Brand:

R. STAHL 9160/13-11-11s Transmitter Supply Unit

Description

Overview

R. STAHL 9160/13-11-11s is a DIN-rail-mounted Ex i isolating amplifier from the Series 9160 transmitter supply unit family, engineered to power and interface intrinsically safe 2-wire and 3-wire field transmitters located in Zone 0, 1, 20, or 21 hazardous areas. The unit accepts a 0/4–20 mA HART-compatible input from the field transmitter, supplies its intrinsically safe loop power, and delivers a fully isolated 0/4–20 mA output signal to the control system, making it a core building block of any Ex i measurement loop feeding a DCS, PLC, or SCADA platform.

As the official trusted supplier and regional supplier for R. STAHL, Seven Star LLC proudly supplies the 9160/13-11-11s and the wider ISpac isolator range to end users, EPC contractors, and system integrators throughout the Sultanate of Oman and the GCC. Every unit is supplied with manufacturer ATEX/IECEx documentation and local technical support, giving instrumentation teams in Muscat, Sohar, and Salalah a dependable source for certified Ex i isolators, with lead time confirmed at quotation.

Operating Principle

Internally, the 9160/13-11-11s limits the voltage and current it can deliver into the field-side loop to values below the ignition energy of the specified gas group, so the transmitter connection itself is intrinsically safe regardless of what happens on the safe-area side of the unit. Three-way galvanic isolation separates the field circuit, the output signal circuit, and the 24 V DC auxiliary supply, so a fault on any one side—including a short circuit or an accidental application of mains voltage—cannot propagate into the hazardous-area wiring or damage connected control-system inputs.

Because the R. STAHL 9160/13-11-11s is fully transparent to HART communication in both directions, a handheld communicator or asset-management system in the control room can poll, configure, and diagnose the field transmitter exactly as if it were wired directly, without any loss of digital data across the barrier. The practical consequence is a measurement loop that combines certified intrinsic safety with full HART diagnostics, so plant engineers get explosion protection without giving up the predictive-maintenance data modern transmitters are designed to provide.

Engineering Design of the R. STAHL 9160/13-11-11s

The 9160/13-11-11s is housed in a slim 17.6 mm wide plastic module designed for direct snap-mounting onto standard NS35/7.5 or NS35/15 DIN rail inside a marshalling cabinet or junction panel, allowing dense packing of isolator channels in racks with limited panel width. Removable screw terminals on both the field-side and system-side connections allow the module to be swapped without disturbing adjacent wiring, which shortens maintenance windows during a shutdown or module replacement.

On the R. STAHL 9160/13-11-11s, front-panel LED indication shows power and channel status at a glance, and the unit accepts a 24 V DC nominal auxiliary supply across an 18–31.2 V DC range, matching the standard control-cabinet power bus used across most GCC process facilities. Its rated ambient operating range of -20°C to +70°C for single-unit mounting covers the great majority of indoor marshalling-cabinet environments found in regional oil, gas, and petrochemical plants, even where cabinet cooling is marginal during peak summer conditions.

Key Features

The R. STAHL 9160/13-11-11s combines robust intrinsic safety with practical panel-building convenience. The R. STAHL 9160/13-11-11s’s key features include:

  • Ex i field circuit rated for Zones 0, 1, 2, 20, 21, and 22 under ATEX and IECEx approval.
  • Transparent bidirectional HART signal transmission for full field-transmitter diagnostics and configuration.
  • Three-way galvanic isolation between field circuit, output signal, and auxiliary power.
  • SIL 2 rated per IEC 61508 for use in safety instrumented functions.
  • Compact 17.6 mm DIN-rail housing for high-density marshalling cabinet layouts.
  • 24 V DC nominal auxiliary supply across an 18–31.2 V DC operating range.
  • Output load capability up to 600 Ω on standard terminals for long control-room cable runs.
  • Wide ambient operating range of -20°C to +70°C suited to regional cabinet conditions.

Industrial Applications

The R. STAHL 9160/13-11-11s is specified wherever a 4–20 mA transmitter—pressure, level, flow, or temperature—is installed in a classified hazardous area and must report back to a control system located in a safe area. Typical applications include tank farm level and pressure transmitters, wellhead and pipeline pressure monitoring, compressor and pump process instrumentation, and any Ex i loop feeding a safety instrumented system where SIL 2 documentation is required by the plant’s functional safety case. The R. STAHL 9160/13-11-11s’s transparent HART pass-through also makes it the preferred choice on projects where predictive-maintenance software needs live access to transmitter diagnostics from the control room.

