Brand:

Finder 78.J1.1.230.2402 24 V DC 75 W DIN Rail Power Supply

Description

Overview

The Finder 78.J1.1.230.2402 is a compact DIN rail switch mode power supply that turns a universal AC or DC line into a regulated 24 V DC rail at 3.2 A, or 77 W. It is the smallest member of the single-phase industrial group inside the Finder 78 series, and it is the only code that uses the J power letter. Panel builders pick it when a PLC rack, a few relays, sensors and a small HMI need a clean control supply and a 120 W unit would be oversized. Seven Star LLC is an independent supplier serving Oman and the GCC.

Decoding the part number

Each block in 78.J1.1.230.2402 carries meaning. The J selects the 75 W output class. The first 1 declares a single-phase supply, the second 1 an AC/DC input with DC output, and 230 identifies the wide input of 100 to 240 V AC or 220 V DC. In the last group, 24 is the output voltage, 0 marks a standard single-stage design without power factor correction, and 2 means an embedded fuse plus an output voltage regulator. A trailing 4 would add a positive logic contact, which this code does not have.

Key features of Finder 78.J1.1.230.2402

  • Output adjustable between 24 and 28 V DC, useful for long cable runs
  • Peak current capability of 4.16 A for 5 ms and a short-circuit peak of 30 A for 100 ms
  • Short circuit protection with hiccup auto-recovery and thermal protection with auto shutdown
  • Overvoltage protection by varistor
  • Parallel connection for more current or redundancy, with an external diode
  • Compliant with IEC/EN 62368-1 and UL 61010, mounted on a 35 mm rail to EN 60715

Electrical data for Finder 78.J1.1.230.2402

Parameter Value
Output voltage and current 24 V DC, 3.2 A at minus 20 to plus 50 degrees C and 230 V AC
Rated power 77 W
Output adjustment 24 to 28 V DC
Voltage variation, no load to full load less than 2 percent
Ripple at full load 120 mV
Hold-up time at full load 12 ms at 115 V AC; 60 ms at 230 V AC
Nominal input 100 to 240 V AC (50/60 Hz); 140 to 338 V DC
Operating input range 90 to 264 V AC; 127 to 370 V DC
Maximum input current at 230 V AC 0.9 A
Inrush current peak at 230 V AC 35 A
Efficiency at 230 V AC 87.5 percent
Stand-by consumption 0.7 W
Start-up delay 1200 ms
Dielectric strength 3000 V AC input to output; 2000 V AC input to earth
Ambient range minus 20 to plus 70 degrees C with derating; IP 20

How the Finder 78.J1.1.230.2402 differs from other 78 series variants

The nearest sibling, the 78.W1.1.230.2402, delivers 5 A and 120 W with 88 percent efficiency and an input draw of 1.3 A, whereas the Finder 78.J1.1.230.2402 stops at 3.2 A and 77 W with a lower 0.9 A draw. Its stand-by power is the same 0.7 W, but its power loss to the environment is only 10.5 W against 16.4 W for the W1. The X1 code reaches 240 W and 35.9 W loss and the Y1 reaches 480 W. Hold-up also differs: the Finder 78.J1.1.230.2402 holds 60 ms at 230 V AC, far longer than the 16 ms of the 120 W unit, so it rides through short mains dips better when lightly loaded.

Where the Finder 78.J1.1.230.2402 fits in Oman and GCC installations

Typical homes for a 24 V, 3.2 A rail are compact control panels in water pumping stations, remote telemetry cabinets, packaged compressor panels, small fire and gas interface boxes and building automation boards. The wide input tolerates the voltage swings seen on remote feeders, while the DC input range lets the same module run from a 220 V DC battery bus in a substation panel. For hot cabinets, remember that the full current rating applies up to 50 degrees C and that output current must be derated at higher temperature.

Mounting, wiring and sizing

Snap the unit on the rail with space above and below for convection, since hot surfaces are marked on the top. Terminals accept a single 4 mm squared conductor or two of 2.5 mm squared, with a tightening torque of 0.8 Nm and a strip length of 8 mm. Size the supply so the steady load is no more than about 80 percent of 3.2 A and use the peak capability for relay and motor starter inrush. Set the output to 24 V first, then raise toward 28 V only to compensate for voltage drop in long cables.

Maintenance and fault finding

The unit has a DC OK indication. When the supply goes into hiccup mode, look for a short or an overload downstream, remove the load and let it restart. Check terminal torque at each shutdown, clean dust from the ventilation slots and verify the output with a meter after panel work. Keep a spare, because the embedded input fuse is not meant to be replaced in the field.

Ordering notes

Quote the full code Finder 78.J1.1.230.2402, since neighbouring codes differ in power, input class or contact options. Redundancy modules and diodes for paralleling are separate items, and we can quote them with the supply.

Related items you may also need: Finder 22.32.0.230.1340 25 A 2 NO Modular Contactor | Finder 78.Y3.1.440.2414 24 V 480 W Three-Phase Power Supply | Finder 7P.04.8.260.1025 Type 1+2 Three-Phase Surge Protection Device | All Finder products.

