Brand: Eaton
Eaton DILM95-22 Contactor 95 A, 45 kW
Description
Eaton DILM95-22(230V50HZ,240V60HZ) contactor for 45 kW at 400 V AC-3
The Eaton DILM95-22(230V50HZ,240V60HZ) is a three-pole AC contactor from the Moeller DILM range, built to switch motors up to 45 kW at 400 V and 75 kW at 690 V in AC-3 duty. The -22 version includes a 2 N/O + 2 N/C auxiliary block, so the 95 A contactor arrives with its control contacts fitted. Seven Star LLC supplies the DILM95-22(230V50HZ,240V60HZ) in Oman and the GCC.
With 95 A of AC-3 current and 130 A of AC-1 current it sits in the upper part of the DILM line. The housing measures 175 × 170 × 90 mm (length/depth × height × width) and weighs 2.22 kg, so panel space can be planned from the catalog entry before the order is placed.
How to read the model code DILM95-22(230V50HZ,240V60HZ)
The code splits into three parts. DILM95-22 is the contactor series and size: the number 95 is the rated AC-3 operational current in amperes at 400 V, here 95 A. The absence of a C means screw terminals on both the main and the coil circuit. The suffix -22 states that a fitted 2 N/O + 2 N/C auxiliary contact set is included, so the catalog entry lists two normally open and two normally closed contacts. The bracket gives the coil: 230V50HZ,240V60HZ means the coil is designed for 230 V 50 Hz / 240 V 60 Hz AC coil.
DILM95-22(230V50HZ,240V60HZ) technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Eaton DILM95-22(230V50HZ,240V60HZ) (catalog number 239527) |
| Series | Eaton Moeller DILM contactor, Contactors for motors, screw terminals |
| Number of main poles | 3 (three N/O main contacts) |
| Auxiliary contacts | 2 N/O + 2 N/C (included) |
| AC-3 rated current, 380/400/415 V | 95 A |
| AC-3 rated power at 380/400 V, 50 Hz | 45 kW |
| AC-3 rated power at 240 V, 50 Hz | 32 kW |
| AC-3 rated current at 500 V | 95 A |
| AC-3 rated current at 660/690 V | 80 A (75 kW at 690 V) |
| AC-1 rated current, 380/400/415 V | 130 A |
| AC-4 rated current at 380 to 415 V | 50 A |
| Rated operational voltage Ue, AC, max | 690 V |
| Rated insulation voltage Ui | 690 V |
| Rated impulse withstand voltage Uimp | 8000 V AC |
| Coil | 230 V 50 Hz / 240 V 60 Hz AC coil |
| Pick-up / drop-out voltage | 0.8 to 1.1 × Uc (pick-up); 0.6 to 0.3 × Uc (drop-out), of the coil rated voltage |
| Coil consumption, pick-up (50 Hz / 60 Hz) | 310 VA / 345 VA |
| Coil consumption, sealed (50 Hz) | 26 VA / 5.8 W |
| Closing / opening delay (main contacts) | 14 to 20 ms / 9 to 14 ms |
| Mechanical lifespan | 10,000,000 operations 7,000,000 Operations (Coil 50/60 Hz) |
| Operating frequency | 3600 operations per hour (mechanical) |
| Main terminals, stranded | 1 x (16 – 70) mm² or 2 x (16 – 50) mm² |
| Main terminals, flexible with ferrule | 1 x (10 – 70) mm² or 2 x (10 – 50) mm² |
| Control terminals, flexible with ferrule | 1 x (0.75 – 2.5) mm² or 2 x (0.75 – 2.5) mm² |
| Copper band | 2 x (6 x 16 x 0.8) mm |
| Tightening torque | 14 Nm (main circuit) |
| Control terminals | Screw |
| Short-circuit protection, type 2 coordination, 400 V / 690 V | 160 A gG/gL / 160 A gG/gL |
| Ambient temperature, open | -25 °C to 60 °C |
| Ambient temperature, enclosed (max) | 40 °C |
| Heat dissipation (current-dependent / static) | 12.6 W / 5.8 W |
| Degree of protection | IP00 |
| Dimensions | 175 × 170 × 90 mm (length/depth × height × width) |
| Weight | 2.22 kg |
What the DILM95-22(230V50HZ,240V60HZ) switches and how the coil behaves
Utilisation categories matter more than the headline ampere figure. In AC-3 the contactor starts squirrel-cage motors and breaks the current while the motor is running, which is the normal case for pumps, fans and compressors; the 95 A rating is for that duty. In AC-4, plugging and inching, the permitted current is much lower (50 A at 380 to 415 V), so a drive that is reversed or jogged often needs a larger contactor than its nameplate kilowatts suggest. In AC-1, for resistive loads such as heaters, the contactor carries 130 A.
