Brand:

Lenze E84AVSCE5524SX0 8400 StateLine C Inverter 5.5 kW

Description

5.5 kW inverter of the 8400 StateLine C family

The Lenze E84AVSCE5524SX0 is an Inverter Drives 8400 StateLine C frequency inverter for a 5.5 kW four-pole motor, in the built-in (installation) version. It is fed from 3/PE AC 400 V (320 to 440 V) or 500 V (400 to 550 V) and gives 13.0 A rated output current at 45 degrees C. Data on this page comes from Lenze’s Inverter Drives 8400 hardware manual (EDS84ASC552 EN 10.0, covering StateLine C, HighLine C and TopLine C from 0.25 to 45 kW). Lenze presents the 8400 StateLine on its website, but this C-version code should be confirmed for availability and hardware version before ordering.

Technical specifications

Parameter Specification
Type E84AVSCE5524SX0
Motor power (4-pole ASM) 5.5 kW
Mains connection 3/PE AC 400 V (320 to 440 V) or 500 V (400 to 550 V), 45 to 65 Hz
Mains current, no choke / with choke 18 A / 12.0 A (400 V)
Apparent output power 8.1 kVA
Rated output current, 45 C / 55 C 13.0 A / 9.8 A
Maximum output current 19.5 A (3 s load, 12 s recovery)
Current at 16 kHz 8.7 A (IaM 11.7 A)
Power loss at rated current 275 W
Brake chopper RBmin 47 ohm, peak 15.4 A, 11.2 kW
Size and dimensions GG 4 / 270 x 140 x 199 mm
Mass 4.4 kg

Standards and rated conditions

Rated conditions include an output range of 0 to 1000 Hz and IP20 protection with NEMA 250 type 1 contact protection. Certificates named in the manual: CE, EAC (two technical regulations of the Customs Union), UL 508C and, with external mains choke only, CSA 22.2 No. 14.

How the code E84AVSCE5524SX0 breaks down

Position by position: E84 (8400), A (version 1), V (vector), SC (StateLine C), E (installation mounting), 552 (5.5 kW), 4 (4 = 400/500 V three-phase), S (IE33 standard environment), X (without safety system), and finally 0, the standard design.

What the controller offers

Features listed for StateLine C include VFCplus and VFCplus eco V/f control, sensorless vector control, S-ramps, flying restart, brake management and chopper, and 200 percent overload for 3 s. I/O is 5 digital in, 1 digital out, 1 analog in, 1 analog out and a relay, with an HTL encoder input to 10 kHz. CANopen is on board and MCI slots take the fieldbus modules.

Installation and selection notes

Size GG 4 measures 270 x 140 mm in front view. Rated figures hold for 2 and 4 kHz, no choke; 16 kHz gives 8.7 A. Connect a brake resistor of 47 ohm minimum to the internal chopper. A choke cuts the mains current from 18 A to 12.0 A. Order the X400 keypad (EZAEBK1001) and MCI modules separately.

Environmental data: storage 1K3 from minus 25 to plus 60 degrees C, transport 2K3 from minus 25 to plus 70 degrees C and operation 3K3 from minus 10 to plus 55 degrees C. Above the stated temperatures the rated output current falls by 2.5 percent per degree, and above 1000 m altitude by 5 percent per 1000 m, up to 4000 m. Pollution degree 2 applies, and vibration resistance in operation is stated up to 0.7 g. These conditions apply to the 5.5 kW size, rated at 13.0 A.

Operating the 5.5 kW StateLine C in Gulf plant conditions

The operating range of this inverter is minus 10 to plus 55 °C, with full rated current of 13.0 A up to 45 °C and 9.8 A at 55 °C. In an Omani pump house or a rooftop panel that sits in direct summer sun, the air inside an unventilated cabinet can easily exceed the outside temperature, so the realistic rating to plan with is often the derated figure rather than the 45 °C value. A few practical points follow from the manual data:

  • Cabinet cooling: at rated current the drive dissipates about 275 W. Size the cabinet fan, filter or air conditioner for this loss plus every other heat source in the enclosure.
  • Derating: above the stated temperature limits, output current falls by 2.5 percent per degree; above 1000 m altitude by 5 percent per 1000 m. Most coastal sites in Oman are well below 1000 m, but interior and mountain sites should be checked.
  • Dust: the unit is IP20 and rated for pollution degree 2, so it belongs inside a sealed or filtered enclosure. Conductive dust or sand on the heatsink reduces cooling and should be removed during routine maintenance.
  • Switching frequency: higher switching frequencies reduce motor noise but lower the available current (8.7 A at 16 kHz). For hot cabinets, staying at 2 or 4 kHz keeps the full rating available.

