Description
A compact IP20 drive with built-in filter, brake chopper and STO
The Danfoss VLT Midi Drive FC 280 is a general-purpose AC drive for conveyors, mixers, packaging machines, pumps, fans and compressors, covering 0.37 kW to 22 kW. Danfoss describes it as the evolution of the VLT 2800 and designs it so that harmonic mitigation, an EMC filter, dual-channel Safe Torque Off and a brake chopper are already inside the housing, which removes the cost and panel space of external parts.
Single-phase types use an active power factor correction stage that keeps harmonics below 8 percent THDi, while three-phase types use an integrated DC choke to stay below 48 percent. The same control algorithm drives induction and permanent magnet motors.
Technical specifications
| Parameter | Specification |
|---|---|
| Series | VLT Midi Drive FC 280, the evolution of the VLT 2800 drive |
| Mains supply | 1 x 200-240 V, 3 x 200-240 V and 3 x 380-480 V (-15 / +10 percent), 50/60 Hz |
| Power range | 3 x 380-480 V: 0.37 to 22 kW; 3 x 200-240 V: 0.37 to 3.7 kW; 1 x 200-240 V: 0.37 to 2.2 kW |
| Displacement power factor | Near unity (above 0.98) |
| Output | 0-100 percent of supply voltage; 0-500 Hz; ramp times 0.01 to 3600 s |
| Motor control | Induction and permanent magnet motors; PM motor open-loop control (VVC+) over the whole power range |
| Digital I/O | 6 (7) programmable digital inputs, 1 digital output, PNP or NPN logic, 0-24 V DC |
| Pulse / encoder inputs | 2 pulse inputs / 2 encoder inputs (one pair configurable as encoder input), 0-24 V DC |
| Analog I/O | 2 analog inputs (voltage or current, 0 to 10 V, 0/4-20 mA); 1 analog output 0/4-20 mA; 1 relay output |
| Integrated features | Harmonic mitigation (DC choke on 3-phase units; active PFC on single-phase units), RFI filter (Cat. C2 / EN 61800-3), dual-channel Safe Torque Off, brake chopper on 3-phase units up to 22 kW |
| Harmonics | Below 48 percent THDi (3-phase, integrated DC choke); below 8 percent THDi (single-phase, active PFC) |
| Fieldbus | Modbus RTU and FC Protocol integrated; options PROFINET dual port, POWERLINK dual port, EtherNet/IP dual port, PROFIBUS, CANopen; 24 V DC backup supply option |
| User interface | USB port, pluggable terminals, set-up wizards, numerical LCP (option), graphical LCP, VLT Memory Module MCM 102 |
| Installation | Side-by-side or horizontal mounting without derating; operates up to 45 C without derating; RFI switch for IT mains |
| Approvals | CE, UL listed, cUL, TUV, RCM, EAC |
| Enclosure | IP20, frame sizes K1 to K5 |
Installation, commissioning and communication
Frame sizes K1 to K5 are IP20 and can be mounted side by side or horizontally without derating, at ambient temperatures up to 45 C without derating. Pluggable terminals and an integrated USB port allow quick wiring and PC connection without a USB adapter driver. Set-up wizards cover common applications, and the VLT Memory Module lets a technician copy parameters or update firmware.
Modbus RTU and FC Protocol are standard. PROFINET, POWERLINK and EtherNet/IP with dual ports, PROFIBUS and CANopen are options, and an optional 24 V DC supply keeps the fieldbus alive when the mains is off. The fact sheet also describes an easy retrofit for existing VLT 2800 installations.
Selecting a frame and a type code
Pick the drive from the motor power at the supply voltage in use, then check the frame size for the panel. The table lists the enclosure dimensions printed in the Danfoss fact sheet; weights across the IP20 range run from 2.3 kg to 12.5 kg, and the fact sheet assigns each power size to its frame.
| Frame | Height A (mm) | Width B (mm) | Depth C (mm) |
|---|---|---|---|
| K1 | 210 | 75 | 168 |
| K2 | 272.5 | 90 | 168 |
| K3 | 272.5 | 115 | 168 |
| K4 | 320 | 135 | 245 |
| K5 | 410 | 150 | 245 |
Confirm before ordering: supply voltage and phases, rated motor current and overload, the fieldbus option, the control panel (numerical or graphical), safety needs, and the full ordering type code. For simpler duties see the Danfoss FC 51; for higher performance see the Danfoss FC 102; other drives are in the AC drives category.
How the Danfoss VLT Midi Drive FC 280 works
The drive turns the incoming mains supply into direct current and then builds a new output with the voltage and frequency the motor needs. The control algorithm sets the output so the motor holds the speed that was set. Changing the output frequency changes the motor speed.