The coil is a dual-frequency AC coil. Pick-up is specified at 0.8 to 1.1 × Uc of the rated control voltage and drop-out at 0.6 to 0.3 × Uc, so a control supply that sags during the start of a large motor in the same panel should still be checked against the lower limit. At pick-up the coil draws 310 VA at 50 Hz, falling to 26 VA / 5.8 W once the armature is sealed. That inrush matters when a PLC relay output or a small control transformer has to drive several contactors at once.
Closing takes 14 to 20 ms and opening 9 to 14 ms at the main contacts, which is useful when contactor timing is part of an interlocking or star-delta sequence. The catalog lists a mechanical life of 10,000,000 operations and an operating frequency of 3600 operations per hour (mechanical).
Where the DILM95-22(230V50HZ,240V60HZ) fits in the DILM range
The DILM contactors from DILM40 to DILM95 form a continuous ladder of ratings, and the DILM95-22(230V50HZ,240V60HZ) is one rung of it. Neighbouring catalog entries are the DILM40-22, DILM50, DILM65, DILM80 and DILM95; the DILMC variants carry the same power ratings with spring-loaded control terminals. For motor protection the usual companion devices are ZB overload relays and PKZM4 motor-protective circuit-breakers from the same manufacturer, and for control the auxiliary contact modules in the same series. Always confirm mechanical fit of an overload relay to the exact contactor before ordering.
| Model | AC-3, 400 V | AC-3 power | AC-1, 400 V | Auxiliary contacts |
|---|---|---|---|---|
| DILM40-22 | 40 A | 18.5 kW | 60 A | 2 N/O + 2 N/C |
| DILM50 | 50 A | 22 kW | 80 A | none |
| DILM65 | 65 A | 30 kW | 98 A | none |
| DILM80 | 80 A | 37 kW | 110 A | none |
| DILM95 | 95 A | 45 kW | 130 A | none |
Selection checklist for the DILM95-22(230V50HZ,240V60HZ)
- Motor full-load current at the actual voltage: the 95 A AC-3 rating must exceed it with margin for the duty cycle.
- Duty category: AC-3 for normal starting, AC-4 for plugging or jogging, AC-1 for heaters; for AC-4 use the 50 A figure.
- Control voltage and frequency: this entry is for 230 V 50 Hz / 240 V 60 Hz AC coil; a different coil needs a different catalog entry.
- Auxiliary contacts: two N/O and two N/C are already included.
- Terminals: screw on the control side, screw main terminals taking 1 x (16 – 70) mm² or 2 x (16 – 50) mm² stranded.
- Short-circuit protection: the catalog gives 160 A gG/gL for type 2 coordination at 400 V.
- Ambient temperature: open mounting up to 60 °C, enclosed up to 40 °C.
Installation, commissioning and maintenance of the DILM95-22(230V50HZ,240V60HZ)
Mount the contactor on a flat plate or on a suitable rail as shown in its instruction sheet and leave the clearances recommended for this size (IP00 open-frame design). Tighten the terminal screws to 14 Nm (main circuit) and keep conductor stripping lengths as specified. Use ferrules on flexible cable; the main terminal accepts 1 x (10 – 70) mm² or 2 x (10 – 50) mm² with ferrule.
During commissioning, measure the coil voltage at the terminals while the motor starts, not only at no load. A contactor that chatters or drops out during a start is almost always a voltage-drop problem in the control circuit. Check that the interlock between forward and reverse contactors is wired correctly before the first run. In service, inspect the contacts at planned shutdowns for pitting and blackening, check that the terminals are still tight after thermal cycling, and keep dust out of the armature area.
Typical applications in Oman and the GCC
Contactors of this size start the pumps, compressors and ventilation fans that run the large utility systems of Omani industrial sites: seawater and process-water booster pumps in desalination and water-treatment plants, cooling-tower fans, and compressors in gas processing. In the Gulf climate, switchgear rooms run warm and panels are often dusty, so the -25 °C to 60 °C ambient range, with the lower enclosed limit of 40 °C, should be compared with the real panel temperature rather than the room temperature. Where several contactors share a cabinet, use the heat-dissipation figure of 12.6 W per device when sizing air conditioning or ventilation. Typical uses are direct-on-line starters, the line and delta contactors of star-delta starters, soft starter bypass contactors and heater switching.