Typical applications for a 5.5 kW vector inverter

A 5.5 kW four-pole motor is common on conveyors, mixers, circulation and transfer pumps, ventilation fans, packaging machines and material handling equipment. StateLine C combines V/f control (VFCplus and the energy-saving VFCplus eco mode) with sensorless vector control, so the same unit can run a quadratic fan or pump load with reduced energy use or a conveyor that needs good torque at low speed. Flying restart allows the drive to catch a fan that is already spinning, for example after a short supply interruption, and the internal brake chopper with an external resistor of at least 47 ohm handles loads that must decelerate faster than they coast down.

Commissioning and maintenance checklist

  1. Check the nameplate against the order code E84AVSCE5524SX0 and confirm the mains voltage (400 V or 500 V range).
  2. Install the recommended fuses and, where specified, the mains choke; the choke reduces the input current from 18 A to 12.0 A at 400 V and is required for CSA approval.
  3. Use shielded motor cable with the shield bonded at both ends for EMC-compliant installation, and keep control wiring separated from power cables.
  4. Enter the motor nameplate data before the first run so that the vector control model matches the motor.
  5. Set the ramps, current limit and any brake resistor parameters, then test under load.
  6. During periodic maintenance, inspect fans and heatsinks, retighten power terminals and save a copy of the parameter set for fast replacement.

Communication options

CANopen is built in, which suits machines already using CAN-based networks. For plants based on PROFIBUS, PROFINET, EtherCAT or EtherNet/IP, a communication module is fitted in the MCI slot; these modules are ordered separately and should be listed on the request together with the X400 keypad if local parameter access is needed.

What to include in an RFQ

  • Complete type code E84AVSCE5524SX0 and the quantity.
  • Supply voltage and frequency at site, and whether a mains choke or EMC filter is required.
  • Motor nameplate data (power, current, speed, voltage).
  • Required fieldbus module and keypad, plus any brake resistor.
  • Ambient conditions inside the panel and the existing unit’s hardware version if this is a replacement.

Documents and quotation

The attached Lenze hardware manual carries the complete rating, dimension, fuse and accessory tables. See AC Drives for related inverters. A quotation needs the complete code, mains voltage, motor nameplate and fieldbus; the variant should be verified against the nameplate before ordering.

Datasheets & Documents
  • PDF Manual Lenze Inverter Drives 8400 hardware manual EDS84ASC552 EN 10.0 Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lenze is a German company for drive and automation technology for machine building, founded in 1947 and headquartered in Aerzen, Lower Saxony. Its portfolio runs from frequency inverters, servo inverters and motors to controllers, engineering software and digital services.

Seven Star LLC is an independent supplier in Muscat. We list Lenze frequency and servo inverters, including current and earlier generations, for machine builders and maintenance teams in Oman and the GCC.

Lenze product series

Current inverters on this site are the i500 family: the i510 compact frequency inverter, the i550 cabinet inverter and its i550 protec decentral version for mounting on the machine, and the i950 cabinet servo inverter. Earlier generations that are still widely installed are also listed: the 8400 StateLine C inverters (E84AVSC...), the 8200 vector frequency inverters (E82EV...) and the 9300 servo position controllers and servo inverters (EVS93...), including versions with Safe Torque Off.

Where Lenze drives are used

Conveyors and intralogistics, packaging and bottling lines, pumps and fans, hoists, textile and printing machines, and positioning axes on special machines. Many plants in the region keep 8200 vector and 9300 drives in service and need exact replacements or a planned migration to the i500 series.

Ordering Lenze inverters: what we need

Send the complete type code from the nameplate, for example E84AVSCE5524SX0, together with the supply voltage, motor power and current, the control interface or fieldbus module, and any options such as safety functions, keypad or brake resistor. When replacing an installed drive, keep the parameter set and wiring records, because a new unit or a successor model must be parameterised to match the machine.

Frequently Asked Questions

What power is the E84AVSCE5524SX0 rated for?
5.5 kW for a four-pole asynchronous motor, supplied from 3/PE AC 400 V (320 to 440 V) or 500 V (400 to 550 V).
What is the rated output current of the E84AVSCE5524SX0?
13.0 A up to 45 degrees C and 9.8 A up to 55 degrees C, with 19.5 A overload current for 3 s.
Is the E84AVSCE5524SX0 an i500 inverter?
No. The E84AVSC code identifies the Inverter Drives 8400 StateLine C family, not the i500 series.
Does the E84AVSCE5524SX0 include Safe Torque Off?
No. The X in the type code means without safety system; the B version carries Safe Torque Off.
What does the E84AVSCE5524SX0 measure physically?
270 x 140 x 199 mm and 4.4 kg according to the Lenze hardware manual.