- Automation & ControlView all 3,158 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Encoders
- Motor Soft Starters
- CCTV & Security
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Pizzato
Pizzato CS AM12P1MU Standstill Safety Module, 3NO Relay
Description
Overview
If the guard lock of a motor-driven machine must be released only at true standstill, and the lock circuit works with ordinary contacts rather than semiconductor signals, then relay outputs are the practical choice. The Pizzato CS AM12P1MU is the relay version of the Pizzato motor standstill module: it monitors the residual voltage of the motor phases, and it closes three normally open safety contacts when the motor has stopped. The housing is 45 x 114 mm, the supply is 24 Vdc, and the P in the code points to the version with a USB type-C port for the CS AM Configurator software. Seven Star LLC is an independent supplier serving Oman and the GCC.
Relay stage of the Pizzato CS AM12P1MU
The three safety contacts are forcibly guided according to EN 61810-3, made of silver alloy, and rated at up to 230/240 Vac with 6 A per contact. Utilisation categories are AC-15 at 250 Vac with 3 A and DC-13 at 24 Vdc with 3 A, and the UL category is R300 with B300. The sum of squared currents is limited to 36 A2, the minimum current is 10 mA, and the contact resistance is up to 100 milliohm at 1 A and 24 Vdc. The contacts last more than 100,000 operating cycles electrically, while the mechanical endurance of the relays is 10 million cycles. An external fuse of 4 A type gG protects the contact circuit, and the module itself needs a 2 A type gG fuse in the 24 Vdc supply.
Technical overview for Pizzato CS AM12P1MU
| Characteristic | Value |
|---|---|
| Function | SF1 motor standstill monitoring |
| Outputs | 3NO relay safety contacts |
| Housing size | 45 x 114 mm, polyamide PA 66 |
| Supply | 24 Vdc plus or minus 15 percent |
| Supply current | 80 mA minimum; 450 mA relay inrush with signalling on; 380 mA holding |
| Phase measuring range | 0 to 690 V |
| Frequency input of AM1 types | 0 to 3 kHz |
| Thresholds | VH 40 to 500 mV or 200 to 2000 mV (trimmer), VL from 20 mV |
| Activation time tZA | Below 120 ms |
| Deactivation time tZR1 | Below 60 ms; release without supply below 40 ms |
| Safety data SF1 | SIL 3, PL e, category 4, MTTFD 70 years, PFHD 1.00E-09 per hour |
| External device monitoring | Maximum state change delay tEDM 500 ms |
| Temperature | Minus 25 to plus 55 degrees Celsius |
| Insulation | Measuring domain 690 V to SELV; relay contacts 250 Vac |
What separates CS AM12P1MU from CS AM11P1MU
- Output: three relay contacts here, two OSSD semiconductor outputs on the CS AM11 code.
- Housing: 45 x 114 mm here, 22.5 x 114 mm on the CS AM11 code.
- Switching ability: up to 230/240 Vac and 6 A here, 24 Vdc and 0.25 A for the OSSD outputs.
- Timing: deactivation below 60 ms and activation below 120 ms here, below 40 ms and below 100 ms on the OSSD version.
- Supply current: 450 mA at relay inrush here, up to 800 mA with all outputs loaded on the OSSD version.
Using relay contacts for guard locking
Most guard locking switches and interlocks accept a simple contact: the lock solenoid is wired through the safety contact of the standstill module, so the door can only be opened when the contacts are closed. The relay outputs allow this directly at 24 Vdc or at mains voltage, without an interposing relay. Two contacts can be connected in series for redundancy and the third can feed a signal to the PLC, or all three can be used for separate circuits. Remember that the safety function reaches the stated level only when the connected devices and wiring support it.
Cautions from the manual
The module detects standstill only by measuring residual voltages. For inverter-fed motors the compatibility of both devices must be checked beforehand, and the connection between module and inverter must use a shielded cable with the shield attached to the motor. For dc motors only the standstill function is possible, and for suspended loads a freely moving load can make the motor behave as a generator, so a consistency check is needed. The self-test takes 3 seconds after power-up.
Choosing the thresholds in practice
Two voltages define the behaviour. The started-motor threshold VH tells the module that the motor is running, and the standstill threshold VL tells it that the motor has stopped. VL can be set from 20 mV up to 99 percent of VH, so there is a hysteresis band between them that prevents chatter when the residual voltage hovers around one value. With the trimmer, ten positions select VH within one of two ranges, 40 to 500 mV or 200 to 2000 mV, and in software mode VH may be set anywhere from 40 to 2000 mV. Residual voltage differs from motor to motor, so the best value is found by measurement and not by calculation. Observe the module on the real machine during several stops, from different speeds and with different loads, and write down the thresholds that gave stable and correct results. Change one threshold at a time, and repeat the stop test after each change so that the effect is clear.
Regional use
In Omani and Gulf plants, standstill detection is a standard request in cement, mining, oil and gas fabrication and water treatment, where large motors, mixers and centrifuges coast for a long time. Plant electricians appreciate that the module needs no sensor on the shaft, which makes retrofits on existing motors quick.