Where the FC 280 is used
- Conveyors
- Mixers
- Packaging machines
- Pumps and fans
- Compressors
Selection checklist for the FC 280
- Mains supply voltage
- Single or three-phase input
- Motor power
- Motor type
- Digital and analog I/O count
- Fieldbus option
- Brake chopper need
- Panel space
Installation, commissioning and maintenance notes for the FC 280
Mount the drive in the panel with free space for cooling air. Wire the mains, the motor and the control terminals, then run the set-up wizard. Check the terminals and the cooling path at regular intervals.
Requesting a quotation for the Danfoss VLT Midi Drive FC 280
Please send the mains voltage, the motor power and the fieldbus needed. Seven Star LLC serves industrial customers in Oman and the GCC and replies with a quotation based on the information provided.
FC 280 drive type
It is a general-purpose AC drive.
FC 280 maker
It is made by Danfoss.
FC 280 predecessor
It is the evolution of the VLT 2800 drive.
FC 280 power range
The range covers 0.37 kW to 22 kW.
FC 280 three-phase 400 V range
The 3 x 380-480 V types run from 0.37 to 22 kW.
FC 280 three-phase 200 V range
The 3 x 200-240 V types run from 0.37 to 3.7 kW.
FC 280 single-phase range
The 1 x 200-240 V types run from 0.37 to 2.2 kW.
FC 280 mains frequency
The mains frequency is 50 or 60 Hz.
FC 280 power factor
The displacement power factor is near unity.
FC 280 output frequency
The output runs from 0 to 500 Hz.
FC 280 ramp times
Ramp times run from 0.01 to 3600 seconds.
FC 280 motor control
It drives induction and permanent magnet motors.
FC 280 open-loop control
Permanent magnet open-loop control covers the whole power range.
FC 280 built-in filter
An RFI filter is built in.
FC 280 harmonic mitigation
A DC choke or active power factor correction is built in.
FC 280 safe torque off
Dual-channel Safe Torque Off is built in.
FC 280 brake chopper
A brake chopper is built into the three-phase units.
FC 280 digital inputs
It has six programmable digital inputs.
FC 280 digital output
It has one digital output.
FC 280 analog inputs
It has two analog inputs for voltage or current.
FC 280 analog output
It has one analog output of 0/4-20 mA.
FC 280 relay output
It has one relay output.
FC 280 fieldbus
Modbus RTU and the FC protocol are built in.
FC 280 fieldbus options
Options include PROFINET, EtherNet/IP, PROFIBUS and CANopen.
FC 280 user interface
It has a USB port, pluggable terminals and set-up wizards.
FC 280 memory module
The VLT Memory Module MCM 102 stores the settings.
Drive records for the FC 280
Record the motor data, the parameter set and the date of each service.
Choosing the right FC 280 size
Choose the size from the motor power and the supply voltage.
Documents and quotation
The attached file is the two-page Danfoss Drives fact sheet for the VLT Midi Drive FC 280 with features, specifications and dimensions. For a quotation, send the full type code (for example FC-280P4K0T4E20H1), quantity and any fieldbus or LCP options to Seven Star LLC, an independent supplier in Muscat.
Datasheets & Documents
- Fact Sheet Danfoss Drives fact sheet: VLT Midi Drive FC 280 (DKDD.PFP.820.A7.02) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
From its headquarters in Nordborg, Denmark, where it was founded in 1933, Danfoss makes the drives, valves and sensors found in pump rooms, chiller plants and cold stores. Its blue VLT frequency converters are probably the most familiar of them.
Seven Star LLC lists Danfoss VLT drives, pressure transmitters, refrigeration valves and HVAC control valves, and supplies them to contractors and plant owners in Oman against the exact code number on the label.
Danfoss product families on this page
Among the VLT drives listed, three are each aimed at a different duty: the VLT HVAC Drive FC 102 for fans and building services, the VLT AQUA Drive FC 202 for water and wastewater pumping, and the VLT AutomationDrive FC 302 for general industrial machinery. The LCP 12 control panel with potentiometer (code number 132B0101) is also listed; Danfoss specifies it for the VLT Micro Drive FC 51. In pressure measurement there are the MBS 3000 general purpose transmitter and the MBS 5100. Valves include the AB-QM pressure independent control valve in DN 15 to DN 250, the EVR 25 servo-operated solenoid valve and the ICV pilot-operated valve for industrial refrigeration.
Where Danfoss equipment is used
District cooling and chilled water plants, air handling units, booster and irrigation pump stations, desalination and wastewater works, ammonia and CO2 refrigeration plants, food storage and marine engine rooms are the usual places. Demand in the GCC is driven largely by cooling and water.
Ordering Danfoss parts: what we need
Every Danfoss product has a code number, and drives also carry a long type code string on the label. Send both. For a drive we need the motor power and current, the mains voltage, enclosure rating, any fieldbus or option card and the filter class. For an MBS transmitter give the pressure span, output signal, pressure connection and electrical connection. For valves give the size, connection type, coil voltage where relevant and the refrigerant or medium.
Browse Danfoss products by category: AC Drives, Pressure Instrumentation, Control Valves, Solenoid Valve.

Reviews
There are no reviews yet.