Brand:

Victaulic Series 713 Swing Check Valve DN50 to DN100

Description

Overview

Check valves protect pumps and equipment by stopping reverse flow, and the Victaulic Series 713 does so in a compact grooved package. It is a swing check valve with a stainless steel clapper, available in sizes 2 to 4 inch, DN50 to DN100, with ductile iron body and grooved ends. Seven Star LLC is an independent supplier serving Oman and the GCC. This page is based on publication 08.54 and explains the rating, materials and installation rules in everyday language.

Ratings

The pressure class depends on size: up to 750 psi, which is 5170 kPa, for the 2 1/2 to 4 inch sizes, and up to 1000 psi, 6895 kPa, for the 2 inch size. The operating temperature range is set by the gasket choice. Grade EHP EPDM, with red and green stripes, covers minus 30 to plus 250 degrees F, minus 34 to plus 120 degrees C, for water and many chemicals, and Grade T nitrile covers minus 20 to plus 180 degrees F, minus 29 to plus 82 degrees C for oil-related services. The publication notes that the valve is not recommended for vertical installations.

Technical data of Victaulic Series 713

Item Value
Product Swing check valve, Victaulic Series 713
Sizes 2 to 4 inch / DN50 to DN100
Pressure class up to 750 psi / 5170 kPa for 2 1/2 to 4 inch; up to 1000 psi / 6895 kPa for 2 inch
Body ductile iron ASTM A536 grade 65-42-12, black enamel
Optional coating fusion bonded epoxy
Clapper stainless steel ASTM A351 grade CF8M
Clapper pin type 316 stainless steel
Torsion spring type 302/304 stainless steel in 2 1/2 to 4 inch; none in 2 inch
Seat gasket grade EHP EPDM or grade T nitrile
Ends OGS grooved; EndSeal groove optional
Pipe material carbon steel

How Series 713 differs from other Victaulic check valves

Victaulic offers several check valve types. The Series 716 is a spring-assisted silent check in a different body, and the 717 is a FireLock valve for fire protection systems. The 713 is a swing type with a stainless steel clapper and, in sizes 2 1/2 inch and larger, a torsion spring that helps the clapper close promptly. The 2 inch valve has no torsion spring, so it relies on gravity and flow reversal. That is a real difference when choosing between sizes, since the 2 inch valve should only be installed horizontally and may close more slowly.

Where it is used

Typical uses are pump discharge lines, chilled and hot water circuits, condensate return and general utility water. In Oman and the GCC the compact grooved format is attractive for plant rooms where space is tight. The stainless steel clapper resists corrosion in warm water, but the valve should not be used in steam. Select nitrile seals if the fluid carries oil, and EPDM if it is hot water within the stated range.

Selection list

  • Nominal size 2, 2 1/2, 3 or 4 inch.
  • Gasket: grade EHP EPDM for water, grade T nitrile for oil-related fluids.
  • Horizontal installation only; not recommended vertically.
  • Coating: standard black enamel or optional fusion bonded epoxy.
  • Check the working pressure of the size against your system.

Installation

Mount the valve with the flow arrow pointing downstream, using grooved couplings at each end. Allow clearance so that the access cap can be removed in service. Install in a horizontal run with the access cap on top, support the pipe on both sides and flush the line before commissioning to remove debris that could hold the clapper open.

Maintenance

The access cap permits inspection of the clapper and seat without removing the valve from the line. Look for wear on the seat gasket, scoring on the clapper and a weak or damaged torsion spring. Replace the seat gasket with the same grade, and follow the manufacturer’s instructions for the closure bolts.

Requesting a quotation for Victaulic Series 713

Send us the size, gasket grade, coating and quantity.

Choosing a check valve for pump systems

A pump check valve has two jobs: to open easily when the pump runs and to close quickly when it stops. If it closes slowly, the flow reverses before the clapper reaches the seat, and the resulting slam can create pressure surges that damage pipes and instruments. Swing check valves like the 713 are simple, have low flow resistance and cause little pressure loss when open, but they depend on the correct installation and on flow conditions. The torsion spring found in the 2 1/2 to 4 inch sizes shortens the closing time, which lowers the risk of slam in normal systems. For systems with fast flow reversals or with a risk of strong surges, a spring-assisted silent check may be a better choice.

Place the valve at a distance from the pump discharge so that turbulent flow does not make the clapper flutter. A few pipe diameters of straight run upstream is a common rule of thumb. Avoid putting the valve directly after a throttling valve or an elbow, because uneven flow causes vibration and early wear of the seat. In systems with several pumps in parallel, give each pump its own check valve so that one pump cannot be driven backward by the others.

Because the body is fully ductile iron with a stainless steel clapper and pin, the valve resists the corrosion that usually damages inexpensive check valves in warm water. If your fluid contains abrasive particles, plan strainers upstream, as grit on the seat is the most frequent cause of leakage. Also remember to flush new pipework before start-up, since welding debris, jointing compound and construction dirt will otherwise collect at the seat and clapper during the first weeks of operation.

Record the valve position, the direction of flow and the installation date on the maintenance sheet, and include the check valve in the list of items inspected whenever the pump is overhauled.