Service and checks
Check the thresholds and the response at each proof test, keep the configuration file with its password if software is used, and compare the observed standstill with the point at which the outputs close. Replace the module if its diagnostics report a fault that persists.
Related items you may also need: Pizzato FR 693 Safety Switch with Separate Actuator, 1NO+1NC | Pizzato FR 1007 Position Switch, Adjustable Roller | Pizzato FD 1001 Metal Position Switch with Plunger | All Pizzato products.
Before you order the Pizzato CS AM12P1MU
- To avoid a wrong delivery, compare the code on the nameplate of the installed unit with the Pizzato CS AM12P1MU code on this page.
- The quotation for the Pizzato CS AM12P1MU states the confirmed code, the condition of the unit and the lead time to site.
- The attached manufacturer datasheet covers the Pizzato CS AM12P1MU ratings, dimensions and installation details.
- Delivery of the Pizzato CS AM12P1MU is arranged to project sites in Oman and across the GCC, alongside the rest of our safety switches & guard locking range.
- A spare Pizzato CS AM12P1MU on the shelf is a simple way to protect critical service from long lead times.
Documents and quotation
The Pizzato manual of the CS AM series is attached to this page with the function descriptions, wiring and technical data. To request a quotation, send an RFQ listing Pizzato CS AM12P1MU, the quantity and the delivery destination in Oman or the GCC, and add the motor data if you want us to check the application.
Other Models in the CS AM Range
Seven Star LLC supplies models from the CS AM range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Pizzato CS AM11P1MU Motor Standstill Safety Module | Safety Switches & Guard Locking | View details |
| Pizzato CS AM12P1MU Standstill Safety Module, 3NO Relay | Safety Switches & Guard Locking | You are viewing this model |
Datasheets & Documents
- Datasheet Pizzato CS AM12P1MU Standstill Safety Module, 3NO Relay Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Pizzato Elettrica is an Italian maker of position switches and safety devices, founded in 1984 as a manufacturer of position switches and based in Marostica, near Vicenza. It took the name Pizzato Elettrica in 1988 and added safety modules around 2002. The company designs and assembles its products in Marostica, where it opened a new 25,000 m² headquarters in 2019.
Seven Star LLC is an independent supplier in Muscat. We list Pizzato switches for machine builders and maintenance teams in Oman and the GCC.
Pizzato company profile
| Founded | 1984, Italy |
|---|---|
| Headquarters | Marostica, Italy |
| Name since | 1988 |
| Catalogue | More than 7,000 standard products |
| Product families | FR, FD and FK position switches, NG and NS safety interlocks, NX RFID safety switches, safety modules, foot switches |
Milestones
- 1984: Pizzato is founded.
- 1988: The company becomes Pizzato Elettrica.
- 2019: A new headquarters opens in Marostica.
Pizzato product series
Position switches include the FD 1001 metal switch with plunger, the FK 301 switch with plunger and snap action contacts, and the FR 1007 switch with adjustable roller lever.
Switches are chosen by the housing (metal or technopolymer), actuator, contact block and electrical connection. Snap action contacts switch quickly regardless of actuator speed, and positive opening contacts are used in safety circuits.
Plunger actuators suit short, straight movements against a cam or stop, while adjustable roller levers let the operating point be set on site and suit cams and moving parts that pass the switch. Metal housings stand up to heavy duty and impacts, and each data sheet states the IP rating, mechanical life and operating temperature range.
Where Pizzato switches are used
End of travel detection on machines, conveyors, doors and guards, cranes and lifting equipment.
Pizzato products we list
| Family | Examples |
|---|---|
| Automation Accessories | FD 1001 Metal Position Switch with Plunger, FK 301 Position Switch with Plunger, FR 1007 Position Switch |
Ordering Pizzato switches: what we need
Send the full article code, or the actuator type, contacts, housing and cable entry.
Facts checked against Pizzato's own timeline and EtherCAT member profile, October 2026.
Browse Pizzato products by category: Automation Accessories.
FAQ
Questions about the Pizzato CS AM12P1MU Standstill Safety Module, 3NO
Answers from our engineering team on installation, compatibility and integration.
01What outputs does the Pizzato CS AM12P1MU have?
Three normally open safety relay contacts, forcibly guided, rated up to 230/240 Vac and 6 A, with AC-15 3 A at 250 V.
02How does the CS AM12P1MU differ from the CS AM11P1MU?
The AM12 code has relay contacts in a 45 x 114 mm housing, while the AM11 code has two OSSD outputs in a 22.5 x 114 mm housing.
03What are the response times of the CS AM12P1MU?
For standstill monitoring the activation time is below 120 ms and the deactivation time below 60 ms, with release without supply below 40 ms.
04What fuses does the CS AM12P1MU need?
The manual gives a 2 A type gG fuse for the supply and a 4 A type gG fuse for the relay output circuit.
05Can the CS AM12P1MU be used with inverter-fed motors?
Yes, but the manual states that compatibility must be checked and a shielded cable with the shield attached to the motor must be used.


















Reviews