Brand:

MTL MTL4573 THC/RTD Temperature Converter

Description

One converter for many sensor types: the MTL4573

Temperature measurement projects often involve a mixture of thermocouples and RTDs. The MTL MTL4573 is a single-channel, software-configured converter that takes either kind of sensor and produces a 4-20 mA signal into 600 ohm. It sits on the MTL4500 backplane, so safe-area wiring and power come through the backplane connector and only the sensor wires are plugged into the front.

MTL4573 sensor and accuracy data

Model MTL4573
Channels one
Thermocouples J, K, T, E, R, S, B, N (BS EN 60584-1:1996), XK (GOST); minimum span 3 mV
mV input -75 to +75 mV, minimum span 3 mV
RTDs Pt100/500/1000 (BS EN 60751:2008), Cu-50, Cu-53, Ni100/500/1000
RTD wiring 2, 3 or 4 wire
Resistance 0 to 400 ohm, minimum span 10 ohm
RTD excitation 200 microamps
CJC error 1.0 degree C or less, selectable on or off
Input accuracy 15 microvolts or 0.05 percent; Pt100 80 milliohm
Output accuracy 11 microamps
Output 4 to 20 mA into 600 ohm
Response time typically 500 ms
Supply current 50 mA at 24 V (20 mA signal)
Dissipation 1.2 W at 24 V
LEDs green EBD/power/status; yellow alarm

Early burnout detection and out-of-range options on the MTL4573

Early burnout detection is the most distinctive item. With it selected, the module indicates when the loop resistance of a thermocouple increases by more than 50 ohm, typically a sign of a corroding or loosening junction. A maintenance team can then act before the measurement is lost. The output can follow the NAMUR NE43 characteristic so that the control system distinguishes failure currents from valid measurements.

Maximum lead resistance for thermocouples is 600 ohm with the safety drive enabled, and above 10 kilohm when it is disabled.

MTL4573 compared with MTL5573 and MTL4576 types

The DIN-rail twin is the MTL5573 already common in the market. The MTL4573 is the backplane version for system-vendor racks. The two-channel MTL4576-RTD and MTL4576-THC give double density but specialise in one input kind and limit load to 300 ohm. Choose the MTL4573 when a loop has a mixed sensor population, when 600 ohm of output burden is needed, or when 4-wire RTD connection is required.

For a plain resistance repeater without 4-20 mA conversion the MTL4582B is the alternative.

Applications in Oman and GCC plants

Process heaters, reformer tubes, turbine exhausts, motor windings and storage tanks all offer temperature points, and in a project they are rarely all one sensor type. A single converter model simplifies engineering, spares and training. With one part number a plant can cover Pt100 on tanks, type K on heaters and type S or B on high-temperature points.

The wide thermocouple list including R, S and B reaches the high-temperature furnaces found in metals, glass and petrochemical crackers.

Installation and configuration of the MTL4573

Plug the HAZ-CJC connector on terminals 1 to 3 when a thermocouple is used, since it carries an integral CJC sensor. Insert the module in its backplane slot, connect the PCL45USB lead in the safe area and run PCS45 to choose the sensor, range, burnout action and output characteristic. Then verify with a calibrator: a Pt100 over a 250 ohm span should give about 0.1 percent of span accuracy and 1.0 microamp per degree C drift, according to the datasheet example.

For crimped connectors, use the manufacturer-recommended 12 mm ferrule length and 14 mm wire trim.

Maintenance of the MTL4573

Save the configuration to disk for every loop. A replacement module takes the same file in minutes. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Setting up a typical loop on the MTL4573

Example one: a Pt100 on a storage tank, ranged 0 to 100 degrees C. The span is about 38.5 ohm, which is within the 10 ohm minimum. The 80 milliohm input accuracy then equals about 0.2 percent of span, and the 11 microamp output term adds about 0.07 percent, giving roughly 0.3 percent in total. Using a three-wire connection removes most cable resistance error.

Example two: a type K thermocouple on a process heater, ranged 0 to 800 degrees C. The input span is about 33 mV, so the 15 microvolt floor is tiny, about 0.05 percent of span. The dominant term is the cold-junction error of up to 1.0 degree C, which is why the integral HAZ-CJC plug and proper extension cable are specified.

Example three: a 4-wire Pt1000 on a precision process. Four-wire connection eliminates lead resistance entirely, and the 10 to 1000 ohm span permitted for Pt and Ni sensors gives good resolution. Because the converter output can drive up to 600 ohm, long cable runs to a remote controller do not exhaust the loop compliance.

In all cases, the response time of about 500 ms is perfectly adequate for temperature, and the 1.2 W dissipation at 24 V is modest.

Documentation completes the picture. Print the PCS45 configuration report and file it with the loop folder, together with the sensor type, range, burnout action and the CJC state. When a failed unit is replaced years later, the file removes any doubt about whether the loop was set for NAMUR NE43 or for the MTL out-of-range characteristic, a detail that otherwise needs a trial and error session at the cabinet.

Cabinet planning is straightforward: the 1.2 W dissipation and 50 mA draw at 24 V are lower than most two-wire repeaters feeding the same loop count.

Documents and quotation

The dataset sheet EPSx573 gives the full configuration table. Send an RFQ stating MTL4573, quantity and your delivery location in Oman or the GCC.

