Autonics TK4S-14RR 48×48 Heating Cooling PID Controller

Description

Overview

Some processes must be heated and cooled by the same controller, for example an injection moulding barrel that needs a heater and a fan, a chiller loop or a water bath that cools after overshoot. The Autonics TK4S-14RR handles this with two relay outputs, one for heating and one for cooling, in a compact 48 x 48 mm DIN case. Its PID algorithm treats the two outputs as one control loop, so heating and cooling do not fight each other. Seven Star LLC is an independent supplier serving Oman and the GCC.

What the type name Autonics TK4S-14RR means

TK4 is the four-digit family, and S is the 48 x 48 mm case. The first digit after the dash, 1, gives alarm 1 as the optional output. Then 4 is the 100 to 240 V AC supply. The first R is the relay used for output 1, and the second R means OUT2 is a heating and cooling relay output. A reader who sees N in that last place knows that there is no second control output; R and C add one, as relay or as selectable current or SSR drive.

Data table for Autonics TK4S-14RR

Item Data
Front size 48 x 48 mm, panel cut-out 45 mm square
Supply 100 to 240 V AC 50/60 Hz, 90 to 110 percent
OUT1 (heating) Relay 250 V AC 3 A, 30 V DC 3 A, 1a
OUT2 (cooling) Relay 250 V AC 3 A, 30 V DC 3 A, 1a
Alarm 1 Relay 250 V AC 3 A, 1a
Thermocouple inputs K, J, E, T, B, R, S, N, C, G, L, U and Platinel II
RTD inputs Cu50, Cu100, JPt100, DPt50, DPt100, Nickel120
Analog inputs 0-10 V, 0-5 V, 1-5 V, 0-100 mV, 0-20 mA, 4-20 mA
Sampling period 50 ms
Control modes ON/OFF, P, PI, PD, PID; heating, cooling or heating and cooling
Display accuracy PV plus or minus 0.3 percent or plus or minus 1 degree C, whichever is greater, plus 1 digit, at 23 degrees C plus or minus 5
Control cycle 0.1 to 120.0 seconds for relay output
Hysteresis 0.1 to 100.0 degrees (thermocouple, RTD)
Relay life 5 million mechanical, 100,000 electrical (OUT1 and OUT2)
Ambient minus 10 to plus 50 degrees C
Protection IP65 front panel
Weight about 105 g, about 150 g packaged

How the Autonics TK4S-14RR differs from other TK4S variants

The TK4S-14RN has the same case and alarm but no second control output, so it can only heat or only cool. The Autonics TK4S-14RR adds the cooling relay, and when you configure it for heating only or cooling only, the spare OUT2 relay can serve as alarm output 3. Other TK4S codes change option 1 to 2, R, T, A, B or D to add a second alarm, a 4 to 20 mA transmission output, RS485 communication, or digital inputs. Note that in the TK4S-D version the OUT2 terminal is used for a digital input and therefore is not available as a cooling output.

Heating and cooling in one loop

In heating and cooling mode, the controller computes a single manipulated value. The manipulated value is shared between output 1 for heating and output 2 for cooling, so only one of the two works at a time. This is valuable for processes with exothermic reactions or high thermal inertia, where heat input must sometimes be actively removed. The PID constants can be found by auto tuning, indicated by a flashing AT lamp, and they are stored for ten years in non-volatile memory. Because both outputs are relays, the control cycle should not be too short: the electrical life of 100,000 operations is reached in a few months if a relay is switched every second.

Where it is used

In Oman and the wider GCC, heating and cooling control is requested for plastics and packaging machines, laboratory incubators, cooling water skids, pharmaceutical and food processes, and climate chambers. The 48 mm size leaves room on a crowded panel, and the IP65 front gives protection against dust and water spray on production floors. Remember that the rated maximum ambient is 50 degrees C, so provide ventilation in panels exposed to summer heat.

Wiring guidance

The supply and relay wiring should use AWG 20 or heavier wire, and the terminals are tightened to 0.74 to 0.90 N m. The sensor connects to the input terminals with its polarity checked, and RTDs use three wires of equal length and gauge, with a line resistance of 5 ohm or less per line. Do not wire to unused terminals. Relay contacts are rated for resistive loads only, so for heaters above 3 A or for contactor coils with high inrush, use an external contactor or solid state relay.

