---|---|
| Eclipse 706 | Guided wave radar | Level and interface in separators, chambers and boiler drums, unaffected by changing density |
| Pulsar R80 | 80 GHz FMCW radar | Narrow-beam non-contact level in tanks with internals and in solids |
| Pulsar R86 | 26 GHz radar | Non-contact level in process and storage vessels |
| Pulsar R96 | 6 GHz radar | Non-contact level where vapour, foam or condensation are present |
| E4 Modulevel | Displacer | Level and interface in high-pressure, high-temperature vessels, often replacing older torque tube units |
| Echotel 961/962 | Ultrasonic gap switch | High and low level alarms and pump protection |
| Thermatel TD1/TD2 | Thermal dispersion switch | Flow and no-flow detection and level switching for liquids and gases |
Guided wave radar sends pulses down a probe and times the reflection from the surface, so dust, vapour and changes in density don't affect the reading. That is why it often replaces displacers on separators and chambers. Non-contact radar suits tanks where nothing should touch the product, and a higher frequency gives a narrower beam that avoids tank internals.
Where Magnetrol instruments are used
In Oman and the GCC, Magnetrol transmitters and switches measure level in production separators, slug catchers, storage tanks, boiler drums and feedwater heaters, and protect pumps in oil and gas, refining, petrochemical, power and water plants.
Ordering Magnetrol instruments: what we need
Send the complete model number from the nameplate. On Magnetrol instruments every digit sets the electronics, the probe or antenna, the process connection and the approvals. For a new application, send the medium, the dielectric constant if known, the measuring range, the pressure and temperature, the process connection and the hazardous area classification.
Facts checked against Magnetrol and AMETEK company information, October 2026.
Browse Magnetrol products by category: Level Transmitter.
FAQ
Questions about the Magnetrol Modulevel P51 Flanged Top Level Controller
Answers from our engineering team on installation, compatibility and integration.
01How is the Magnetrol Modulevel P51 mounted?
It mounts on top of the vessel through a flange, with the displacer suspended inside the tank rather than in an external cage.
02What is the suspension cable length for the Modulevel P51?
The standard adjustable stainless steel cable is 8 feet (2.4 m) long and is ordered as a separate item under part number 32-3110-001.
03What level range can the Modulevel P51 cover?
The level range is limited only by displacer length, from fractions of an inch up to 10 feet (3 m).
04Is the Modulevel P51 interchangeable with cage models?
The catalogue states that top mounting models are directly interchangeable with the external cage models.
05What control actions are available on the Modulevel P51?
The head can be proportional, transmitter, proportional plus integral or differential gap, and direct or reverse acting.


















Reviews