When preparing an enquiry for the Finder 78.J1.1.230.2402, send the complete part number exactly as printed on the nameplate or in your bill of materials, the quantity you need, the supply voltage and phase of the installation, the required delivery location and any documentation you need to accompany the order. Having these details in the first message allows the sales team to check availability, confirm the configuration against the datasheet and respond with a quotation without additional clarification rounds.

Documents and quotation

The series datasheet covering the Finder 78.J1.1.230.2402 is attached to this page, including ordering information, derating curves and wiring diagrams. Please send your RFQ with Finder 78.J1.1.230.2402, the quantity and your delivery location in Oman or the GCC.

Datasheets & Documents
  • PDF Datasheet Finder 78.J1.1.230.2402 24 V DC 75 W DIN Rail Power Supply Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Finder is an Italian manufacturer of relays, timers and other electromechanical and electronic devices for industry and buildings. It was founded in 1954 by Piero Giordanino, who had patented a step relay in 1949, and it is headquartered in Almese, Piedmont, where most of its manufacturing still takes place. Finder is owned and run by the Giordanino family.

Seven Star LLC is an independent supplier in Muscat. We list Finder relays, power supplies and protection devices for control panels, building services and machine automation in Oman and the GCC.

Finder company profile

Founded 1954, Italy, by Piero Giordanino
Headquarters Almese, Piedmont, Italy; more than 70 % of manufacturing is done there
Ownership Giordanino family
Range More than 14,000 product types, according to the company
Product families Industrial relays (series 40, 46, 55, 60), interface relay modules (34, 38, 39), timers (80, 85), monitoring relays (70, 71), surge protection (7P), switch-mode power supplies (78), thermostats and panel fans

Milestones

  • 1949: Piero Giordanino patents his first step relay.
  • 1954: Finder is founded.
  • 1965: The plant in Almese opens.
  • 1966: The Series 60 industrial relay is launched.

Finder product series

Relays include the 46.61 miniature industrial relay, the 62.32 power relay with magnetic blow-out for DC loads, the 38.51 relay interface module and the 7S forcibly guided safety relay. Control relays include the 72.01 liquid level control relay and the 80.01 multi-function modular timer, and the 22.32 modular contactor switches loads up to 25 A.

Power supplies include the 78.12, 78.36, 78.W1, 78.Y1 and three-phase 78.Y3 DIN rail units from 12 W to 480 W, and surge protection includes the 7P.04 Type 1+2 and 7P.45 Type 2 three-phase devices.

Where Finder devices are used

Control panels for machines, pumps and HVAC, distribution boards in commercial and residential buildings, water tank and well level control, lighting control and the protection of electrical installations against surges.

Finder products we list

Family Examples
Automation Accessories 38.51.7.024.0050 24 V DC 6 A Relay Inter…, 46.61.9.024.0040 16 A Miniature Industri…, 62.32.9.024.4800 16 A Magnetic Blow DC P…, 72.01.9.024.0000 Liquid Level Control Re…, 7P.04.8.260.1025 Type 1+2 Three-Phase Su…, 7P.45.8.275.1020 Type 2 Three-Phase Surg…, 7S.23.9.024.0210 Forcibly Guided Safety…, 80.01.0.240.0000 Multi-Function Modular…
Power Modules 78.12.1.230.2400 24 V 12 W DIN Rail Powe…, 78.36.1.230.2402 24 V 36 W Modular Power…, 78.W1.1.230.2402 24 V 120 W DIN Rail Pow…, 78.Y1.1.230.2412 24 V 480 W Single-Phase…, 78.Y3.1.440.2414 24 V 480 W Three-Phase…
Contactors & Overload Relays 22.32.0.230.1340 25 A 2 NO Modular Conta…

Ordering Finder products: what we need

Quote the complete ordering code, for example 62.32.9.024.4800, which includes coil voltage and contact variant, together with the quantity, the supply voltage and frequency and any approvals the project requires. With that information the matching Finder version can be confirmed against the datasheet before a quotation is issued.

Facts checked against Finder's own company pages (findernet.com), October 2026.

FAQ

Questions about the Finder 78.J1.1.230.2402 24 V DC 75 W DIN Rail Power

Answers from our engineering team on installation, compatibility and integration.

01What output does the Finder 78.J1.1.230.2402 provide?
It gives 24 V DC at 3.2 A (77 W), adjustable between 24 and 28 V DC, from an input of 100 to 240 V AC or 140 to 338 V DC.
02Can the Finder 78.J1.1.230.2402 be paralleled?
Yes. The datasheet lists parallel operation for more current or redundancy when an external diode is used on each output.
03What is the difference between 78.J1 and 78.W1?
The J1 is rated 3.2 A and 77 W with 87.5 percent efficiency, while the W1 provides 5 A and 120 W at 88 percent and draws 1.3 A instead of 0.9 A.
04What does the 2 at the end of 2402 mean?
The final digit 2 means the supply includes an embedded fuse and an output voltage regulator, but no positive logic contact, which the digit 4 would add.
05What temperature range applies to the 78.J1.1.230.2402?
Full current is available from minus 20 to plus 50 degrees C at 230 V AC, and the ambient range extends to plus 70 degrees C with derating.