Eaton ZB12-6 Overload Relay 4-6 A

Description

Eaton ZB12-6 thermal overload relay, 4 – 6 A

The Eaton ZB12-6 (catalog number 278439) is a small thermal overload relay adjustable from 4 to 6 A. At 400 V that covers motors of roughly 1.5 to 2.2 kW. It has one N/O and one N/C auxiliary contact, trips to Class 10 A and mounts directly onto the contactor. Seven Star LLC supplies the ZB12-6 in Oman and the GCC.

A narrow range matters at low currents: the closer the dial window is to the motor nameplate, the more accurate the protection. The ZB12-6 is therefore the right choice for small motors, not a larger relay turned down to its minimum.

Reading the model code ZB12-6

ZB is the Eaton Moeller thermal overload relay series. 12 after it is the frame size (the 12 or 32 reflects the largest current the frame covers), and the number after the hyphen, here 6, is the top of the adjustable range in amperes. The relay is therefore adjustable from 4 to 6 A. A relay from the same frame with a different suffix covers a different current band, so the suffix has to match the motor nameplate.

ZB12-6 technical specifications

Parameter Specification
Manufacturer / part number Eaton ZB12-6 (catalog number 278439)
Series / frame size Eaton Moeller ZB, ZB12
Overload release setting 4 – 6 A
Dimensions / weight 88 mm deep × 67 mm high × 45 mm wide; 0.142 kg
Heat dissipation 5.1 W total, 1.7 W per pole at 6 A
Short-circuit protection, type 2 20 A gG/gL
Short-circuit protection, type 1 25 A gG/gL
UL/CSA branch circuit fuse 100 kA with Class J/CC fuse, max. 10 A (600 V)
Contacts 1 N/O and 1 N/C auxiliary contact
Trip class Class 10 A to IEC 60947-4-1
Phase-failure sensitivity Yes, per IEC/EN 60947 and VDE 0660 part 102
Features Test/off button, trip-free release, manual/auto reset pushbutton
Temperature compensation Continuous, residual error ≤ 0.25 %/K above 40 °C
Rated operational voltage 690 V max.
Impulse withstand voltage 6000 V AC; 4000 V for auxiliary and control circuits
Auxiliary contact ratings AC-15: 1.5 A at 120 V and 230 V, 0.9 A at 400 V; DC-13: 0.9 A at 24 V, 0.75 A at 60 V, 0.4 A at 110 V, 0.2 A at 220 V
Ambient temperature −25 to +55 °C; −25 to +40 °C enclosed
Mounting Direct mounting on the contactor
Main terminals M4, 1.8 Nm; Pozidriv 2 or 1 × 6 mm slotted; strip 10 mm
Control terminals M3.5, 1.2 Nm; strip 8 mm
Approvals listed on sheet CE, UL, CSA, VDE 0660, IEC/EN 60947-4-1

Data comes from the manufacturer specification sheet for this catalog number; verify against the rating plate on the delivered relay.

How the ZB12-6 protects the motor

Each phase passes through a bimetal strip. Motor current heats the strips; if the heating persists beyond the Class 10 A trip curve, the bimetals bend, move a release mechanism and switch the auxiliary contacts. The N/C contact (95/96) is wired into the contactor coil circuit to drop the motor out, and the N/O contact (97/98) can signal an alarm. Temperature compensation is continuous, so the trip point stays stable as the panel warms or cools. The relay is also sensitive to phase failure: an unbalanced current causes a faster trip, which protects the motor if one supply phase is lost.

The yellow dial sets the trip current inside the range. A test/off button checks the contact wiring, and the reset button can be set to manual or automatic. Trip-free release means the relay cannot be held closed against a fault by keeping the reset pressed.

Where the ZB12-6 fits in the system

The ZB12-6 sits on the small DILM contactors, such as the DILM7 and DILM9 types. Smaller ZB12 relays cover lower currents, and above it ZB12-10 and ZB12-16 cover larger motors. The sheet allows a maximum of 20 A gG/gL for type 2 and 25 A gG/gL for type 1 coordination, which is far below the values for the 16 A relays, so fuse selection must follow the table above. A PKZM0 breaker can also be used upstream. Confirm the combination in the manufacturer selection table.