Information to send with an RFQ for DILM95-22(230V50HZ,240V60HZ)
- Exact part number DILM95-22(230V50HZ,240V60HZ) and the quantity required.
- Control voltage and frequency available in the panel.
- Motor power, voltage and duty (normal starting, jogging or reversing).
- Whether auxiliary contact modules or a mechanical interlock are required.
- Delivery location and required date.
Documents and quotation
The official Eaton Moeller series contactor datasheet for the DILM95 frame, shown as DILM95(230V50HZ,240V60HZ) with catalog no. 239480 (English) is attached on this page as a PDF for the Eaton DILM95-22. It lists the AC-1, AC-3 and AC-4 operational currents, the motor ratings from 220 V to 690 V, the coil pick-up and sealing power, the short-circuit coordination, the conductor cross-sections, the dimensions and the IEC/EN 60947, UL and CSA approvals. The DILM95-22 uses the same 45 kW main circuit and adds a built-in auxiliary block with 2 N/O and 2 N/C contacts. Check the coil voltage, the auxiliary contact arrangement and the terminal type against your panel, then send us the quantity and the delivery location for a quotation.
Seven Star LLC supplies Eaton industrial control products in Oman and the GCC, quoting against the exact catalog number.
Other Models in the Eaton Dilm Contactor Large Range
Seven Star LLC supplies models from the Eaton Dilm Contactor Large range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Eaton DILM40-22 Contactor 40 A, 18.5 kW | Contactors & Overload Relays | View details |
| Eaton DILM50 Contactor 50 A, 22 kW | Contactors & Overload Relays | View details |
| Eaton DILM65 Contactor 65 A, 30 kW | Contactors & Overload Relays | View details |
| Eaton DILM80-22 Contactor 80 A, 37 kW | Contactors & Overload Relays | View details |
| Eaton DILM95-22 Contactor 95 A, 45 kW | Contactors & Overload Relays | You are viewing this model |
| Eaton DILMC80 Contactor 80 A, 37 kW | Contactors & Overload Relays | View details |
| Eaton DILMC95 Contactor 95 A, 45 kW | Contactors & Overload Relays | View details |
Datasheets & Documents
- Datasheet Eaton DILM95 Contactor Datasheet (PDF) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.
Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.
Eaton company profile
| Founded | 1911, New York, USA, by Joseph O. Eaton |
|---|---|
| Early move | Cleveland, Ohio, 1914 |
| Headquarters | Dublin, Ireland, since the 2012 Cooper Industries acquisition |
| Listing | New York Stock Exchange (ETN) |
| Brands | Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC |
| Product families | FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling |
Milestones
- 1911: Joseph O. Eaton starts an axle business in New York.
- 1914: The business moves to Cleveland.
- 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.
Eaton circuit protection listed here
The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.
Where Eaton breakers and fuses are used
Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.
Eaton products we list
Ordering Eaton parts: what we need
Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.
Facts checked against Eaton's corporate history and investor materials, October 2026.
Browse Eaton products by category: Circuit Breaker.
FAQ
Questions about the Eaton DILM95-22 Contactor 95 A, 45 kW
Answers from our engineering team on installation, compatibility and integration.
01What is the AC-3 rating of the DILM95-22(230V50HZ,240V60HZ)?
The catalog entry lists 95 A at 380/400/415 V AC-3, which corresponds to 45 kW at 400 V and 32 kW at 240 V, 50 Hz. At 690 V the AC-3 current is 80 A.
02What coil does the DILM95-22(230V50HZ,240V60HZ) use?
The coil is specified as 230 V 50 Hz / 240 V 60 Hz AC coil. The coil draws 310 VA at pick-up at 50 Hz and 26 VA / 5.8 W when sealed, so the control supply must cope with the inrush.
03Does the DILM95-22(230V50HZ,240V60HZ) include auxiliary contacts?
Yes, the -22 version includes 2 N/O and 2 N/C auxiliary contacts in the catalog entry. Count the contacts needed before ordering.
04Which terminals does the DILM95-22(230V50HZ,240V60HZ) have?
Main terminals are screw type and take 1 x (16 – 70) mm² or 2 x (16 – 50) mm² stranded; the control terminals are screw. The catalog gives a tightening torque of 14 Nm (main circuit).
05Can the DILM95-22(230V50HZ,240V60HZ) be used for jogging or reversing duty?
Reversing and jogging are AC-4 duty, where the permitted current is lower: 50 A at 380 to 415 V for this contactor. Size it from the AC-4 value, not from the AC-3 kilowatt rating.