Related items you may also need: Victaulic Style 07 Zero-Flex Rigid Coupling | Victaulic Style 77 Standard Flexible Coupling | Victaulic Series 761 Vic-300 MasterSeal Butterfly Valve | All Victaulic products.

Victaulic Series 713 ordering checklist

  • When the Victaulic Series 713 replaces an installed unit, check the existing nameplate against the code on this page before ordering.
  • Every enquiry for the Victaulic Series 713 is answered with a written confirmation of the code and expected lead time.
  • Use the attached datasheet to check the Victaulic Series 713 ratings, dimensions and connection details against your drawings.
  • We supply the Victaulic Series 713 as part of our check valves range to plants in Oman and the GCC.
  • For critical duty, keeping one Victaulic Series 713 as a site spare shortens downtime after a failure.

Details needed to quote the Victaulic Series 713

The Victaulic Series 713 is a product style that is supplied in many sizes and material combinations, so a single order line is defined by the details below rather than by the style name alone.

  • Nominal size of the Victaulic Series 713 and the pipe outside diameter it must fit (IPS or metric).
  • Pipe end preparation: roll grooved, cut grooved or plain end, and the pipe material.
  • Body and trim materials, seat or seal elastomer grade, and the fluid and temperature it must handle.
  • Working pressure required and any approval needed for the service, for example fire protection listings.
  • Operator or accessory options, such as lever, gear operator, tamper switch or test and drain fittings, where the valve offers them.

Send these details, or the Victaulic part number from an existing installation or drawing, and the quotation will confirm the exact orderable item and the matching gasket.

Documents and quotation

The manufacturer’s publication 08.54 is attached. Send your RFQ with Victaulic Series 713, the size, quantity and delivery location in Oman or the GCC.

Other Models in the Victaulic Valve Range

Seven Star LLC supplies models from the Victaulic Valve range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Victaulic Series 726 Vic-Ball Valve, Grooved, DN40-DN150Ball ValvesView details
Victaulic Series 713 Swing Check Valve DN50 to DN100Check ValvesYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Victaulic Series 713 Swing Check Valve DN50 to DN100 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Victaulic is an American maker of grooved mechanical pipe joining systems, valves and fire protection products, headquartered in Easton, Pennsylvania. Its grooved coupling was patented in 1919 by Ernest Tribe, and the name combines 'victory' and 'hydraulic'. Victaulic is privately held and reinvests in its own plants and technology.

Seven Star LLC lists Victaulic couplings and butterfly valves, among them the Style 107N QuickVic rigid coupling, and supplies Victaulic couplings and fittings for mechanical, utility and process piping in Oman on inquiry.

Victaulic company profile

Origins 1919, grooved coupling patent
Name From 'victory' and 'hydraulic'
Headquarters Easton, Pennsylvania
Ownership Privately held
Product families Style 07, 77 and 107N grooved couplings, Vic-300 MasterSeal butterfly valves, FireLock fire protection valves and sprinklers, grooved fittings and tools

Milestones

  • 1919: The grooved Victaulic coupling is patented.
  • 2019: Victaulic marks 100 years.

Victaulic Style 107N QuickVic couplings

The Style 107N is a rigid coupling for roll-grooved or cut-grooved carbon steel and stainless steel pipe in sizes from 2 to 12 inches (DN 50 to DN 300). Victaulic rates it from full vacuum up to 750 psi (5171 kPa), but the working pressure of a given joint depends on pipe material, wall thickness and size. The housing has an angled bolt pad that makes the joint rigid, and a galvanized finish is optional.

Where Victaulic couplings are used and what to send

The manufacturer names HVAC, utility and process piping as the applications for this style. For an inquiry, send the style number, nominal size, pipe material and schedule, the fluid and temperature so the gasket grade can be checked, the housing finish and the quantity. GCC consultants often ask for the submittal sheet, which we provide from the manufacturer.

Facts checked against Victaulic's 100-year innovation timeline, October 2026.

Victaulic products we list

Family Examples
Pipes & Fittings Style 07 Zero-Flex Rigid Coupling, Style 107N QuickVic Rigid Coupling, Style 77 Standard Flexible Coupling
Fire Fighting FireLock Series 705 Butterfly Valve
Butterfly Valves Series 761 Vic-300 MasterSeal Butterfly…

FAQ

Questions about the Victaulic Series 713 Swing Check Valve DN50 to DN100

Answers from our engineering team on installation, compatibility and integration.

01What is the Victaulic Series 713?
It is a grooved swing check valve with a stainless steel clapper in sizes 2 to 4 inch, DN50 to DN100.
02What is the pressure rating of the Series 713?
Up to 750 psi for the 2 1/2 to 4 inch sizes and up to 1000 psi for the 2 inch size, according to publication 08.54.
03Does the Victaulic Series 713 have a torsion spring?
Yes in sizes 2 1/2 to 4 inch, made of type 302/304 stainless steel; the 2 inch size has no torsion spring.
04Can the Series 713 be installed vertically?
The publication notes that it is not recommended for vertical installations.
05Which gaskets are available for the Series 713?
Grade EHP EPDM for water and chemicals and grade T nitrile for petroleum products and oils, each with a stated temperature range.