Selection checklist for the ZB12-6

  • Set the dial to the motor nameplate current; the usable window is 4 – 6 A.
  • Use the N/C contact in the control circuit and keep the N/O for signalling only.
  • Check that the contactor frame accepts this relay by direct mounting; otherwise a separate mounting kit is needed.
  • Match the short-circuit device to the type 1 or type 2 values shown above.
  • Choose manual reset for pumps and conveyors where an unattended restart is a hazard.
  • Remember the relay protects the motor against overload, not against short circuit.

Installation and commissioning of the ZB12-6

Slide the relay onto the contactor terminals so the three power pins engage, then tighten the main screws to 1.8 Nm. Control wires go to terminals 95/96 and 97/98 with 1.2 Nm. After wiring, set the dial to the nameplate current, press test to confirm the N/C opens, then reset. During commissioning measure the actual motor current and trim the setting if it differs from the nameplate. Periodic checks should include terminal tightness and a trip test after any long outage.

Typical applications in Oman and the GCC

Motors of 1.5 to 2.2 kW appear in small circulation pumps, dosing pumps, extraction fans, gate and door drives and conveyor sections in water treatment and light industry across Oman and the GCC. Because the relay sits in cabinets that are often in hot service rooms, the stable temperature compensation of the bimetals helps avoid nuisance trips in summer, and the low heat dissipation of about 1.7 W per pole at 6 A keeps the panel load small.

Family table around ZB12-6

Relay Setting range Frame
ZB12-6 4 – 6 A ZB12
ZB12-10 6 – 10 A (see site listing) ZB12
ZB12-16 12 – 16 A ZB12

Information to send with an RFQ for the ZB12-6

  • Exact part number: ZB12-6
  • Quantity and delivery location
  • Motor power, voltage and nameplate current
  • Contactor type the relay will be mounted on
  • Starting method and whether manual or auto reset is needed

Documents and quotation

The manufacturer specification sheet for ZB12-6 is attached on this page for reference.

Send the part number ZB12-6 with the quantity and we will confirm availability and lead time. Seven Star LLC supplies Eaton products in Oman and the GCC from Muscat.

Other Models in the Eaton Zb Overload Range

Seven Star LLC supplies models from the Eaton Zb Overload range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Eaton ZB12-16 Overload Relay 12-16 AContactors & Overload RelaysView details
Eaton ZB32-16 Overload Relay 10-16 AContactors & Overload RelaysView details
Eaton ZB12-6 Overload Relay 4-6 AContactors & Overload RelaysYou are viewing this model
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.

Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.

Eaton company profile

Founded 1911, New York, USA, by Joseph O. Eaton
Early move Cleveland, Ohio, 1914
Headquarters Dublin, Ireland, since the 2012 Cooper Industries acquisition
Listing New York Stock Exchange (ETN)
Brands Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC
Product families FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling

Milestones

  • 1911: Joseph O. Eaton starts an axle business in New York.
  • 1914: The business moves to Cleveland.
  • 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.

Eaton circuit protection listed here

The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.

Where Eaton breakers and fuses are used

Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.

Eaton products we list

Family Examples
Circuit Breakers LPJ-35SP Class J Time-Delay Fuse, NZMN1-A80 Molded Case Circuit Breaker, NZMN2-A250 Molded Case Circuit Breaker, NZMN3-AE400 Molded Case Circuit Breaker, PKZM0-1
AC Drives DA1-342D2FB-A20C AC Drive, PowerXL DG1-34140FN-C21C Variable Freque…

Ordering Eaton parts: what we need

Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.

Facts checked against Eaton's corporate history and investor materials, October 2026.

FAQ

Questions about the Eaton ZB12-6 Overload Relay 4-6 A

Answers from our engineering team on installation, compatibility and integration.

01What is the setting range of the ZB12-6?
4 to 6 A, set with the yellow dial on the front of the relay, with Class 10 A tripping.
02Which motors suit the ZB12-6?
Small motors whose nameplate current falls between 4 and 6 A, typically around 1.5 to 2.2 kW at 400 V.
03What fuse is allowed with the ZB12-6?
Type 2 coordination is 20 A gG/gL and type 1 is 25 A gG/gL; the UL/CSA Class J/CC fuse is limited to 10 A at 600 V.
04Does the ZB12-6 have a test function?
Yes, a test/off button checks the contacts, and the release is trip-free with a manual or auto reset pushbutton.
05How much heat does the ZB12-6 give off?
About 5.1 W across three poles, 1.7 W per pole, at the 6 A rated current.