Selection Notes for the MTL MTL4573

When comparing the MTL MTL4573 with alternatives, start from the duty it must perform: the measured or controlled variable, the range and accuracy you need, the environment at the mounting point and the interface to your control system. Check the electrical and mechanical connections against the installed equipment, and confirm any hazardous-area or ingress-protection requirements for the location. If any point is unclear, send a photo of the nameplate and a short description of the application, and we will compare it with the MTL (Eaton) isolator & barrier range and confirm the correct order code before you commit.

Other Models in the MTL4500 Backplane Range

Seven Star LLC supplies models from the MTL4500 Backplane range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
MTL MTL4544D Dual-Output Repeater Power SupplyIsolator & BarrierView details
MTL MTL4541A Backplane HART Current RepeaterIsolator & BarrierView details
MTL MTL4521 Loop-Powered Solenoid Driver, IICIsolator & BarrierView details
MTL MTL4573 THC/RTD Temperature ConverterIsolator & BarrierYou are viewing this model
Datasheets & Documents
  • PDF Datasheet MTL MTL4573 THC/RTD Temperature Converter Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

MTL is a British maker of intrinsic safety interfaces, surge protection and hazardous-area equipment, founded in 1971 in Luton as Measurement Technology Ltd, a spin-off from Kent Instrumentation. In 2008 Cooper Industries bought MTL Instruments for £144 million and placed it in its Crouse-Hinds division; Eaton acquired Cooper in 2012. MTL is now part of Eaton's Crouse-Hinds business, alongside the MEDC signalling range.

Seven Star LLC lists MTL isolators, a fieldbus barrier and the configuration tools for them, and supplies MTL (Eaton) barriers and spare modules to sites in Oman as an independent supplier.

MTL (Eaton) company profile

Founded 1971, Luton, England, as Measurement Technology Ltd
Origin Spin-off from Kent Instrumentation
Headquarters Luton, England
Ownership Eaton (Crouse-Hinds), via Cooper Industries from 2008
Product families MTL5500 and MTL4500 isolators, MTL7700 zener barriers, 9300 fieldbus barriers, surge protection devices, process junction boxes, PCS45 configuration software; MEDC beacons, sounders and call points

Milestones

  • 1971: Measurement Technology Ltd is founded in Luton.
  • 2007: MTL acquires ELPRO Technologies, RTK Instruments and Ocean Technical Systems.
  • 2008: Cooper Industries acquires MTL Instruments for £144 million.
  • 2012: Eaton acquires Cooper Industries.

MTL product families listed here

Most of the listed items are DIN-rail galvanic isolators. The MTL5541 repeater power supply and the MTL5576-THC temperature converter belong to the MTL5500 range, and the MTL 5043 repeater power supply comes from the earlier MTL5000 range that many plants still run. The MTL 9370-FB2 is a fieldbus barrier for intrinsically safe FOUNDATION fieldbus spurs. PCS45 software with the PCL45USB link is the configurator for MTL converter modules. For the listed part CPM08-BN, please send a label photo so the number can be matched to the manufacturer's records. Newer labels show Eaton MTL, older ones Measurement Technology Ltd, and the module numbers are the same. The MTL 9608 is a fieldbus junction box with eight spur outlets plus a trunk-in connection, listed under the Crouse-Hinds series part number FCS-9608.

Where MTL barriers and isolators are used

These interfaces sit in marshalling cabinets wherever instruments are located in Zone 0, 1 or 2 areas: gas plants, refineries, offshore platforms, tank farms and chemical units across the GCC. They power 2-wire transmitters, pass HART, convert thermocouple signals and drive solenoids or alarms while limiting energy to the field circuit.

MTL (Eaton) products we list

Family Examples
Isolator & Barrier Eaton MTL5541 Repeater Power Supply, MTL 5043, MTL 9370-FB2 Intrinsically Safe Fieldbus…, MTL CPM08-BN, MTL5576-THC Temperature Isolator Module
Automation Accessories MTL 9608 Process Junction Box
Automation Software MTL PCS45 Configuration Software and PCL…

Ordering MTL modules: what we need

Send the full module number including every suffix, for example MTL5576-THC and not just MTL5576, and the quantity. Tell us if the module mounts on DIN rail or on a backplane, because MTL5500 and MTL4500 parts are not interchangeable. For a fieldbus barrier give the number of spurs and the enclosure reference. A photo of the side label, which shows the certificate numbers, helps when the certificate for your project file must match.

Facts checked against the Eaton MTL company history and Drives & Controls coverage of the 2008 Cooper offer, October 2026.

FAQ

Questions about the MTL MTL4573 THC/RTD Temperature Converter

Answers from our engineering team on installation, compatibility and integration.

01Which sensors can the MTL4573 convert?
Thermocouple types J, K, T, E, R, S, B, N and XK, mV from minus 75 to plus 75 mV, Pt100, Pt500 and Pt1000, Cu-50, Cu-53, Ni100, Ni500, Ni1000 RTDs in 2, 3 or 4 wires, and resistance from 0 to 400 ohm.
02What is early burnout detection?
For thermocouples it warns when loop resistance rises by more than 50 ohm, before the sensor fails completely, and is indicated on the green LED.
03How does the output behave outside the range?
The out-of-range characteristic is selectable, MTL or NAMUR NE43, and the safety drive on sensor failure can be upscale, downscale or off.
04What load can the 4-20 mA output drive?
Up to 600 ohm, twice the 300 ohm of the 5576 two-channel types.
05How is the module configured?
From a PC with PCS45 software and a PCL45USB interface; for thermocouples a HAZ-CJC plug on terminals 1 to 3 holds an integral cold-junction sensor.