In Oman and the GCC, Seven Star LLC distributes the 9160/13-11-11s to upstream and downstream oil and gas operators, refineries, and petrochemical complexes across Oman and the wider GCC, including projects in the Sohar and Salalah free zones and Duqm’s expanding industrial base. Instrumentation teams standardizing marshalling-cabinet designs around certified Ex i isolators, or replacing obsolete isolator models during a control-system migration, rely on our documentation support and confirmed lead times to keep commissioning schedules on track.

Technical Specifications

The table below summarizes the principal ratings for the R. STAHL 9160/13-11-11s Ex i transmitter supply unit.

Parameter Specification
Model 9160/13-11-11s (Art. No. 214895)
Function Ex i transmitter supply unit / isolating amplifier
Input Signal 0/4–20 mA with HART, max. 50 mA
Output Signal 0/4–20 mA with HART, 0–600 Ω load (standard terminals)
Auxiliary Supply 24 V DC nominal, 18–31.2 V DC range
Isolation 3-way galvanic isolation, field / output / power
Mounting Width 17.6 mm, DIN rail NS35/15 and NS35/7.5
Ambient Temperature -20°C to +70°C (single device)
Hazardous Area Approval ATEX / IECEx [Ex ia Ga] IIC, [Ex ia Da] IIIC, Zones 0/1/2/20/21/22
Functional Safety SIL 2 per IEC 61508, PFDavg 2.29E-04 (1-year proof test)
Storage Temperature -40°C to +80°C

Request a Quote for R. STAHL 9160/13-11-11s

For the R. STAHL 9160/13-11-11s, instrumentation and EPC teams across Oman and the GCC can request a formal quotation for the R. STAHL 9160/13-11-11s Ex i transmitter supply unit directly from Seven Star LLC’s instrumentation division. In Oman and the GCC, we supply on request with lead time confirmed at quotation, provide the full ATEX/IECEx technical datasheet on request, and support marshalling-cabinet specification, replacement, and SIL documentation for both new-build and brownfield hazardous-area projects. Contact our team today to confirm lead time, pricing, and certification paperwork for your next shutdown or turnaround.

Browse the full R. STAHL range or see more Isolator & Barrier products supplied by Seven Star LLC in Oman and the GCC.

Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand
R. STAHL has worked from Waldenburg, Germany, since 1876 and today concentrates on electrical equipment for explosive atmospheres: isolators, remote I/O, plugs and sockets, control and distribution gear. Seven Star LLC lists R. STAHL intrinsically safe interface modules and Ex plugs and sockets and supplies them to instrument and electrical teams in Oman, working from the type number on the device.

R. STAHL products listed here

Two interface items are on this page: the 9160/13-11-11s transmitter supply unit, an isolator that powers a two-wire transmitter in the hazardous area and passes its signal to the safe side, and the 9475 Ex i digital output module, a remote I/O module for driving intrinsically safe solenoids and indicators. The connector items are the Series 8570 16 A Ex plug and socket and the 8579/12-506 63 A plug.

Ordering R. STAHL parts: what we need

Send the full type number as printed, for example 9160/13-11-11s. The digits after the slash define channels, signal type and terminal style, and the final letter matters. For plugs and sockets we need the current rating, number of poles, voltage and frequency, and the earth contact position, since these are keyed to prevent mismatched connections. State the zone and the certification scheme used on your GCC site.

Frequently Asked Questions

What does the R. STAHL 9160/13-11-11s do?
It is an Ex i transmitter supply unit that powers 2- and 3-wire intrinsically safe field transmitters and passes their 4-20 mA and HART signal back to the control system through three-way galvanic isolation.
Does it reduce installation cost compared to flameproof wiring?
Yes. Because the field circuit is intrinsically safe, standard cable can be run to the transmitter instead of heavy flameproof conduit, reducing both material and labor cost on new installations.
What transmitter types is the 9160/13-11-11s compatible with?
It is compatible with standard 2-wire and 3-wire 4-20 mA transmitters and mA sources, including 4-wire transmitters, across pressure, level, flow, and temperature measurement types.
Can it integrate with existing HART-based asset management systems?
Yes. The unit is transparent to bidirectional HART communication, allowing existing asset-management software or handheld communicators to poll and configure the field transmitter without any loss of diagnostic data.
Is Seven Star LLC a trusted supplier for R. STAHL products?
Yes, Seven Star LLC supplies R. STAHL products to customers in Oman and the GCC and can provide the manufacturer documentation and technical support on request.