Operating the front keys

The MODE key moves between parameter groups, the arrow keys change values, and the A/M function can change between automatic and manual operation, shown by the MAN lamp. The OUT1 and OUT2 lamps show which relay is on, and AL1 shows the alarm. In run mode the red display shows PV and the green display shows SV, while in setting mode the red display shows the parameter name. Lock the keys after commissioning to prevent unintended changes.

Service tips

If the display flashes OPEN, the sensor has been disconnected, and the output follows the sensor error value that you configured. Re-check connections and sensor continuity first. Over time, replace the controller when relay contacts become noisy or stick. Keep spare units of the same code on the shelf for production-critical heaters, and record the PID values found by auto tuning so that a replacement unit can be loaded with the same constants and the process restored within minutes of the swap.

Related items you may also need: Autonics E40S6-2500-6-L-5 Rotary Encoder Incremental | Omron E3Z-T62 Photoelectric Sensor 30 m through-beam | SICK VL18-4P3240 M18 Metal Retro-Reflective Sensor, 3 m | All Autonics products.

Documents and quotation

The TK series product manual that covers the Autonics TK4S-14RR is attached with the ordering table, input ranges, connection diagrams and dimensions. Send an RFQ with the part number Autonics TK4S-14RR, quantity and delivery location in Oman or the GCC.

Other Models in the TK Range

Seven Star LLC supplies models from the TK range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Autonics TK4S-14RN PID Temperature Controller 48×48 mmControllers & Data AcquisitionView details
Autonics TK4M-14RN 72×72 PID Temperature Controller RelayPhotoelectric SensorsView details
Autonics TK4S-14RR 48×48 Heating Cooling PID ControllerPhotoelectric SensorsYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Autonics TK4S-14RR 48x48 Heating Cooling PID Controller Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Autonics is a South Korean maker of sensors and controllers, founded in 1977 as a small engineering business making controllers for looms. It took the Autonics name in 1988 and opened a new corporate headquarters in Busan in 2014. Autonics makes proximity and photoelectric sensors, rotary encoders, temperature controllers, counters, timers and stepper motor systems, with factories in Busan and Yangsan.

Seven Star LLC lists the Autonics E40S6-2500-6-L-5 incremental rotary encoder and supplies Autonics sensors and control devices in Oman and the GCC.

Autonics company profile

Founded 1977, South Korea
Current name Autonics, since 1988
Headquarters Busan, South Korea
Factories Busan and Yangsan
Product families E40 and E50 rotary encoders, PR proximity sensors, BJ photoelectric sensors, TK temperature controllers

Milestones

  • 1977: The company is founded.
  • 1988: Renamed Autonics Corporation.
  • 2014: Opens its Busan headquarters.

Reading the Autonics E40S encoder code

E40S is the 40 mm diameter shaft-type incremental encoder, and the 6 that follows is the 6 mm shaft. 2500 is the resolution in pulses per revolution. The next 6 means six output signals: A, B and Z with their inverted signals. L is a line driver output and the final 5 is a 5 V DC supply. The same 40 mm body is made in hollow shaft form as the E40H and E40HB series.

Where Autonics encoders are used

Servo and spindle feedback, conveyor length measurement, packaging and printing machines.

Ordering Autonics encoders: what we need

Send the complete model string from the label. If it is worn off, give the body and shaft diameter, pulses per revolution, output type, supply voltage and cable or connector style.

Facts checked against Autonics corporate profiles, October 2026.

FAQ

Questions about the Autonics TK4S-14RR 48×48 Heating Cooling PID

Answers from our engineering team on installation, compatibility and integration.

01What does the last R mean in Autonics TK4S-14RR?
It means OUT2 is a heating and cooling type relay output, so the controller has two relays for simultaneous heating and cooling control.
02What is the panel size of the Autonics TK4S-14RR?
It is a 48 x 48 mm DIN controller that needs a 45 mm square panel cut-out and weighs about 105 g.
03What supply does the Autonics TK4S-14RR need?
The code digit 4 means 100 to 240 V AC at 50/60 Hz, with a permissible voltage range of 90 to 110 percent of the rating.
04Can the Autonics TK4S-14RR drive an SSR?
This code has relay outputs on both OUT1 and OUT2, so for SSR drive you would choose a code with S or C in the output position instead.
05What happens when the sensor of the Autonics TK4S-14RR breaks?
The display flashes OPEN every 0.5 seconds, and the control output goes to the value set in the sensor error MV parameter.